 "manufacturer": "Fujitsu General",
 "manufacturer_slug": "fujitsu-general",
 "model": "UTY-VMSX Modbus converter (one indoor unit)",
 "model_slug": "uty-vmsx",
 "short_model": "UTY-VMSX",
 "aliases": [
  "UTY-VMSX"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "Fujitsu General UTY-VMSX Modbus RTU converter, one per indoor unit, per interface specification part no. 9708438047-05.",
 "summary": "The UTY-VMSX connects a single Fujitsu indoor unit to an RS-485 Modbus RTU network as a slave. Input registers report mode, on/off, setpoint, room temperature, fan, louvres, errors and lockouts; holding registers send commands, where 0 always means 'no change'. All values are single 16-bit registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The specification states the rule: the frame address is the remainder of the register number divided by 10000, minus 1. Its example sends 35555 as 5554. So 30054 is input register 53 and 40002 is holding register 1."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Interface specification - Modbus convertor UTY-VMSX",
  "doc_number": "9708438047-05",
  "revision_date": null,
  "url": "https://www.fujitsu-general.com/datafiles/W9708438047-0501_IF_En_UTY-VMSX.pdf",
  "pages": "Communication spec and function list p. 6; object composition pp. 7-12 (printed page numbers)"
 },
 "notes": [
  "Function codes: 03 and 04 read, 06 and 16 write. If the indoor unit lacks a function or cannot report a value, an FC04 read returns 0.",
  "Serial settings per the spec: 9600 or 19200 bps, 8 data bits, parity even/odd/none, 2 stop bits with no parity or 1 with parity. No factory default address or speed is printed; they are set on the converter.",
  "Temperatures in input registers are x4 (0.25 °C steps). Temperature commands use bit 0 as a 'change' flag and bits 1-8 as the value x4, so 20 °C is written as 161; the spec prints a table for 18-30 °C.",
  "The setpoint limit registers 30066-30068 pack two values (upper in bits 0-7, lower in bits 8-15) so they are listed raw.",
  "Write all six limit registers 40012-40017 together with FC16 when switching between 'no limit' and 'limit', and keep each lower limit below its upper limit.",
  "Model name (30003) and software version (30007) are packed character codes; the spec does not give a character table, so they are listed raw.",
  "Not listed: holding registers 40018-40022 (external thermo-off and human-detection settings), whose rows are hard to align reliably in the printed table."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "Converter baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "9600 bps",
    "1": "19200 bps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "30002",
   "name": "Converter slave address",
   "description": "Bits 0-7: address 1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "30003",
   "name": "Converter model name info",
   "description": "Encoded model name characters (bits 0-7 and 8-15).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "30007",
   "name": "Converter software version",
   "description": "Four 4-bit fields of the version string.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "30009",
   "name": "Converter error",
   "description": "Bits 8-11 error sub-code, bits 12-15 error code section.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error (1 = error)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 53,
   "documented": "30054",
   "name": "Operation mode status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Auto",
    "2": "Cool",
    "3": "Dry",
    "4": "Heat",
    "5": "Fan"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "30055",
   "name": "On/Off status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Stop",
    "2": "Operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 55,
   "documented": "30056",
   "name": "Set temperature",
   "description": "Bits 0-8 hold the setpoint x4 (0.25 °C steps).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.25,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 56,
   "documented": "30057",
   "name": "Fan speed status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Auto",
    "2": "Quiet",
    "3": "Low",
    "4": "Med",
    "5": "High",
    "6": "Med-Low",
    "7": "Med-High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 57,
   "documented": "30058",
   "name": "Indoor (room) temperature",
   "description": "Bits 0-8 hold the temperature x4 (0.25 °C steps).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.25,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "30059",
   "name": "Indoor unit error",
   "description": "Bits 8-11 error sub-code, bits 12-15 error code section.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Error (1 = error)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 59,
   "documented": "30060",
   "name": "Vertical louvre position",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Swing",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "30061",
   "name": "Horizontal louvre position",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Swing",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4",
    "6": "Position 5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 61,
   "documented": "30062",
   "name": "Remote controller prohibition status",
   "description": "1 = that remote function is locked out.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "All operations",
    "1": "Timer setting",
    "2": "Room temperature setting",
    "3": "Operation mode setting",
    "4": "Start/stop",
    "5": "Start only",
    "6": "Filter reset"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 62,
   "documented": "30063",
   "name": "Filter sign",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No sign",
    "1": "Filter sign"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 63,
   "documented": "30064",
   "name": "Economy mode status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Normal operation",
    "2": "Save operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "30065",
   "name": "Antifreeze status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Normal operation",
    "2": "Antifreeze operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 65,
   "documented": "30066",
   "name": "Setpoint limits status (Cool/Dry)",
   "description": "0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "30067",
   "name": "Setpoint limits status (Heat)",
   "description": "0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 67,
   "documented": "30068",
   "name": "Setpoint limits status (Auto)",
   "description": "0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 68,
   "documented": "30069",
   "name": "Indoor unit special status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Normal status (0 = special status)",
    "1": "Defrosting",
    "2": "Oil recovery",
    "3": "Pump down"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 69,
   "documented": "30070",
   "name": "External thermo-off status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Release",
    "2": "Thermo-off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 70,
   "documented": "30071",
   "name": "Demand status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "No operation",
    "2": "DRM 1",
    "3": "DRM 2",
    "4": "DRM 3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 71,
   "documented": "30072",
   "name": "Human detection auto save",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No operation",
    "1": "Operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 72,
   "documented": "30073",
   "name": "Human detection auto save time",
   "description": "Bits 0-10, set in 15-minute steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 73,
   "documented": "30074",
   "name": "Human detection auto off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No operation",
    "1": "Operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 74,
   "documented": "30075",
   "name": "Human detection auto off time",
   "description": "Bits 0-10, set in 60-minute steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Operation mode command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No change",
    "1": "Auto",
    "2": "Cool",
    "3": "Dry",
    "4": "Heat",
    "5": "Fan"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "On/Off command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No change",
    "1": "Stop",
    "2": "Operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Set temperature command",
   "description": "Write (°C x 4) x 2 + 1, e.g. 20 °C = 161; 0 = no change.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Fan speed command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No change",
    "1": "Auto",
    "2": "Quiet",
    "3": "Low",
    "4": "Med",
    "5": "High",
    "6": "Med-Low",
    "7": "Med-High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Vertical louvre command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No change",
    "1": "Swing",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Horizontal louvre command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No change",
    "1": "Swing",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4",
    "6": "Position 5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40008",
   "name": "Remote controller prohibition command",
   "description": "Bit 0 must be 1 for the other bits to apply.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Apply change (1 = change)",
    "1": "Inhibit all operations",
    "2": "Inhibit timer setting",
    "3": "Inhibit room temperature setting",
    "4": "Inhibit operation mode setting",
    "5": "Inhibit start/stop",
    "6": "Inhibit start only",
    "7": "Inhibit filter reset"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Filter sign reset",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No change",
    "1": "Reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Economy mode command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No change",
    "1": "Normal operation",
    "2": "Save operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Antifreeze command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No change",
    "1": "Release",
    "2": "Antifreeze operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40012",
   "name": "Upper setpoint limit (Cool/Dry)",
   "description": "Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "40013",
   "name": "Lower setpoint limit (Cool/Dry)",
   "description": "Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Upper setpoint limit (Heat)",
   "description": "Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Lower setpoint limit (Heat)",
   "description": "Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40016",
   "name": "Upper setpoint limit (Auto)",
   "description": "Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "Lower setpoint limit (Auto)",
   "description": "Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll input registers 53-58 (30054-30059) with FC04 for mode, on/off, setpoint, fan, room temperature and error. Control with FC06 to holding registers 1-4 (40002-40005); 0 in any command register means no change.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 53,
    "why": "Operation mode"
   },
   {
    "table": "input_register",
    "address": 54,
    "why": "On/off status"
   },
   {
    "table": "input_register",
    "address": 55,
    "why": "Setpoint"
   },
   {
    "table": "input_register",
    "address": 57,
    "why": "Room temperature"
   },
   {
    "table": "input_register",
    "address": 58,
    "why": "Indoor unit error"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "On/off command"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Setpoint command"
   }
  ],
  "enable": "No enable step is described; the converter answers as soon as its address and speed are set.",
  "watchdog": null,
  "quirks": [
   "Address rule: frame address = (register mod 10000) - 1.",
   "Setpoint writes need bit 0 set: (°C x 4) x 2 + 1.",
   "Most status values start at 1 (filter sign and the human-detection flags start at 0); command registers add 0 = no change."
  ],
  "setup": [
   "One UTY-VMSX per indoor unit; up to 31 converters per BMS line without a repeater, 247 with.",
   "3-wire RS-485, max 1000 m."
  ],
  "gotchas": [
   "An FC04 read of a function the indoor unit does not have returns 0, not an exception."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/fujitsu-general/uty-vmsx",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}