 "manufacturer": "Fuji Electric",
 "manufacturer_slug": "fuji-electric",
 "model": "PXR micro controller X (RS-485 Modbus option)",
 "model_slug": "pxr",
 "short_model": "PXR",
 "aliases": [
  "PXR3",
  "PXR4",
  "PXR5",
  "PXR9"
 ],
 "equipment_type": "Sensor (digital temperature controller)",
 "applies_to": "Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.",
 "summary": "The PXR is a Fuji Electric PID temperature controller. With the RS-485 option it is a Modbus RTU slave whose data appear twice: once as internal percentage values (3xxxx/4xxxx) and once in engineering units at the same numbers plus 1000. This map uses the engineering-unit block: PV, SV, MV and status in the input registers, control, alarm and ramp/soak settings in the holding registers, plus alarm bits.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "Odd",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Register numbers are printed Modicon-style with the relative (wire) address beside them; the manual says the wire address is the lower four digits minus 1 (41001 = 03E8H)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Micro Controller X Communication Functions (RS-485 MODBUS) Type PXR",
  "doc_number": "INP-TN512642d-E",
  "revision_date": null,
  "url": "https://americas.fujielectric.com/files/prod_selector_v/Micro%20Controller%20X%20Communication%20Functions%20%28MODBUS%29%20Model%20PXR%20%28TN512642d-E%29.pdf",
  "pages": "Settings p. 5; data format pp. 28-30; engineering-unit map pp. 37-42; bit details pp. 43-44"
 },
 "notes": [
  "Only the engineering-unit block (31001+, 41001+) is listed. The internal-value block at 30001/40001 holds the same items as 0.00-100.00 % of the input range for range-dependent data.",
  "Values carry no decimal point. PV/SV-type values use the P-dP decimal point (41020); P, D, filter and heater current have one decimal; MV, output limits, dead band and output convergence have two.",
  "On over/under-range or open input the PV reads 105 % or -5 % of the range; check 31008.",
  "Reserved/'do not use' registers and the display-mask items (41101-41113) are omitted; DI and alarm option codes are not reproduced.",
  "Writes are accepted beyond the setting range without error; keep values in range."
 ],
 "integration": {
  "summary": "Set CoM parity and a station number on the keypad, then read input registers 31001-31010 (PV, current SV, DV, MV, status) in one request and write the setpoint to 41003.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 1000,
    "why": "PV (31001)"
   },
   {
    "table": "input_register",
    "address": 1001,
    "why": "Current SV (31002)"
   },
   {
    "table": "input_register",
    "address": 1003,
    "why": "Output 1 MV (31004)"
   },
   {
    "table": "input_register",
    "address": 1006,
    "why": "Alarm status (31007)"
   },
   {
    "table": "input_register",
    "address": 1007,
    "why": "Input error status (31008)"
   },
   {
    "table": "holding_register",
    "address": 1002,
    "why": "Face panel SV (41003)"
   },
   {
    "table": "holding_register",
    "address": 1003,
    "why": "RUN/standby (41004)"
   },
   {
    "table": "holding_register",
    "address": 1019,
    "why": "Decimal point (41020)"
   }
  ],
  "enable": "Order the RS-485 option. On the keypad set STno (1-255; 0 stops communication), CoM (parity) and PCoL = 1 (Modbus) where shown.",
  "watchdog": null,
  "quirks": [
   "Speed is fixed at 9600 bps with 8 data bits and 1 stop bit; only parity is selectable (0 odd, 1 even, 2 none).",
   "Monitor SV at 31002, not 41003: the face-panel SV differs while SV-1 or ramp/soak is active.",
   "When changing the decimal point over the bus, rewrite the input scale limits as well."
  ],
  "setup": [
   "Factory defaults: station 1, odd parity, 9600 bps, 8 data bits, 1 stop bit."
  ],
  "gotchas": [
   "Every write is saved to EEPROM automatically (about 100,000 writes); avoid cyclic writes and wait a few seconds after writing before removing power."
  ]
 },
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "00001",
   "name": "Write to non-volatile memory (FIX)",
   "description": "1 = request write of settings to memory.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "10001",
   "name": "Alarm 1 ON/OFF",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "10005",
   "name": "Alarm 2 ON/OFF",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 8,
   "documented": "10009",
   "name": "Alarm 1 relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 9,
   "documented": "10010",
   "name": "Alarm 2 relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 10,
   "documented": "10011",
   "name": "Alarm 3 relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 11,
   "documented": "10012",
   "name": "HB alarm relay output",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 14,
   "documented": "10015",
   "name": "Alarm 3 ON/OFF",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1000,
   "documented": "31001",
   "name": "PV",
   "description": "-1999 to 9999. Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1001,
   "documented": "31002",
   "name": "Current SV",
   "description": "SV actually in use (ramp/soak, SV-1). Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1002,
   "documented": "31003",
   "name": "Deviation (DV)",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1003,
   "documented": "31004",
   "name": "MV output 1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1004,
   "documented": "31005",
   "name": "MV output 2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1005,
   "documented": "31006",
   "name": "Station No.",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1006,
   "documented": "31007",
   "name": "Alarm status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 relay output",
    "1": "Alarm 2 relay output",
    "2": "Alarm 3 relay output",
    "3": "HB alarm relay output",
    "4": "Alarm 1 ON",
    "5": "Alarm 2 ON",
    "6": "Alarm 3 ON",
    "7": "HB alarm relay output"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1007,
   "documented": "31008",
   "name": "Input/unit abnormal status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input lower open circuit",
    "1": "Input upper open circuit",
    "2": "Input under-range",
    "3": "Input over-range",
    "6": "Setting range error",
    "7": "EEPROM error"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1008,
   "documented": "31009",
   "name": "Ramp/soak running position",
   "description": "0 to 17.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1009,
   "documented": "31010",
   "name": "Heater current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1010,
   "documented": "31011",
   "name": "Timer 1 current count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1011,
   "documented": "31012",
   "name": "Timer 2 current count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1012,
   "documented": "31013",
   "name": "Timer 3 current count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1036,
   "documented": "31037",
   "name": "Remote SV input value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "41001",
   "name": "Non-volatile memory write-in (FIX)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No request",
    "1": "Request write"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "41002",
   "name": "PID/FUZZY/SELF selection",
   "description": "Do not change while controlling.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PID",
    "1": "FUZZY",
    "2": "SELF tuning"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "41003",
   "name": "Face panel SV",
   "description": "-1999 to 9999 within SV limits. Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "41004",
   "name": "Control RUN/standby",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RUN",
    "1": "Standby"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "41005",
   "name": "Auto tuning command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled / stop",
    "1": "Standard AT",
    "2": "Low PV type AT"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1005,
   "documented": "41006",
   "name": "P",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1006,
   "documented": "41007",
   "name": "I",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1007,
   "documented": "41008",
   "name": "D",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1008,
   "documented": "41009",
   "name": "Hysteresis (two-position)",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1009,
   "documented": "41010",
   "name": "COOL",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1010,
   "documented": "41011",
   "name": "Dead band",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1011,
   "documented": "41012",
   "name": "Anti-reset windup",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1012,
   "documented": "41013",
   "name": "Output convergence value",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1013,
   "documented": "41014",
   "name": "PV shift",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1014,
   "documented": "41015",
   "name": "SV offset",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1015,
   "documented": "41016",
   "name": "Input type code",
   "description": "0 to 16.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1016,
   "documented": "41017",
   "name": "Temperature unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1017,
   "documented": "41018",
   "name": "Input scale lower limit",
   "description": "-1999 to 9999.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1018,
   "documented": "41019",
   "name": "Input scale upper limit",
   "description": "-1999 to 9999.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1019,
   "documented": "41020",
   "name": "Decimal point place",
   "description": "0 to 2 digits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1021,
   "documented": "41022",
   "name": "Input filter time constant",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1022,
   "documented": "41023",
   "name": "RCJ compensation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1023,
   "documented": "41024",
   "name": "MV limit kind",
   "description": "0 to 15.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1024,
   "documented": "41025",
   "name": "Output 1 lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1025,
   "documented": "41026",
   "name": "Output 1 upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1026,
   "documented": "41027",
   "name": "Output 2 lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1027,
   "documented": "41028",
   "name": "Output 2 upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1030,
   "documented": "41031",
   "name": "SV lower limit",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1031,
   "documented": "41032",
   "name": "SV upper limit",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1038,
   "documented": "41039",
   "name": "Heater burnout alarm set value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1039,
   "documented": "41040",
   "name": "Setting lock",
   "description": "0 to 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1040,
   "documented": "41041",
   "name": "Alarm 1 type",
   "description": "Type code 0 to 34.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1041,
   "documented": "41042",
   "name": "Alarm 2 type",
   "description": "Type code 0 to 34.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1042,
   "documented": "41043",
   "name": "Alarm 3 type",
   "description": "Type code 0 to 34.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1043,
   "documented": "41044",
   "name": "Alarm 1 set value / lower limit",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1044,
   "documented": "41045",
   "name": "Alarm 2 set value / lower limit",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1045,
   "documented": "41046",
   "name": "Alarm 3 set value / lower limit",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1046,
   "documented": "41047",
   "name": "Alarm 1 upper limit",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1047,
   "documented": "41048",
   "name": "Alarm 2 upper limit",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1048,
   "documented": "41049",
   "name": "Alarm 3 upper limit",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1049,
   "documented": "41050",
   "name": "Alarm 1 hysteresis",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1050,
   "documented": "41051",
   "name": "Alarm 2 hysteresis",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1051,
   "documented": "41052",
   "name": "Alarm 3 hysteresis",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1052,
   "documented": "41053",
   "name": "Alarm 1 ON-delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1053,
   "documented": "41054",
   "name": "Alarm 2 ON-delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1054,
   "documented": "41055",
   "name": "Alarm 3 ON-delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1056,
   "documented": "41057",
   "name": "Ramp/soak 1 target value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1057,
   "documented": "41058",
   "name": "Ramp/soak 2 target value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1058,
   "documented": "41059",
   "name": "Ramp/soak 3 target value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1059,
   "documented": "41060",
   "name": "Ramp/soak 4 target value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1060,
   "documented": "41061",
   "name": "Ramp/soak 5 target value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1061,
   "documented": "41062",
   "name": "Ramp/soak 6 target value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1062,
   "documented": "41063",
   "name": "Ramp/soak 7 target value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1063,
   "documented": "41064",
   "name": "Ramp/soak 8 target value",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1064,
   "documented": "41065",
   "name": "Ramp/soak 1 ramp time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1065,
   "documented": "41066",
   "name": "Ramp/soak 1 soak time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1066,
   "documented": "41067",
   "name": "Ramp/soak 2 ramp time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1067,
   "documented": "41068",
   "name": "Ramp/soak 2 soak time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1068,
   "documented": "41069",
   "name": "Ramp/soak 3 ramp time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1069,
   "documented": "41070",
   "name": "Ramp/soak 3 soak time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1070,
   "documented": "41071",
   "name": "Ramp/soak 4 ramp time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1071,
   "documented": "41072",
   "name": "Ramp/soak 4 soak time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1072,
   "documented": "41073",
   "name": "Ramp/soak 5 ramp time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1073,
   "documented": "41074",
   "name": "Ramp/soak 5 soak time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1074,
   "documented": "41075",
   "name": "Ramp/soak 6 ramp time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1075,
   "documented": "41076",
   "name": "Ramp/soak 6 soak time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1076,
   "documented": "41077",
   "name": "Ramp/soak 7 ramp time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1077,
   "documented": "41078",
   "name": "Ramp/soak 7 soak time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1078,
   "documented": "41079",
   "name": "Ramp/soak 8 ramp time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1079,
   "documented": "41080",
   "name": "Ramp/soak 8 soak time",
   "description": "Minutes (keypad shows hh:mm).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1080,
   "documented": "41081",
   "name": "Ramp/soak mode",
   "description": "0 to 15.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1081,
   "documented": "41082",
   "name": "Ramp/soak command",
   "description": "Write 0-2; reading 3 means the program ended.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "oFF (stop)",
    "1": "rUn (run)",
    "2": "HLd (hold)",
    "3": "End (read only)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1082,
   "documented": "41083",
   "name": "Ramp/soak pattern selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Steps 1-4",
    "1": "Steps 5-8",
    "2": "Steps 1-8"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1084,
   "documented": "41085",
   "name": "PV stable range",
   "description": "Engineering units; decimal point per P-dP (41020).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1086,
   "documented": "41087",
   "name": "Communication DI action request",
   "description": "Bits 0-1: 00 = face panel SV, 01 = SV-1; held until changed or power off.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Select SV-1",
    "5": "Cancel alarm 1 latch",
    "6": "Cancel alarm 2 latch",
    "7": "Cancel alarm 3 latch",
    "8": "ALM1 relay timer DI",
    "9": "ALM2 relay timer DI",
    "10": "ALM3 relay timer DI"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1087,
   "documented": "41088",
   "name": "Control action type code",
   "description": "0 to 19.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1088,
   "documented": "41089",
   "name": "Output 1 proportional cycle",
   "description": "0 = current output; 1-150 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1089,
   "documented": "41090",
   "name": "Output 2 proportional cycle",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1096,
   "documented": "41097",
   "name": "Hysteresis mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "off",
    "1": "on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1113,
   "documented": "41114",
   "name": "Re-transmission output type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "PV",
    "1": "SV",
    "2": "MV",
    "3": "DV"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1116,
   "documented": "41117",
   "name": "Local/remote",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Local",
    "1": "Remote"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/fuji-electric/pxr",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}