 "manufacturer": "GE Multilin",
 "manufacturer_slug": "ge-multilin",
 "model": "Multilin PQMII power quality meter",
 "model_slug": "multilin-pqmii",
 "short_model": "PQMII",
 "aliases": [
  "PQM II",
  "GE Multilin PQMII",
  "PQM2"
 ],
 "equipment_type": "Power meter (power quality meter)",
 "applies_to": "Multilin PQMII per instruction manual GEK-113532 (communications guide chapter).",
 "summary": "The Multilin PQMII is a panel-mount power quality meter, now documented by GE Vernova. It speaks Modbus RTU on its RS-485 ports, with all data in one hexadecimal memory map. This map covers currents, voltages, power, power factor, energy, demand, frequency, THD and the command registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The memory map prints addresses in hex, and the manual's examples send that hex value on the wire (e.g. a read of 3 registers starting at 006B). Actual values are input registers, setpoints and commands holding registers; function 03 and 04 both read either area."
 },
 "default_word_order": "ABCD",
 "firmware": "Software revision 2.2x",
 "source": {
  "title": "PQMII Power Quality Meter Communications Guide",
  "doc_number": "GEK-113532 (manual P/N 1601-9090-A1)",
  "revision_date": null,
  "url": "https://www.gevernova.com/grid-solutions/sites/default/files/resources/products/manuals/pqmii/gek-113532-GEV.pdf",
  "pages": "long-integer rule and worked example COMM-4/5; functions COMM-5 to COMM-13; memory map COMM-14 onward (actual values from COMM-16); data formats COMM-57"
 },
 "notes": [
  "Word order: the manual says long integers occupy two registers, high-order register first, and its worked example (02F0 = 004Fh, 02F1 = 35D1h -> 51911.21 kW) confirms ABCD.",
  "Data formats: F1 unsigned 16-bit, F2 signed 16-bit, F3 unsigned 32-bit, F4 signed 32-bit. Scales are copied from the Units and Scale column (0.01 x kW, 0.1 x %, 0.01 x Hz).",
  "Up to 125 registers can be read in one request; up to 60 written.",
  "Phase B current THD (0479h) is left out because its units/scale cell is blank in the table. Min/max time stamps, tariff energies/costs, per-harmonic data and setpoints are left out.",
  "The user-definable area (index 0180h-01F7h, data 0100h-0177h) can gather scattered registers into one block.",
  "Communication defaults are not listed: the RS-485 setpoint rows (e.g. baud rate at 1018h) give codes whose meaning is not readable in this copy of the table."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "0000",
   "name": "Product device code",
   "description": "Reads 73 for a PQMII.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 540,
   "documented": "021C",
   "name": "General status",
   "description": "Status flags (format F109 in the manual).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 576,
   "documented": "0240",
   "name": "Phase A current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 577,
   "documented": "0241",
   "name": "Phase B current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 578,
   "documented": "0242",
   "name": "Phase C current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 579,
   "documented": "0243",
   "name": "Average current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 580,
   "documented": "0244",
   "name": "Neutral current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 581,
   "documented": "0245",
   "name": "Current unbalance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 640,
   "documented": "0280-0281",
   "name": "Voltage Van",
   "description": "High register first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 642,
   "documented": "0282-0283",
   "name": "Voltage Vbn",
   "description": "High register first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 644,
   "documented": "0284-0285",
   "name": "Voltage Vcn",
   "description": "High register first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 646,
   "documented": "0286-0287",
   "name": "Average phase voltage",
   "description": "High register first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 648,
   "documented": "0288-0289",
   "name": "Voltage Vab",
   "description": "High register first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 650,
   "documented": "028A-028B",
   "name": "Voltage Vbc",
   "description": "High register first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 652,
   "documented": "028C-028D",
   "name": "Voltage Vca",
   "description": "High register first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 654,
   "documented": "028E-028F",
   "name": "Average line voltage",
   "description": "High register first.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 656,
   "documented": "0290",
   "name": "Voltage unbalance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 752,
   "documented": "02F0-02F1",
   "name": "3-phase real power",
   "description": "Signed, high register first.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 754,
   "documented": "02F2-02F3",
   "name": "3-phase reactive power",
   "description": "Signed, high register first.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 756,
   "documented": "02F4-02F5",
   "name": "3-phase apparent power",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 758,
   "documented": "02F6",
   "name": "3-phase power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 759,
   "documented": "02F7-02F8",
   "name": "Phase A real power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 761,
   "documented": "02F9-02FA",
   "name": "Phase A reactive power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 763,
   "documented": "02FB-02FC",
   "name": "Phase A apparent power",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 765,
   "documented": "02FD",
   "name": "Phase A power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 766,
   "documented": "02FE-02FF",
   "name": "Phase B real power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 768,
   "documented": "0300-0301",
   "name": "Phase B reactive power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 770,
   "documented": "0302-0303",
   "name": "Phase B apparent power",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 772,
   "documented": "0304",
   "name": "Phase B power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 773,
   "documented": "0305-0306",
   "name": "Phase C real power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 775,
   "documented": "0307-0308",
   "name": "Phase C reactive power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 777,
   "documented": "0309-030A",
   "name": "Phase C apparent power",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 779,
   "documented": "030B",
   "name": "Phase C power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 976,
   "documented": "03D0-03D1",
   "name": "3-phase positive real energy",
   "description": "Imported real energy.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 978,
   "documented": "03D2-03D3",
   "name": "3-phase negative real energy",
   "description": "Exported real energy.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 980,
   "documented": "03D4-03D5",
   "name": "3-phase positive reactive energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 982,
   "documented": "03D6-03D7",
   "name": "3-phase negative reactive energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 984,
   "documented": "03D8-03D9",
   "name": "3-phase apparent energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 986,
   "documented": "03DA-03DB",
   "name": "Energy used in last 24 h",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1024,
   "documented": "0400",
   "name": "Phase A current demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1025,
   "documented": "0401",
   "name": "Phase B current demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1026,
   "documented": "0402",
   "name": "Phase C current demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1027,
   "documented": "0403",
   "name": "Neutral current demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1028,
   "documented": "0404-0405",
   "name": "3-phase real power demand",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1030,
   "documented": "0406-0407",
   "name": "3-phase reactive power demand",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1032,
   "documented": "0408-0409",
   "name": "3-phase apparent power demand",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kVA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1088,
   "documented": "0440",
   "name": "Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1089,
   "documented": "0441",
   "name": "Frequency minimum",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1090,
   "documented": "0442",
   "name": "Frequency maximum",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1144,
   "documented": "0478",
   "name": "Phase A current THD",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1146,
   "documented": "047A",
   "name": "Phase C current THD",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1147,
   "documented": "047B",
   "name": "Neutral current THD",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1148,
   "documented": "047C",
   "name": "Voltage Van THD",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1149,
   "documented": "047D",
   "name": "Voltage Vbn THD",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1150,
   "documented": "047E",
   "name": "Voltage Vcn THD",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1151,
   "documented": "047F",
   "name": "Voltage Vab THD",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1152,
   "documented": "0480",
   "name": "Voltage Vbc THD",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "0080",
   "name": "Command function code",
   "description": "Write 5 before the operation code (printed range 5).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 129,
   "documented": "0081",
   "name": "Command operation code",
   "description": "Command to run (format F7).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Reset",
    "2": "Alarm relay on",
    "3": "Alarm relay off",
    "10": "Set clock time",
    "11": "Set clock date",
    "14": "Clear energy values",
    "15": "Clear max demand values",
    "16": "Clear min/max current",
    "17": "Clear min/max voltage",
    "18": "Clear min/max power",
    "19": "Clear max THD",
    "20": "Clear switch input pulse count",
    "31": "Clear event record",
    "34": "Clear all demand",
    "35": "Clear min/max frequency"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 0240h-0245h for currents, 0280h-0290h for voltages (32-bit), 02F0h-030Bh for power and PF, 03D0h-03D9h for energy and 0440h for frequency. Use the command registers to clear energy or min/max values.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 576,
    "why": "Phase A current"
   },
   {
    "table": "input_register",
    "address": 648,
    "why": "Voltage Vab"
   },
   {
    "table": "input_register",
    "address": 752,
    "why": "3-phase real power"
   },
   {
    "table": "input_register",
    "address": 758,
    "why": "3-phase power factor"
   },
   {
    "table": "input_register",
    "address": 1088,
    "why": "Frequency"
   },
   {
    "table": "input_register",
    "address": 976,
    "why": "Imported real energy"
   }
  ],
  "enable": "Set the slave address, baud rate and parity in the PQMII setpoints for the COM port in use; Modbus RTU is the native protocol.",
  "watchdog": null,
  "quirks": [
   "Hex addresses are wire addresses.",
   "32-bit values are high register first; signed values (F4) are two's complement across both registers."
  ],
  "setup": [
   "Address 0 is broadcast (setpoint stores and commands only); give each meter its own address."
  ],
  "gotchas": [
   "Voltages are whole volts in 32-bit registers; power is in 0.01 kW units, not watts."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/ge-multilin/multilin-pqmii",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}