 "manufacturer": "Fuji Electric",
 "manufacturer_slug": "fuji-electric",
 "model": "FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)",
 "model_slug": "frenic-hvac-aqua",
 "short_model": "FRENIC-HVAC / AQUA",
 "aliases": [
  "FRENIC-HVAC",
  "FRENIC-AQUA",
  "FRN-AR",
  "FRN-AQ"
 ],
 "equipment_type": "Variable frequency drive (HVAC / pump)",
 "applies_to": "Fuji Electric FRENIC-HVAC (AR) and FRENIC-AQUA (AQ) inverters on the RS-485 port in Modbus RTU mode (y10 = 0); RS-485 Communication User's Manual 24A7-E-0021b.",
 "summary": "FRENIC-HVAC and FRENIC-AQUA drives for fans and pumps speak Modbus RTU on their RS-485 port. Every function code (F, E, H, y, S, M ...) is a holding register found by a fixed group/number rule; the S codes carry frequency, run and PID commands and the M codes carry monitors, status words and alarm history. This map lists the communication command and monitor codes and the link settings.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "parameter-derived",
  "note": "Each function code is a holding register at 40000 + group code x 256 + number (manual Table 3.2: F=0, E=1, H=4, S=7, M=8, y=14). In the frame the high byte is the group code and the low byte the number, so the wire address is group x 256 + number; the manual's examples send 08 06 for M06 and 07 01 for S01."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "RS-485 Communication User's Manual (FRENIC-HVAC / FRENIC-AQUA)",
  "doc_number": "24A7-E-0021b",
  "revision_date": null,
  "url": "https://americas.fujielectric.com/files/24A7-E-0021b.pdf",
  "pages": "pp. 2-19 to 2-22 (H30, y codes), 3-4 to 3-5 (address rule, Table 3.2), 3-12 (examples), 5-2 to 5-15 (S and M codes), 5-66 to 5-67 (data formats 14-16)"
 },
 "notes": [
  "All function code data are single 16-bit words; no 32-bit values are used in this map.",
  "Per-unit values (S01, S12, S13, M01, M06, M68, M72, M73) use +/-20000 = 100 % or maximum frequency; convert with the drive's maximum frequency (F03).",
  "M09 output frequency is unsigned over Modbus RTU (0.00-655.35 Hz); the signed range in the table applies to the Fuji general-purpose inverter protocol.",
  "Codes marked not supported on HVAC/AQUA in the manual (torque and flux commands, motor temperature M22) are left out.",
  "Accel/decel times (F07/F08, S08/S09) use Fuji's packed floating-point format [12] and are not listed.",
  "M14 bit 6 (TL, torque limiting) is left out: the bit table lists it, but the bit diagram of format 16 shows bit 6 as unused (0).",
  "M86 uses alarm-history format 41: the low byte is the light alarm code and the high byte counts consecutive repeats of the same alarm."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 1054,
   "documented": "H30",
   "name": "Communications link function (mode selection)",
   "description": "Selects frequency and run command sources when the link is enabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Freq: inverter / Run: inverter",
    "1": "Freq: RS-485 (RJ-45) / Run: inverter",
    "2": "Freq: inverter / Run: RS-485 (RJ-45)",
    "3": "Freq: RS-485 (RJ-45) / Run: RS-485 (RJ-45)",
    "4": "Freq: RS-485 port 2 / Run: inverter",
    "5": "Freq: RS-485 port 2 / Run: RS-485 (RJ-45)",
    "6": "Freq: inverter / Run: RS-485 port 2",
    "7": "Freq: RS-485 (RJ-45) / Run: RS-485 port 2",
    "8": "Freq: RS-485 port 2 / Run: RS-485 port 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1793,
   "documented": "S01",
   "name": "Frequency reference (p.u.)",
   "description": "+/-20000 = maximum frequency. Takes priority over S05 when not 0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1797,
   "documented": "S05",
   "name": "Frequency reference (0.01 Hz)",
   "description": "Frequency command in 0.01 Hz steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1798,
   "documented": "S06",
   "name": "Operation command",
   "description": "Run, direction, X terminals and reset (format 14).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "FWD run forward",
    "1": "REV run reverse",
    "2": "X1",
    "3": "X2",
    "4": "X3",
    "5": "X4",
    "6": "X5",
    "7": "X6",
    "8": "X7",
    "11": "EN",
    "13": "XF (FWD terminal function)",
    "14": "XR (REV terminal function)",
    "15": "RST alarm reset"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1799,
   "documented": "S07",
   "name": "Universal DO",
   "description": "Command to DO terminals assigned as universal DO.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1804,
   "documented": "S12",
   "name": "Universal AO",
   "description": "+/-20000 = full scale.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1805,
   "documented": "S13",
   "name": "PID command",
   "description": "+/-20000 = +/-100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1806,
   "documented": "S14",
   "name": "Alarm reset command",
   "description": "Write 1 to reset; always reads 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No action",
    "1": "Reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1811,
   "documented": "S19",
   "name": "Speed command",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1823,
   "documented": "S31",
   "name": "External PID command 1",
   "description": "+/-20000 = +/-100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2049,
   "documented": "M01",
   "name": "Frequency reference, final (p.u.)",
   "description": "+/-20000 = maximum frequency.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2053,
   "documented": "M05",
   "name": "Frequency reference, final (0.01 Hz)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2054,
   "documented": "M06",
   "name": "Output frequency 1 (p.u.)",
   "description": "+/-20000 = maximum frequency, before slip compensation.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2055,
   "documented": "M07",
   "name": "Torque real value",
   "description": "% of motor rated torque.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2057,
   "documented": "M09",
   "name": "Output frequency",
   "description": "0.00-655.35 Hz over Modbus RTU (unsigned).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2058,
   "documented": "M10",
   "name": "Input power",
   "description": "% of nominal applicable motor output.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2059,
   "documented": "M11",
   "name": "Output current (effective)",
   "description": "% of inverter rated current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2060,
   "documented": "M12",
   "name": "Output voltage (effective)",
   "description": "Resolution 1 V in practice.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2061,
   "documented": "M13",
   "name": "Operation command, final",
   "description": "Combined keypad/terminal/comms command, format 14.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "FWD run forward",
    "1": "REV run reverse",
    "2": "X1",
    "3": "X2",
    "4": "X3",
    "5": "X4",
    "6": "X5",
    "7": "X6",
    "8": "X7",
    "11": "EN",
    "13": "XF (FWD terminal function)",
    "14": "XR (REV terminal function)",
    "15": "RST alarm reset"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2062,
   "documented": "M14",
   "name": "Operation status",
   "description": "Format 16.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "FWD during forward rotation",
    "1": "REV during reverse rotation",
    "2": "EXT during DC braking / pre-exciting",
    "3": "INT inverter shut down",
    "4": "BRK during braking",
    "5": "NUV DC link voltage established (0 = undervoltage)",
    "7": "VL during voltage limiting",
    "8": "IL during current limiting",
    "9": "ACC during acceleration",
    "10": "DEC during deceleration",
    "11": "ALM alarm relay (any fault)",
    "12": "RL communications effective",
    "15": "BUSY writing function code data"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2063,
   "documented": "M15",
   "name": "General-purpose output terminals",
   "description": "Format 15.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Y1",
    "1": "Y2",
    "2": "Y3",
    "3": "Y4",
    "4": "Y5",
    "8": "30 (alarm relay)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2064,
   "documented": "M16",
   "name": "Latest alarm code",
   "description": "Alarm code 0-254.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2065,
   "documented": "M17",
   "name": "Last alarm code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2066,
   "documented": "M18",
   "name": "Second last alarm code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2067,
   "documented": "M19",
   "name": "Third last alarm code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2068,
   "documented": "M20",
   "name": "Cumulative operation time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2069,
   "documented": "M21",
   "name": "DC link bus voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2071,
   "documented": "M23",
   "name": "Model code",
   "description": "Series, generation, destination and supply in four hex digits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2072,
   "documented": "M24",
   "name": "Capacity code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2073,
   "documented": "M25",
   "name": "ROM version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2074,
   "documented": "M26",
   "name": "Transmission error code",
   "description": "RS-485 communications error code, 0-127.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2092,
   "documented": "M44",
   "name": "Inverter internal air temperature on alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2093,
   "documented": "M45",
   "name": "Heat sink temperature on alarm",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2094,
   "documented": "M46",
   "name": "Life of main circuit capacitor",
   "description": "Remaining capacity, 0.0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2095,
   "documented": "M47",
   "name": "Life of PC board capacitor",
   "description": "Cumulative run time in 10 h steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2096,
   "documented": "M48",
   "name": "Life of heat sink cooling fan",
   "description": "Cumulative run time in 10 h steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2109,
   "documented": "M61",
   "name": "Inverter internal air temperature",
   "description": "Current value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2110,
   "documented": "M62",
   "name": "Heat sink temperature",
   "description": "Current value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2111,
   "documented": "M63",
   "name": "Load factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2112,
   "documented": "M64",
   "name": "Motor output",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2116,
   "documented": "M68",
   "name": "PID final command",
   "description": "+/-20000 = +/-100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2120,
   "documented": "M72",
   "name": "PID feedback value",
   "description": "+/-20000 = +/-100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2121,
   "documented": "M73",
   "name": "PID output",
   "description": "+/-20000 = +/-100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2126,
   "documented": "M78",
   "name": "Rotation speed command",
   "description": "Speed command in rpm (min-1).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2127,
   "documented": "M79",
   "name": "Rotation speed",
   "description": "Output rotation speed in rpm (min-1).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2134,
   "documented": "M86",
   "name": "Latest light alarm code",
   "description": "Low byte = light alarm code, high byte = consecutive repeat count (format 41).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3585,
   "documented": "y01",
   "name": "RS-485 port 1 station address",
   "description": "1-247 for Modbus RTU.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3586,
   "documented": "y02",
   "name": "RS-485 port 1 communications error processing",
   "description": "What the drive does on a comms error while running from the link.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Trip Er8 at once",
    "1": "Run for the y03 time, then trip Er8",
    "2": "Run for the y03 time; trip Er8 only if comms not restored",
    "3": "Keep running"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3587,
   "documented": "y03",
   "name": "RS-485 port 1 error processing timer",
   "description": "Timer used by y02 settings 1 and 2, 0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3588,
   "documented": "y04",
   "name": "RS-485 port 1 baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "2400 bps",
    "1": "4800 bps",
    "2": "9600 bps",
    "3": "19200 bps",
    "4": "38400 bps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3590,
   "documented": "y06",
   "name": "RS-485 port 1 parity",
   "description": "In Modbus RTU the stop bits follow the parity choice.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity (2 stop bits)",
    "1": "Even parity (1 stop bit)",
    "2": "Odd parity (1 stop bit)",
    "3": "No parity (1 stop bit)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3592,
   "documented": "y08",
   "name": "RS-485 port 1 no-response error detection time",
   "description": "0 = disabled, 1-60 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3594,
   "documented": "y10",
   "name": "RS-485 port 1 protocol selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Modbus RTU",
    "1": "Loader commands",
    "2": "Fuji general-purpose inverter protocol",
    "3": "Metasys N2",
    "5": "BACnet"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set y10 = 0 (Modbus RTU), y01 address and y04/y06 serial settings, and H30 = 3 so frequency and run commands come from RS-485. Write S05 (Hz) or S01 (p.u.) for speed and S06 bit 0/1 for run forward/reverse; poll M09, M11, M14 and M16.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1797,
    "why": "S05 frequency command"
   },
   {
    "table": "holding_register",
    "address": 1798,
    "why": "S06 run command"
   },
   {
    "table": "holding_register",
    "address": 1806,
    "why": "S14 alarm reset"
   },
   {
    "table": "holding_register",
    "address": 2057,
    "why": "M09 output frequency"
   },
   {
    "table": "holding_register",
    "address": 2059,
    "why": "M11 output current"
   },
   {
    "table": "holding_register",
    "address": 2062,
    "why": "M14 status"
   },
   {
    "table": "holding_register",
    "address": 2064,
    "why": "M16 latest alarm"
   },
   {
    "table": "holding_register",
    "address": 1054,
    "why": "H30 link mode"
   }
  ],
  "enable": "Select Modbus RTU with y10 = 0 and set H30 (communications link function) so the frequency and/or run command come from RS-485 (3 = both from the RJ-45 port). If a digital input is assigned to LE (enable communications link), it must be ON.",
  "watchdog": "y08 sets a no-response detection time (0 = off, 1-60 s); y02/y03 choose whether the drive trips at once, after a timer, or keeps running.",
  "quirks": [
   "Addresses are function-code based: wire address = group code x 256 + number (for example H30 = 4 x 256 + 30 = 1054).",
   "Reads are limited to 50 words and do not cross a function code group; unused codes read as 0.",
   "Reading S codes returns the last value written over comms, not the live command; read the M codes for the live value.",
   "Alarm reset through S06 needs bit 15 set then cleared; S14 = 1 resets in one write.",
   "S14 = 1 resets an alarm even when H30, y98, y99 or the LE terminal block the link; S06 bit 15 only works when the link is enabled."
  ],
  "setup": [
   "y01 station address 1-247, y04 baud (0-4 = 2400-38400 bps), y06 parity (stop bits follow parity in Modbus RTU), data length fixed at 8 bits.",
   "y09 adds a response interval (0.00-1.00 s) for slow masters."
  ],
  "gotchas": [
   "If S01 is not 0 it overrides S05; write 0 to S01 when using S05.",
   "Writing an alarm reset while a run command is still set restarts the drive immediately."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/fuji-electric/frenic-hvac-aqua",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}