 "manufacturer": "FW Murphy",
 "manufacturer_slug": "fw-murphy",
 "model": "Interchange Comm Control Module MX5-R2 (Standard IO mode)",
 "model_slug": "mx5-r2",
 "short_model": "MX5-R2",
 "aliases": [
  "MX5-R2",
  "Interchange MX5-R2",
  "Enovation Controls MX5-R2"
 ],
 "equipment_type": "Remote I/O module (engine / pump controller expansion)",
 "applies_to": "FW Murphy MX5-R2 modules with date code S8 or later running the Standard IO application (default); pulse registers need firmware 4.4.10111 / date code U10 or later.",
 "summary": "The MX5-R2 is FW Murphy's I/O and communications expansion module for Centurion controllers, with 24 digital inputs, 10 analog inputs, a magnetic pickup, 16 digital outputs and 4 analog outputs. In Standard IO mode it is a Modbus RTU server on two RS-485 ports and RS-232 and a Modbus TCP server on Ethernet, all using one holding-register table. This map covers the whole published table.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Registers are printed in 6-digit Modicon form (400001 = holding register 1). Wire address = number - 400001, e.g. digital inputs 400021 = address 20 and IP address 465197 = address 65196."
 },
 "default_word_order": "ABCD",
 "firmware": "Date code S8 or later; pulse engine registers 4.4.10111 / date code U10 or later",
 "source": {
  "title": "Interchange Comm Control Module MX5-R2 Series Operations Manual",
  "doc_number": "00-02-3003",
  "revision_date": "2025-02-11",
  "url": "https://fwmurphy.com/wp-content/uploads/2025/02/00-02-3003.pdf",
  "pages": "pp. 4-5 (communications), pp. 6-10 (holding register table), pp. 10-12 (register descriptions)"
 },
 "notes": [
  "Analog inputs: the register notes call them signed 16-bit counts, but the table gives full scale as 32768 = 5 V or 25 mA while the text says 32767 = 24 mA (4 mA = 5243, 20 mA = 26214). They are left as raw INT16 counts; calibrate against the stated 4-20 mA counts.",
  "The 400090-400097 polarity rows reuse the DI1-DI8 byte labels in the table; this map labels them by the register's channel pair (DI9-DI24).",
  "Factory-use registers 400002-400004, 400051-400052, 400084 and 400098-400115 are left out.",
  "Default serial framing: the module answers with 1 stop bit at addresses 1-31 and 2 stop bits at 32-239; parity is not stated."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "400001",
   "name": "Hardware type",
   "description": "Module ID; MX5-R2 returns 33.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "400005",
   "name": "Bootloader build version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "400007",
   "name": "Firmware number",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "400008",
   "name": "Firmware build version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "400009-400010",
   "name": "Firmware checksum",
   "description": "32-bit; MSW in 400009, LSW in 400010.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "400011",
   "name": "Firmware major version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "400012",
   "name": "Firmware minor version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "400013",
   "name": "Bootloader major version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "400014",
   "name": "Bootloader minor version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "400021",
   "name": "Digital inputs 1-16",
   "description": "0 = open, 1 = closed; bit 0 = DI1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI1 closed",
    "1": "DI2 closed",
    "2": "DI3 closed",
    "3": "DI4 closed",
    "4": "DI5 closed",
    "5": "DI6 closed",
    "6": "DI7 closed",
    "7": "DI8 closed",
    "8": "DI9 closed",
    "9": "DI10 closed",
    "10": "DI11 closed",
    "11": "DI12 closed",
    "12": "DI13 closed",
    "13": "DI14 closed",
    "14": "DI15 closed",
    "15": "DI16 closed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "400022",
   "name": "Digital inputs 17-24",
   "description": "0 = open, 1 = closed; bit 0 = DI17.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI17 closed",
    "1": "DI18 closed",
    "2": "DI19 closed",
    "3": "DI20 closed",
    "4": "DI21 closed",
    "5": "DI22 closed",
    "6": "DI23 closed",
    "7": "DI24 closed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "400023",
   "name": "System voltage",
   "description": "Supply voltage; 320 = 32.0 V DC.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "400024",
   "name": "Analog input 1",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "400025",
   "name": "Analog input 2",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "400026",
   "name": "Analog input 3",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "400027",
   "name": "Analog input 4",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "400028",
   "name": "Analog input 5",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "400029",
   "name": "Analog input 6",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "400030",
   "name": "Analog input 7",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "400031",
   "name": "Analog input 8",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "400032",
   "name": "Analog input 9",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "400033",
   "name": "Analog input 10",
   "description": "Raw A/D counts; full scale depends on the channel type register.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "400038",
   "name": "Frequency input",
   "description": "Magnetic pickup input, 0-10,000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "400047",
   "name": "Analog output 1 signal",
   "description": "0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "400048",
   "name": "Analog output 2 signal",
   "description": "0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "400049",
   "name": "Analog output 3 signal",
   "description": "0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "400050",
   "name": "Analog output 4 signal",
   "description": "0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "400053",
   "name": "RTC seconds",
   "description": "Range 0-59; applied when 400060 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "400054",
   "name": "RTC minutes",
   "description": "Range 0-59; applied when 400060 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "400055",
   "name": "RTC hours",
   "description": "Range 0-23; applied when 400060 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "400056",
   "name": "RTC day of week",
   "description": "Range 1-7; applied when 400060 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "400057",
   "name": "RTC day",
   "description": "Range 1-31; applied when 400060 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "400058",
   "name": "RTC month",
   "description": "Range 1-12; applied when 400060 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "400059",
   "name": "RTC year",
   "description": "Range 2000-3000; applied when 400060 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "400060",
   "name": "Clock set enable",
   "description": "Write 1 to load 400053-400059 into the clock.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Set clock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "400061",
   "name": "Digital outputs 1-16",
   "description": "Bit 0 = DO1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "DO1 on",
    "1": "DO2 on",
    "2": "DO3 on",
    "3": "DO4 on",
    "4": "DO5 on",
    "5": "DO6 on",
    "6": "DO7 on",
    "7": "DO8 on",
    "8": "DO9 on",
    "9": "DO10 on",
    "10": "DO11 on",
    "11": "DO12 on",
    "12": "DO13 on",
    "13": "DO14 on",
    "14": "DO15 on",
    "15": "DO16 on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "400063",
   "name": "Digital outputs at power-up",
   "description": "Stored state applied before any client talks; bit 0 = DO1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "DO1 on",
    "1": "DO2 on",
    "2": "DO3 on",
    "3": "DO4 on",
    "4": "DO5 on",
    "5": "DO6 on",
    "6": "DO7 on",
    "7": "DO8 on",
    "8": "DO9 on",
    "9": "DO10 on",
    "10": "DO11 on",
    "11": "DO12 on",
    "12": "DO13 on",
    "13": "DO14 on",
    "14": "DO15 on",
    "15": "DO16 on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "400064",
   "name": "Digital outputs at comm failure",
   "description": "State applied after the 400073 timeout; bit 0 = DO1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "DO1 on",
    "1": "DO2 on",
    "2": "DO3 on",
    "3": "DO4 on",
    "4": "DO5 on",
    "5": "DO6 on",
    "6": "DO7 on",
    "7": "DO8 on",
    "8": "DO9 on",
    "9": "DO10 on",
    "10": "DO11 on",
    "11": "DO12 on",
    "12": "DO13 on",
    "13": "DO14 on",
    "14": "DO15 on",
    "15": "DO16 on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "400065",
   "name": "Analog output 1 at power-up",
   "description": "D/A counts, 65535 = 24 mA; stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "400066",
   "name": "Analog output 2 at power-up",
   "description": "D/A counts, 65535 = 24 mA; stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "400067",
   "name": "Analog output 3 at power-up",
   "description": "D/A counts, 65535 = 24 mA; stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "400068",
   "name": "Analog output 4 at power-up",
   "description": "D/A counts, 65535 = 24 mA; stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "400069",
   "name": "Analog output 1 at comm failure",
   "description": "D/A counts, 65535 = 24 mA; stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "400070",
   "name": "Analog output 2 at comm failure",
   "description": "D/A counts, 65535 = 24 mA; stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "400071",
   "name": "Analog output 3 at comm failure",
   "description": "D/A counts, 65535 = 24 mA; stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "400072",
   "name": "Analog output 4 at comm failure",
   "description": "D/A counts, 65535 = 24 mA; stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "counts",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "400073",
   "name": "Communication timeout",
   "description": "Silence on all ports for this long switches outputs to their comm-failure states.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "400074",
   "name": "Analog input 1 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "400075",
   "name": "Analog input 2 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "400076",
   "name": "Analog input 3 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "400077",
   "name": "Analog input 4 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "400078",
   "name": "Analog input 5 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "400079",
   "name": "Analog input 6 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 79,
   "documented": "400080",
   "name": "Analog input 7 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA",
    "2": "5 kohm resistive",
    "3": "3 kohm resistive",
    "4": "10 kohm resistive",
    "5": "30 kohm resistive"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "400081",
   "name": "Analog input 8 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA",
    "2": "5 kohm resistive",
    "3": "3 kohm resistive",
    "4": "10 kohm resistive",
    "5": "30 kohm resistive"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "400082",
   "name": "Analog input 9 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA",
    "2": "5 kohm resistive",
    "3": "3 kohm resistive",
    "4": "10 kohm resistive",
    "5": "30 kohm resistive"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "400083",
   "name": "Analog input 10 type",
   "description": "Stored setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-5 V DC",
    "1": "0-25 mA",
    "2": "5 kohm resistive",
    "3": "3 kohm resistive",
    "4": "10 kohm resistive",
    "5": "30 kohm resistive"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "400085",
   "name": "Serial port baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "9600",
    "2": "19200",
    "3": "38400",
    "4": "57600",
    "5": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 85,
   "documented": "400086",
   "name": "Digital input 1-2 polarity",
   "description": "High byte DI1, low byte DI2: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "400087",
   "name": "Digital input 3-4 polarity",
   "description": "High byte DI3, low byte DI4: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 87,
   "documented": "400088",
   "name": "Digital input 5-6 polarity",
   "description": "High byte DI5, low byte DI6: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "400089",
   "name": "Digital input 7-8 polarity",
   "description": "High byte DI7, low byte DI8: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "400090",
   "name": "Digital input 9-10 polarity",
   "description": "High byte DI9, low byte DI10: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 90,
   "documented": "400091",
   "name": "Digital input 11-12 polarity",
   "description": "High byte DI11, low byte DI12: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "400092",
   "name": "Digital input 13-14 polarity",
   "description": "High byte DI13, low byte DI14: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 92,
   "documented": "400093",
   "name": "Digital input 15-16 polarity",
   "description": "High byte DI15, low byte DI16: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 93,
   "documented": "400094",
   "name": "Digital input 17-18 polarity",
   "description": "High byte DI17, low byte DI18: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 94,
   "documented": "400095",
   "name": "Digital input 19-20 polarity",
   "description": "High byte DI19, low byte DI20: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 95,
   "documented": "400096",
   "name": "Digital input 21-22 polarity",
   "description": "High byte DI21, low byte DI22: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "400097",
   "name": "Digital input 23-24 polarity",
   "description": "High byte DI23, low byte DI24: 0 closed DC-, 1 closed DC+, 2 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "*400116",
   "name": "High-resolution pulse enable",
   "description": "Bit 0 = DO1; pulse on/off times then override 400061.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "DO1 pulse enabled",
    "1": "DO2 pulse enabled",
    "2": "DO3 pulse enabled",
    "3": "DO4 pulse enabled",
    "4": "DO5 pulse enabled",
    "5": "DO6 pulse enabled",
    "6": "DO7 pulse enabled",
    "7": "DO8 pulse enabled",
    "8": "DO9 pulse enabled",
    "9": "DO10 pulse enabled",
    "10": "DO11 pulse enabled",
    "11": "DO12 pulse enabled",
    "12": "DO13 pulse enabled",
    "13": "DO14 pulse enabled",
    "14": "DO15 pulse enabled",
    "15": "DO16 pulse enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "*400117",
   "name": "DO1 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "*400118",
   "name": "DO1 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "*400119",
   "name": "DO2 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "*400120",
   "name": "DO2 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "*400121",
   "name": "DO3 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "*400122",
   "name": "DO3 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "*400123",
   "name": "DO4 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "*400124",
   "name": "DO4 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "*400125",
   "name": "DO5 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 125,
   "documented": "*400126",
   "name": "DO5 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "*400127",
   "name": "DO6 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "*400128",
   "name": "DO6 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "*400129",
   "name": "DO7 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 129,
   "documented": "*400130",
   "name": "DO7 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 130,
   "documented": "*400131",
   "name": "DO8 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 131,
   "documented": "*400132",
   "name": "DO8 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "*400133",
   "name": "DO9 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "*400134",
   "name": "DO9 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "*400135",
   "name": "DO10 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 135,
   "documented": "*400136",
   "name": "DO10 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "*400137",
   "name": "DO11 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 137,
   "documented": "*400138",
   "name": "DO11 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 138,
   "documented": "*400139",
   "name": "DO12 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 139,
   "documented": "*400140",
   "name": "DO12 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "*400141",
   "name": "DO13 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 141,
   "documented": "*400142",
   "name": "DO13 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "*400143",
   "name": "DO14 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 143,
   "documented": "*400144",
   "name": "DO14 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 144,
   "documented": "*400145",
   "name": "DO15 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 145,
   "documented": "*400146",
   "name": "DO15 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 146,
   "documented": "*400147",
   "name": "DO16 pulse on time",
   "description": "0-255 x 50 ms; 0 keeps the output off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 147,
   "documented": "*400148",
   "name": "DO16 pulse off time",
   "description": "5-255 x 50 ms (minimum 250 ms).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 50,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65196,
   "documented": "465197",
   "name": "IP address part 1",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65197,
   "documented": "465198",
   "name": "IP address part 2",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65198,
   "documented": "465199",
   "name": "IP address part 3",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65199,
   "documented": "465200",
   "name": "IP address part 4",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65200,
   "documented": "465201",
   "name": "Network mask part 1",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65201,
   "documented": "465202",
   "name": "Network mask part 2",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65202,
   "documented": "465203",
   "name": "Network mask part 3",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65203,
   "documented": "465204",
   "name": "Network mask part 4",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65204,
   "documented": "465205",
   "name": "Gateway part 1",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65205,
   "documented": "465206",
   "name": "Gateway part 2",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65206,
   "documented": "465207",
   "name": "Gateway part 3",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65207,
   "documented": "465208",
   "name": "Gateway part 4",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65208,
   "documented": "465209",
   "name": "DNS1 part 1",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65209,
   "documented": "465210",
   "name": "DNS1 part 2",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65210,
   "documented": "465211",
   "name": "DNS1 part 3",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65211,
   "documented": "465212",
   "name": "DNS1 part 4",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65212,
   "documented": "465213",
   "name": "DNS2 part 1",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65213,
   "documented": "465214",
   "name": "DNS2 part 2",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65214,
   "documented": "465215",
   "name": "DNS2 part 3",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65215,
   "documented": "465216",
   "name": "DNS2 part 4",
   "description": "One octet, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65216,
   "documented": "465217",
   "name": "Ethernet IP options",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Static IP, no auto IP",
    "1": "DHCP, no auto IP",
    "2": "Static IP, auto IP if no DHCP/IP",
    "3": "DHCP, auto IP if no DHCP/IP"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65217,
   "documented": "465218",
   "name": "MAC address word 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65218,
   "documented": "465219",
   "name": "MAC address word 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65219,
   "documented": "465220",
   "name": "MAC address word 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll holding registers 400021-400038 for inputs, write 400061 and 400047-400050 for outputs, and set 400073 plus the comm-failure registers so outputs go to a safe state if the client stops polling.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 20,
    "why": "Digital inputs 1-16"
   },
   {
    "table": "holding_register",
    "address": 21,
    "why": "Digital inputs 17-24"
   },
   {
    "table": "holding_register",
    "address": 23,
    "why": "Analog input 1"
   },
   {
    "table": "holding_register",
    "address": 37,
    "why": "Frequency input"
   },
   {
    "table": "holding_register",
    "address": 60,
    "why": "Digital outputs 1-16"
   },
   {
    "table": "holding_register",
    "address": 46,
    "why": "Analog output 1"
   },
   {
    "table": "holding_register",
    "address": 72,
    "why": "Comm timeout"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Hardware type check (33)"
   }
  ],
  "enable": "Standard IO mode is the default (COP LED code 4,2). To reload it: power up with DIP 5-8 closed and DIP 2 open, 1/3/4 closed. DIP 5-8 closed with 1-4 closed loads factory defaults (baud, Ethernet, channel configuration).",
  "watchdog": "Register 400073 sets a communication timeout in seconds; when no client talks on any port for that time, outputs go to the states in 400064 and 400069-400072. Pulse mode is also cancelled on comm loss.",
  "quirks": [
   "Supported functions: 03, 06 and 16 only; invalid addresses return an exception.",
   "Polarity registers pack two inputs: high byte = odd channel, low byte = even channel.",
   "The firmware checksum is split MSW (400009) then LSW (400010)."
  ],
  "setup": [
   "RS-485: A (+) on terminals 61/62, B (-) on 80/81; twisted shielded pair, 120 ohm.",
   "Serial default 9600 baud, up to 115.2k via 400085; set the RTU client timeout to at least 400 ms.",
   "Ethernet default 192.168.0.100 / 255.255.255.0, gateway 0.0.0.0; change via 465197-465217."
  ],
  "gotchas": [
   "In Rockwell IO mode the Ethernet ports speak EtherNet/IP (CIP) only, not Modbus TCP.",
   "DIP switches 5-8 double as address switches; the special functions only act when they are closed at power-up."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/fw-murphy/mx5-r2",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}