 "manufacturer": "Finder",
 "manufacturer_slug": "finder",
 "model": "7M.24 single-phase energy meter (Modbus RS485)",
 "model_slug": "7m24",
 "short_model": "7M.24",
 "aliases": [
  "7M.24",
  "7M24",
  "Finder 7M24 Modbus"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "Finder 7M.24 single-phase meters with RS485 communication, per the 7M24 section of 'Modbus Communication Protocol 7M24 - 7M38' v2.",
 "summary": "The 7M.24 is Finder's single-phase MID energy meter for DIN rail. The RS485 version answers Modbus RTU and offers its measurements both in packed integer formats and as IEEE 754 floats. This map uses the float block (voltage, current, powers, power factor, THD, frequency, energy counters) plus identification, status, tariff, reset and serial-port registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Registers are printed as 3xxxx (input, function 04) and 4xxxx (holding, functions 03/06/16) with 30000 / 40000 as the memory reference, not 30001. The document's request example reads U1 (30107) by sending start address 0x006B = 107. Wire address = printed number minus 30000 or 40000: Pt float 32490 is input register 2490."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Modbus Communication Protocol 7M24 - 7M38",
  "doc_number": "v2",
  "revision_date": "2021-06-30",
  "url": "https://cdn.findernet.com/app/uploads/Modbus-7M24-7M38_v2_30062021.pdf",
  "pages": "Addressing example p. 3; 7M24 input registers pp. 5-10, holding registers pp. 11-21, data types pp. 22-23 (printed page numbers)"
 },
 "notes": [
  "Wire address = printed number - 30000 (input) or - 40000 (holding); see the 30107 / 0x006B example.",
  "T_float is IEEE 754 single precision, high word first (ABCD); the data-type page's example stores 123.45 as 42F6 E666. T3 (signed 32-bit) is also high word first.",
  "Left out: the integer measurement block (T5/T6/T7 packed exponent formats), the mantissa/exponent energy counters and the '1000 x energy counter' block, as for the 7M.38 map.",
  "Left out: duplicate float rows (a second Pt/Qt/St/PFt/frequency set at 32536-32584 and float counters n1-n4 at 32638-32645 without a function code), CAP/IND power factor floats (sign convention not explained), and the alarm, logic, LCD, data-logger and other configuration groups.",
  "Energy counters 1-8 are user counters reset through 40031; what each one integrates is set in its parameter/configuration registers (40421 onward), so check the assignment on the meter.",
  "Writing settings needs the access level raised by writing the user password to 40001-40002 (function 16), then saving with operator command 40012 = 1."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 1,
   "documented": "30001",
   "name": "Model number",
   "description": "16-character text, two characters per register.",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "30009",
   "name": "Serial number",
   "description": "8-character text.",
   "data_type": "STRING",
   "length": 4,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 13,
   "documented": "30013",
   "name": "Software version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "30044",
   "name": "Status register",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Locked",
    "4": "Clock not set"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "30076",
   "name": "MID lock status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Unlocked",
    "1": "Locked"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 99,
   "documented": "30099",
   "name": "Modbus max registers per read",
   "description": "Largest register count the meter accepts in one read.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 101,
   "documented": "30101",
   "name": "Phase valid measurement",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Invalid measurement phase 1"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 103,
   "documented": "30103",
   "name": "Run time",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 197,
   "documented": "30197",
   "name": "External relay status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On",
    "250": "Comm. error",
    "255": "Not connected"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 400,
   "documented": "30400",
   "name": "Checksum status",
   "description": "0 = no error.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Parameter CRC error",
    "1": "Firmware CRC error",
    "2": "MID-lock error",
    "6": "Measurement module checksum error",
    "7": "Software checksum error",
    "8": "Calibration data checksum error",
    "9": "MID setting data checksum error",
    "10": "Setting data checksum error"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 405,
   "documented": "30405",
   "name": "Current active tariff",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2480,
   "documented": "32480",
   "name": "Run time (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2484,
   "documented": "32484",
   "name": "Uavg phase-to-neutral",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2488,
   "documented": "32488",
   "name": "Sum of currents",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2490,
   "documented": "32490",
   "name": "Active power total (Pt)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2492,
   "documented": "32492",
   "name": "Reactive power total (Qt)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2494,
   "documented": "32494",
   "name": "Apparent power total (St)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2496,
   "documented": "32496",
   "name": "Power factor total (PFt)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2498,
   "documented": "32498",
   "name": "Frequency",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2500,
   "documented": "32500",
   "name": "U1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2516,
   "documented": "32516",
   "name": "I1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2530,
   "documented": "32530",
   "name": "Active power L1 (P1)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2538,
   "documented": "32538",
   "name": "Reactive power L1 (Q1)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2546,
   "documented": "32546",
   "name": "Apparent power L1 (S1)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2554,
   "documented": "32554",
   "name": "Power factor L1 (PF1)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2570,
   "documented": "32570",
   "name": "Angle U1-I1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2576,
   "documented": "32576",
   "name": "Power angle total (atan2(Pt,Qt))",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2588,
   "documented": "32588",
   "name": "I1 THD",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2594,
   "documented": "32594",
   "name": "U1 THD",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2658,
   "documented": "32658",
   "name": "Internal temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2750,
   "documented": "32750",
   "name": "Active tariff (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2752,
   "documented": "32752",
   "name": "Energy counter n1",
   "description": "Non-resettable counter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2754,
   "documented": "32754",
   "name": "Energy counter n2",
   "description": "Non-resettable counter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2756,
   "documented": "32756",
   "name": "Energy counter n3",
   "description": "Non-resettable counter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2758,
   "documented": "32758",
   "name": "Energy counter n4",
   "description": "Non-resettable counter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2760,
   "documented": "32760",
   "name": "Energy counter 1",
   "description": "Resettable user counter; Wh, varh or VAh per its parameter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2762,
   "documented": "32762",
   "name": "Energy counter 2",
   "description": "Resettable user counter; Wh, varh or VAh per its parameter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2764,
   "documented": "32764",
   "name": "Energy counter 3",
   "description": "Resettable user counter; Wh, varh or VAh per its parameter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2766,
   "documented": "32766",
   "name": "Energy counter 4",
   "description": "Resettable user counter; Wh, varh or VAh per its parameter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2768,
   "documented": "32768",
   "name": "Energy counter 5",
   "description": "Resettable user counter; Wh, varh or VAh per its parameter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2770,
   "documented": "32770",
   "name": "Energy counter 6",
   "description": "Resettable user counter; Wh, varh or VAh per its parameter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2772,
   "documented": "32772",
   "name": "Energy counter 7",
   "description": "Resettable user counter; Wh, varh or VAh per its parameter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2774,
   "documented": "32774",
   "name": "Energy counter 8",
   "description": "Resettable user counter; Wh, varh or VAh per its parameter.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2985,
   "documented": "32985",
   "name": "Nominal phase voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2987,
   "documented": "32987",
   "name": "Nominal phase current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2989,
   "documented": "32989",
   "name": "Nominal phase power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2991,
   "documented": "32991",
   "name": "Nominal total power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2993,
   "documented": "32993",
   "name": "Nominal total current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2995,
   "documented": "32995",
   "name": "Nominal frequency",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40010",
   "name": "Active access level",
   "description": "0 = full protection.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40012",
   "name": "Operator command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Save settings",
    "2": "Abort settings",
    "3": "Restart instrument"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40015",
   "name": "IR external relay command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40030",
   "name": "Select active tariff",
   "description": "Tariff 1 to 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "40031",
   "name": "Reset energy counters",
   "description": "Set a bit to reset that resettable counter.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "Reset counter 1",
    "1": "Reset counter 2",
    "2": "Reset counter 3",
    "3": "Reset counter 4",
    "4": "Reset counter 5",
    "5": "Reset counter 6",
    "6": "Reset counter 7",
    "7": "Reset counter 8"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "40202",
   "name": "Port 1 Modbus address",
   "description": "1 to 247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 203,
   "documented": "40203",
   "name": "Port 1 baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1200",
    "1": "2400",
    "2": "4800",
    "3": "9600",
    "4": "19200",
    "5": "38400",
    "6": "57600",
    "7": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "40204",
   "name": "Port 1 stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1 stop bit",
    "1": "2 stop bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 205,
   "documented": "40205",
   "name": "Port 1 parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Odd",
    "2": "Even"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 421,
   "documented": "40421",
   "name": "Energy counter n1 parameter",
   "description": "Quantity this counter integrates.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parameter",
    "1": "Active power",
    "2": "Reactive power",
    "3": "Apparent power",
    "5": "Active power phase 1",
    "6": "Reactive power phase 1",
    "7": "Apparent power phase 1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 422,
   "documented": "40422",
   "name": "Energy counter n1 configuration",
   "description": "Which quadrants are counted; decides import vs export.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Quadrant I enabled",
    "1": "Quadrant II enabled",
    "2": "Quadrant III enabled",
    "3": "Quadrant IV enabled",
    "4": "Absolute value",
    "5": "Invert value"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read input registers with function 04 and decode the float block high word first: subtract 30000 from the printed number (U1 at 32500 is wire 2500). Energy comes as floats in Wh/varh from 32752.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 2500,
    "why": "U1 voltage"
   },
   {
    "table": "input_register",
    "address": 2516,
    "why": "I1 current"
   },
   {
    "table": "input_register",
    "address": 2490,
    "why": "Total active power"
   },
   {
    "table": "input_register",
    "address": 2496,
    "why": "Total power factor"
   },
   {
    "table": "input_register",
    "address": 2498,
    "why": "Frequency"
   },
   {
    "table": "input_register",
    "address": 2752,
    "why": "Energy counter n1 (Wh)"
   }
  ],
  "enable": "Modbus RTU runs on the RS485 versions. Port 1 address, baud, stop bits and parity are holding registers 40202-40205; raise the access level with the user password at 40001 first, then save with 40012 = 1.",
  "watchdog": null,
  "quirks": [
   "The memory reference is 30000/40000: printed 30107 is wire address 107.",
   "Floats and 32-bit integers are high word first (ABCD)."
  ],
  "setup": [
   "Modbus address 1-247; 8 data bits only; parity none/odd/even; 1 or 2 stop bits."
  ],
  "gotchas": [
   "Which counter is import or export depends on the counter configuration registers; verify against the display.",
   "Read 30099 for the largest register count the meter accepts per request."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/finder/7m24",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}