 "manufacturer": "Fuji Electric",
 "manufacturer_slug": "fuji-electric",
 "model": "PXH digital controller (Modbus RTU, monitoring map)",
 "model_slug": "pxh",
 "short_model": "PXH",
 "aliases": [
  "PXH"
 ],
 "equipment_type": "Sensor (digital process controller)",
 "applies_to": "Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.",
 "summary": "The PXH is a Fuji Electric digital process controller. Every Modbus value is a 32-bit integer spread over two registers, low word first. This map covers the read-only monitoring block: control mode, PV, SV, deviation, MV, input error, alarm and relay states, ramp/soak position, extra inputs/outputs and DI/DO status.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "Odd",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Register numbers are printed Modicon-style (30259) with the relative wire address beside them (0102H = 30259 - 30001)."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "Digital Controller Communication Functions (MODBUS) Type PXH",
  "doc_number": "INP-TN514207c-E",
  "revision_date": null,
  "url": "https://americas.fujielectric.com/wp-content/uploads/2018/12/PXH-Digital-Controller-Communication-FunctionsMODBUS-TN514207c-E-.pdf",
  "pages": "Settings p. 7; 2-word order pp. 17-18 and 22; data format pp. 24-28; read-only map pp. 49-50"
 },
 "notes": [
  "All PXH data are two registers per value; the manual's read and write examples put the lower word first (CDAB). Read both registers in one request.",
  "Function 04 reads at most 15 registers per request; 03 reads up to 32.",
  "Holding-register parameters (40001-45001) are not included: their decimal-point table could not be tied to each register with certainty.",
  "Values carry no decimal point; PV-type values follow the input range decimal point setting.",
  "Heating/cooling MV (30625-30643), totalizer and timer monitors are omitted."
 ],
 "integration": {
  "summary": "Read input registers 30257-30269 with function 04 (control mode, PV, SV, DV, MV, input error) as 32-bit values with the low word first, two registers per value.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 258,
    "why": "PV1 (30259)"
   },
   {
    "table": "input_register",
    "address": 260,
    "why": "SV1 (30261)"
   },
   {
    "table": "input_register",
    "address": 264,
    "why": "MV1 (30265)"
   },
   {
    "table": "input_register",
    "address": 268,
    "why": "Input error (30269)"
   },
   {
    "table": "input_register",
    "address": 256,
    "why": "Control mode bits (30257)"
   },
   {
    "table": "input_register",
    "address": 832,
    "why": "Alarm 1 status (30833)"
   }
  ],
  "enable": "Set SPD4 (speed), BIT4 (parity) and STN4 (station 0-255; 0 stops communication) for the RS-485 channel on the front keys, then cycle power.",
  "watchdog": null,
  "quirks": [
   "32-bit values are low word first; a single-register write (06) only changes the lower word.",
   "The PC-loader port always uses station 1."
  ],
  "setup": [
   "Factory defaults (RS-485): 38400 bps, 8 data bits, 1 stop bit, odd parity, station 1.",
   "Turn power off and on after changing the communication settings."
  ],
  "gotchas": [
   "After changing the input range over the bus, a FIX command and a power cycle or reset are needed before the new range applies."
  ]
 },
 "registers": [
  {
   "table": "input_register",
   "address": 256,
   "documented": "30257",
   "name": "PID MODE1 current control mode",
   "description": "Status flags: each bit is 1 while that mode or state is active.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Fault",
    "1": "Standby",
    "2": "Remote ack",
    "3": "Other than auto mode",
    "4": "Auto mode request",
    "5": "Remote mode request",
    "6": "Auto tuning",
    "7": "Normal operation",
    "8": "PV tracking",
    "9": "Local SV",
    "10": "Remote SV",
    "11": "Local + PV tracking",
    "12": "Forced manual mode",
    "13": "EX-MV mode",
    "14": "Manual mode"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 258,
   "documented": "30259",
   "name": "PV1 control PV",
   "description": "-5 to 105 % FS; pinned there on over/under range. Input-range decimal point.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 260,
   "documented": "30261",
   "name": "SV1 current setpoint",
   "description": "Decimal point set by the input range (PV1D/UCD1 per template).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 262,
   "documented": "30263",
   "name": "DV1 current deviation",
   "description": "Decimal point set by the input range (PV1D/UCD1 per template).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 264,
   "documented": "30265",
   "name": "MV1 manipulated value",
   "description": "-25.0 to 125.0 %.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 268,
   "documented": "30269",
   "name": "FAULT1 input error status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Over",
    "2": "Under"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 784,
   "documented": "30785",
   "name": "ALM1 relay status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Non-excitation",
    "1": "Excitation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 786,
   "documented": "30787",
   "name": "ALM2 relay status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Non-excitation",
    "1": "Excitation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 788,
   "documented": "30789",
   "name": "ALM3 relay status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Non-excitation",
    "1": "Excitation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 790,
   "documented": "30791",
   "name": "ALM4 relay status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Non-excitation",
    "1": "Excitation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 792,
   "documented": "30793",
   "name": "ALM5 relay status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Non-excitation",
    "1": "Excitation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 794,
   "documented": "30795",
   "name": "ALM6 relay status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Non-excitation",
    "1": "Excitation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 796,
   "documented": "30797",
   "name": "ALM7 relay status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Non-excitation",
    "1": "Excitation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 798,
   "documented": "30799",
   "name": "ALM8 relay status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Non-excitation",
    "1": "Excitation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 832,
   "documented": "30833",
   "name": "ALM1 status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 834,
   "documented": "30835",
   "name": "ALM2 status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 836,
   "documented": "30837",
   "name": "ALM3 status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 838,
   "documented": "30839",
   "name": "ALM4 status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 840,
   "documented": "30841",
   "name": "ALM5 status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 842,
   "documented": "30843",
   "name": "ALM6 status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 844,
   "documented": "30845",
   "name": "ALM7 status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 846,
   "documented": "30847",
   "name": "ALM8 status",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 962,
   "documented": "30963",
   "name": "Ramp/soak elapsed time",
   "description": "0-5999 (minutes or seconds).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 964,
   "documented": "30965",
   "name": "Current pattern No.",
   "description": "0-30.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 966,
   "documented": "30967",
   "name": "Pattern No. selected by DI",
   "description": "0-30.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1024,
   "documented": "31025",
   "name": "PV1 measurement value",
   "description": "Decimal point set by the input range (PV1D/UCD1 per template).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1026,
   "documented": "31027",
   "name": "PV2 measurement value",
   "description": "Decimal point per PV2D.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1030,
   "documented": "31031",
   "name": "AI1 measurement value",
   "description": "Decimal point per AI1D.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1104,
   "documented": "31105",
   "name": "AO1 output value",
   "description": "-25.0 to 125.0 %.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1106,
   "documented": "31107",
   "name": "AO2 output value",
   "description": "-25.0 to 125.0 %.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1136,
   "documented": "31137",
   "name": "DI1-4 input status",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "DI1",
    "14": "DI2",
    "13": "DI3",
    "12": "DI4"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1138,
   "documented": "31139",
   "name": "DI11-15 input status",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "DI11",
    "14": "DI12",
    "13": "DI13",
    "12": "DI14",
    "11": "DI15"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1232,
   "documented": "31233",
   "name": "DO1-4 output status",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DO1",
    "1": "DO2",
    "2": "DO3",
    "3": "DO4"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1234,
   "documented": "31235",
   "name": "DO11-15 output status",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DO11",
    "1": "DO12",
    "2": "DO13",
    "3": "DO14",
    "4": "DO15"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1396,
   "documented": "31397",
   "name": "MVrb valve aperture monitor",
   "description": "-5.0 to 105.0 %.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/fuji-electric/pxh",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}