 "manufacturer": "Fronius",
 "manufacturer_slug": "fronius",
 "model": "Fronius Smart Meter via GEN24 / Tauro inverter (SunSpec meter model int+SF)",
 "model_slug": "smart-meter-gen24-sunspec-int-sf",
 "short_model": "Fronius Smart Meter GEN24 int+SF",
 "aliases": [
  "Fronius Smart Meter 63A",
  "Fronius Smart Meter 50kA",
  "Fronius Smart Meter TS",
  "SunSpec meter model 201/202/203"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "A Fronius Smart Meter wired to a GEN24 or Tauro inverter over Modbus RTU and republished by the inverter over Modbus TCP, with SunSpec Model Type set to int+SF (meter model 201/202/203).",
 "summary": "When a Fronius Smart Meter is connected to a GEN24 or Tauro inverter over Modbus RTU, the inverter republishes its readings over Modbus TCP as a SunSpec device at a configurable unit ID (meter address 1 = 200 by default, up to 204). With the int+SF data type the meter appears as SunSpec model 201, 202 or 203 after the common block. This map covers the common block, the 16-bit current, voltage, frequency, power and power-factor values with their scale factors, and the end block.",
 "transport": [
  "TCP",
  "RTU"
 ],
 "defaults": {
  "unit_id": 200,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "Fronius numbers registers from 1 (SunSpec base register 40001) and tells you to request the register number minus one, so register 40072 is read at wire address 40071. The manual's RTU example reads register 40005 with address bytes 9C 44 (40004)."
 },
 "default_word_order": null,
 "firmware": "Register map archive 1.2.7-2 (Smart_Meter_Register_Map_Int&SF.xlsx); manual 42,0410,2649 rev. 034-28092026.",
 "source": {
  "title": "Fronius GEN24 Modbus TCP & RTU (operating instructions) + Smart_Meter_Register_Map_Int&SF.xlsx",
  "doc_number": "42,0410,2649 (034-28092026)",
  "revision_date": "2026-09",
  "url": "https://www.fronius.com/en/~/downloads/Solar%20Energy/Operating%20Instructions/42,0410,2649.pdf",
  "pages": "PDF English part: printed pp. 68-69 (unit IDs 200-204 for meters, response times), printed pp. 76-77 (Meter address offset), printed p. 112 (Meter Model, meter-location sign table); register table = XLSX 'Complete Map' sheet in https://www.fronius.com/en/~/downloads/Solar%20Energy/Operating%20Instructions/gen24-modbus-api-external-docs.zip"
 },
 "notes": [
  "Register table comes from Fronius' official 'Smart_Meter_Register_Map_Int&SF.xlsx' in gen24-modbus-api-external-docs.zip; behaviour and device IDs come from the GEN24 manual.",
  "Addresses assume SunSpec Model Type = int+SF. With the default float setting the meter shows model 211/212/213 and the register layout is different.",
  "Word order: neither the manual nor the XLSX states the order of 32-bit values, so the 32-bit SID (40001-40002), every acc32 energy counter (TotWhExp/Imp 40108-40123, TotVAhExp/Imp 40125-40140 and the unsupported VArh counters) and the 32-bit event field (40175, documented as hard-coded zero) are left out, together with the energy scale factors.",
  "Phase B/C values are only meaningful on a three-phase meter (model 203).",
  "The sign of W and the meaning of the import/export energy counters depend on the meter location set in the inverter (0 grid, 1 load, 3 external generator, 256-511 sub-load); see the location table in the PDF.",
  "The A, W, VA and VAR scale factors are auto-scaled: read each value block together with its _SF register. Phase B/C power-factor values depend on the grid connection and meter type."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 40002,
   "documented": "40003",
   "name": "ID (common)",
   "description": "Common block ID, reads 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40003,
   "documented": "40004",
   "name": "L (common)",
   "description": "Common block length, reads 65.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40004,
   "documented": "40005",
   "name": "Mn",
   "description": "Manufacturer name (Fronius).",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40020,
   "documented": "40021",
   "name": "Md",
   "description": "Meter model name.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40036,
   "documented": "40037",
   "name": "Opt",
   "description": "Meter name, e.g. <primary>.",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40044,
   "documented": "40045",
   "name": "Vr",
   "description": "Meter software version.",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40052,
   "documented": "40053",
   "name": "SN",
   "description": "Meter serial number.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40068,
   "documented": "40069",
   "name": "DA",
   "description": "Modbus device address of the meter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40069,
   "documented": "40070",
   "name": "ID (meter model)",
   "description": "201 single-phase, 202 split-phase, 203 wye three-phase, 204 delta three-phase.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "201": "Single phase",
    "202": "Split phase",
    "203": "Three phase",
    "204": "Delta three phase"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40070,
   "documented": "40071",
   "name": "L (meter model)",
   "description": "Length of the meter model block, reads 105.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40071,
   "documented": "40072",
   "name": "A",
   "description": "Total AC current",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40075
   },
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40072,
   "documented": "40073",
   "name": "AphA",
   "description": "Phase A current",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40075
   },
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40073,
   "documented": "40074",
   "name": "AphB",
   "description": "Phase B current",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40075
   },
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40074,
   "documented": "40075",
   "name": "AphC",
   "description": "Phase C current",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40075
   },
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40075,
   "documented": "40076",
   "name": "A_SF",
   "description": "Scale factor for current registers.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40076,
   "documented": "40077",
   "name": "PhV",
   "description": "Average phase-to-neutral voltage",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40084
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40077,
   "documented": "40078",
   "name": "PhVphA",
   "description": "Phase A to neutral voltage",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40084
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40078,
   "documented": "40079",
   "name": "PhVphB",
   "description": "Phase B to neutral voltage",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40084
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40079,
   "documented": "40080",
   "name": "PhVphC",
   "description": "Phase C to neutral voltage",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40084
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40080,
   "documented": "40081",
   "name": "PPV",
   "description": "Average phase-to-phase voltage",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40084
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40081,
   "documented": "40082",
   "name": "PhVphAB",
   "description": "Voltage A-B",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40084
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40082,
   "documented": "40083",
   "name": "PhVphBC",
   "description": "Voltage B-C",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40084
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40083,
   "documented": "40084",
   "name": "PhVphCA",
   "description": "Voltage C-A",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40084
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40084,
   "documented": "40085",
   "name": "V_SF",
   "description": "Scale factor for voltage registers.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40085,
   "documented": "40086",
   "name": "Hz",
   "description": "Grid frequency.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40086
   },
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40086,
   "documented": "40087",
   "name": "Hz_SF",
   "description": "Scale factor for frequency.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40087,
   "documented": "40088",
   "name": "W",
   "description": "Total active power (sign depends on meter location)",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40091
   },
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40088,
   "documented": "40089",
   "name": "WphA",
   "description": "Phase A active power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40091
   },
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40089,
   "documented": "40090",
   "name": "WphB",
   "description": "Phase B active power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40091
   },
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40090,
   "documented": "40091",
   "name": "WphC",
   "description": "Phase C active power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40091
   },
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40091,
   "documented": "40092",
   "name": "W_SF",
   "description": "Scale factor for active power.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40092,
   "documented": "40093",
   "name": "VA",
   "description": "Total apparent power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40096
   },
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40093,
   "documented": "40094",
   "name": "VAphA",
   "description": "Phase A apparent power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40096
   },
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40094,
   "documented": "40095",
   "name": "VAphB",
   "description": "Phase B apparent power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40096
   },
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40095,
   "documented": "40096",
   "name": "VAphC",
   "description": "Phase C apparent power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40096
   },
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40096,
   "documented": "40097",
   "name": "VA_SF",
   "description": "Scale factor for apparent power.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40097,
   "documented": "40098",
   "name": "VAR",
   "description": "Total reactive power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40101
   },
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40098,
   "documented": "40099",
   "name": "VARphA",
   "description": "Phase A reactive power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40101
   },
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40099,
   "documented": "40100",
   "name": "VARphB",
   "description": "Phase B reactive power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40101
   },
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40100,
   "documented": "40101",
   "name": "VARphC",
   "description": "Phase C reactive power",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40101
   },
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40101,
   "documented": "40102",
   "name": "VAR_SF",
   "description": "Scale factor for reactive power.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40102,
   "documented": "40103",
   "name": "PF",
   "description": "Total power factor",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40106
   },
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40103,
   "documented": "40104",
   "name": "PFphA",
   "description": "Phase A power factor",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40106
   },
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40104,
   "documented": "40105",
   "name": "PFphB",
   "description": "Phase B power factor",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40106
   },
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40105,
   "documented": "40106",
   "name": "PFphC",
   "description": "Phase C power factor",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40106
   },
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40106,
   "documented": "40107",
   "name": "PF_SF",
   "description": "Scale factor for power factor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40176,
   "documented": "40177",
   "name": "ID (end block)",
   "description": "End block marker, reads 0xFFFF.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40177,
   "documented": "40178",
   "name": "L (end block)",
   "description": "End block length, reads 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Enable the Modbus TCP server in the inverter web UI with SunSpec Model Type int+SF, then poll the meter at its unit ID (default 200). Read 40072-40107 (wire 40071-40106) in one request and apply each _SF register as a power of ten.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 40069,
    "why": "Model ID (203 = three-phase) confirms the int+SF layout"
   },
   {
    "table": "holding_register",
    "address": 40087,
    "why": "Total active power"
   },
   {
    "table": "holding_register",
    "address": 40091,
    "why": "Power scale factor"
   },
   {
    "table": "holding_register",
    "address": 40071,
    "why": "Total current"
   },
   {
    "table": "holding_register",
    "address": 40075,
    "why": "Current scale factor"
   },
   {
    "table": "holding_register",
    "address": 40077,
    "why": "Phase A voltage"
   },
   {
    "table": "holding_register",
    "address": 40084,
    "why": "Voltage scale factor"
   },
   {
    "table": "holding_register",
    "address": 40085,
    "why": "Frequency"
   }
  ],
  "enable": "Inverter web interface > Communication > Modbus: enable the TCP server and choose SunSpec Model Type int+SF. The meter unit ID is set with Meter address offset (factory 200).",
  "watchdog": null,
  "quirks": [
   "Scale factors are signed int16 exponents: value = raw x 10^SF.",
   "The meter is a separate Modbus device (unit ID 200-204 by default) with its own common block starting again at 40001; the inverter itself is always unit ID 1 over TCP.",
   "The model ID at 40070 tells you which layout is active: 201-203 = int+SF, 211-213 = float (different addresses)."
  ],
  "setup": [
   "Fronius Smart Meter address 1 maps to unit ID 200 (default), address 5 to 204.",
   "Query sequentially with a timeout of at least 1 s; block reads are faster than single registers."
  ],
  "gotchas": [
   "Power sign flips with the configured meter location (grid vs load); check the location before trusting import/export direction.",
   "Energy counters are 32-bit and not included here because Fronius does not document their word order."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/fronius/smart-meter-gen24-sunspec-int-sf",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}