 "manufacturer": "Gree",
 "manufacturer_slug": "gree",
 "model": "Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)",
 "model_slug": "export-residential-ac-modbus",
 "short_model": "Gree residential AC Modbus",
 "aliases": [
  "Gree residential split Modbus",
  "Gree wall split Modbus",
  "Gree wired controller Modbus"
 ],
 "equipment_type": "Split AC unit (VRF / split AC gateway built in)",
 "applies_to": "Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.",
 "summary": "On these Gree residential units the Modbus RTU slave lives in the indoor-unit controller or wired controller, so no extra module is needed. Holding registers carry on/off, mode, fan speed, setpoint, louvres, sleep and energy-saving limits plus indoor, return-air and outdoor temperatures; coils carry feature flags, locks and a long list of indoor, outdoor and inverter-drive fault bits. Up to 255 units can share one BMS line.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Registers are words numbered from 0 and coils are bits numbered from 0 (Bit0 = Byte0.0). Word n is wire address n and Bit n is coil n. The example frames agree: reading ten bits from coil 5 sends start address 00 05, and reading two words from address 1 sends 00 01."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Modbus Protocol for export residential air conditioners",
  "doc_number": null,
  "revision_date": "2023-05",
  "url": "https://kesko-onninen-pim-resources-production.s3-eu-west-1.amazonaws.com/pimdocuments/26148852.pdf",
  "pages": "p. 7 serial settings, pp. 8-12 coil/word layout and example frames, pp. 13-14 precautions, pp. 14-19 words, pp. 20-27 bits",
  "unofficial": true
 },
 "notes": [
  "Gree does not host this protocol publicly; the link is the unaltered Gree PDF in the product-document store of the Finnish wholesaler Onninen (Kesko). No document number is printed; the date is the PDF creation date.",
  "Registers are read with function 03 and written with 16; coils are read with 01 and written with 15. Points marked R in the table are read-only.",
  "Only named points are listed; reserved words and bits are left out. Bits 237-239 have no name in the table and are left out.",
  "Mode and swing values are printed in binary in the source (for example 001 = cooling, 1011 = swing positions 1-3); they are given here as decimal.",
  "Left/right swing value 1100 (12) is printed only as '15 position'; the manual does not explain it, so the label is kept as printed.",
  "The outdoor-ambient range is printed as -100 to 155 in whole degrees and is listed as a signed 16-bit value as the table states.",
  "Several fault and status bits apply only to units that have that function (fresh-air valve, gate control, card switch, DRED)."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 17,
   "documented": "Bit17",
   "name": "Remote lock",
   "description": "Unit locked by remote monitoring or a hotel charging system.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlocked",
    "1": "Locked"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 18,
   "documented": "Bit18",
   "name": "Remote temperature shield",
   "description": "Blocks setpoint changes at the unit.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not shielded",
    "1": "Shielded"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 19,
   "documented": "Bit19",
   "name": "Remote mode shield",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not shielded",
    "1": "Shielded"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 20,
   "documented": "Bit20",
   "name": "Remote On/Off shield",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not shielded",
    "1": "Shielded"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 21,
   "documented": "Bit21",
   "name": "Remote energy-saving shield",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not shielded",
    "1": "Shielded"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 24,
   "documented": "Bit24",
   "name": "Absence mode (8 °C heating)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 25,
   "documented": "Bit25",
   "name": "Healthy function",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 26,
   "documented": "Bit26",
   "name": "I-Demand / energy-saving comfort",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "Bit27",
   "name": "Turbo",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 28,
   "documented": "Bit28",
   "name": "Electric heater permission",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Electric heater allowed",
    "1": "Electric heater not allowed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 29,
   "documented": "Bit29",
   "name": "X-fan",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 30,
   "documented": "Bit30",
   "name": "Silent",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 32,
   "documented": "Bit32",
   "name": "Energy saving in cooling active",
   "description": "Write together with bit 33.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "Bit33",
   "name": "Energy saving in heating active",
   "description": "Write together with bit 32.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "Bit34",
   "name": "Button lock (child lock)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "Bit35",
   "name": "On/Off memory",
   "description": "Whether the unit restores its on/off state after power loss.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Memorize",
    "1": "Do not memorize"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 36,
   "documented": "Bit36",
   "name": "°C/°F flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 37,
   "documented": "Bit37",
   "name": "1 °F flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 38,
   "documented": "Bit38",
   "name": "1 °F flag, cooling energy-saving limit",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 39,
   "documented": "Bit39",
   "name": "1 °F flag, heating energy-saving limit",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 40,
   "documented": "Bit40",
   "name": "Timer status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No timer",
    "1": "Timer set"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 46,
   "documented": "Bit46",
   "name": "Gate control system fitted",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 49,
   "documented": "Bit49",
   "name": "Timer On flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not active",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 50,
   "documented": "Bit50",
   "name": "Timer Off flag",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not active",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 51,
   "documented": "Bit51",
   "name": "Room temperature source in current mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Return-air sensor",
    "1": "Wired-controller sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 65,
   "documented": "Bit65",
   "name": "Wired controller temperature sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 74,
   "documented": "Bit74",
   "name": "Up and down swing mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Mode 1, simple swing",
    "1": "Mode 2, fixed angle and small-area swing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 75,
   "documented": "Bit75",
   "name": "Setpoint adjustable in auto mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 97,
   "documented": "Bit97",
   "name": "Indoor evaporator temperature sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 98,
   "documented": "Bit98",
   "name": "Indoor return-air temperature sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 101,
   "documented": "Bit101",
   "name": "Water overflow protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 104,
   "documented": "Bit104",
   "name": "Jumper cap error (indoor)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 105,
   "documented": "Bit105",
   "name": "Indoor fan error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 112,
   "documented": "Bit112",
   "name": "Card in/out status",
   "description": "Hotel key-card switch.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Card out",
    "1": "Card in"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 120,
   "documented": "Bit120",
   "name": "Communication failure with master wired controller",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 122,
   "documented": "Bit122",
   "name": "Communication failure with outdoor unit",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 147,
   "documented": "Bit147",
   "name": "Outdoor fan status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 150,
   "documented": "Bit150",
   "name": "4-way valve status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 151,
   "documented": "Bit151",
   "name": "Compressor status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 152,
   "documented": "Bit152",
   "name": "Compressor discharge temperature protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 153,
   "documented": "Bit153",
   "name": "Refrigerant shortage protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 154,
   "documented": "Bit154",
   "name": "DC fan motor protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 155,
   "documented": "Bit155",
   "name": "4-way valve reversing error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 156,
   "documented": "Bit156",
   "name": "Overpower protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 157,
   "documented": "Bit157",
   "name": "Overload protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 158,
   "documented": "Bit158",
   "name": "Low pressure protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 159,
   "documented": "Bit159",
   "name": "High pressure protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 160,
   "documented": "Bit160",
   "name": "Evaporator anti-freeze protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 161,
   "documented": "Bit161",
   "name": "Outdoor ambient temperature sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 162,
   "documented": "Bit162",
   "name": "Discharge temperature sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 163,
   "documented": "Bit163",
   "name": "Condenser temperature sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 165,
   "documented": "Bit165",
   "name": "Jumper cap error (outdoor)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 166,
   "documented": "Bit166",
   "name": "Outdoor unit memory chip error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 173,
   "documented": "Bit173",
   "name": "Indoor and outdoor units mismatched",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 174,
   "documented": "Bit174",
   "name": "Drive communication failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 177,
   "documented": "Bit177",
   "name": "Cooling-only flag",
   "description": "Heating commands have no effect on cooling-only units.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Cooling and heating",
    "1": "Cooling only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 179,
   "documented": "Bit179",
   "name": "System defrosting",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 184,
   "documented": "Bit184",
   "name": "Drive DC bus undervoltage or voltage-drop error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 185,
   "documented": "Bit185",
   "name": "Drive DC bus overvoltage protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 186,
   "documented": "Bit186",
   "name": "Drive AC input current protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 187,
   "documented": "Bit187",
   "name": "Drive IPM protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 188,
   "documented": "Bit188",
   "name": "Drive PFC protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 189,
   "documented": "Bit189",
   "name": "Inverter compressor start-up failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 190,
   "documented": "Bit190",
   "name": "Inverter compressor phase-loss protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 191,
   "documented": "Bit191",
   "name": "Drive module reset",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 192,
   "documented": "Bit192",
   "name": "Inverter compressor overcurrent protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 193,
   "documented": "Bit193",
   "name": "Inverter compressor power protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 194,
   "documented": "Bit194",
   "name": "Drive current-detection circuit failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 195,
   "documented": "Bit195",
   "name": "Inverter compressor out-of-step protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 196,
   "documented": "Bit196",
   "name": "Compressor stalling",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 198,
   "documented": "Bit198",
   "name": "Drive module high-temperature protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 199,
   "documented": "Bit199",
   "name": "Drive module temperature sensor failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 210,
   "documented": "Bit210",
   "name": "Drive charging circuit failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 211,
   "documented": "Bit211",
   "name": "Drive AC input voltage abnormal",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 214,
   "documented": "Bit214",
   "name": "Temperature drift protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 215,
   "documented": "Bit215",
   "name": "Current sensor connection protection",
   "description": "Current sensor not on the matching U or V phase.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 216,
   "documented": "Bit216",
   "name": "Indoor outlet pipe (gas side) sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 217,
   "documented": "Bit217",
   "name": "Indoor inlet pipe (liquid side) sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 218,
   "documented": "Bit218",
   "name": "Drive board ambient sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 219,
   "documented": "Bit219",
   "name": "Condenser inlet pipe sensor open/short",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 220,
   "documented": "Bit220",
   "name": "Condenser outlet pipe sensor open/short",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 221,
   "documented": "Bit221",
   "name": "Wiring error or expansion valve error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 222,
   "documented": "Bit222",
   "name": "Mode conflict protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 223,
   "documented": "Bit223",
   "name": "Compressor demagnetization protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 224,
   "documented": "Bit224",
   "name": "Whole-unit current detection error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 225,
   "documented": "Bit225",
   "name": "AC contactor protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 226,
   "documented": "Bit226",
   "name": "Overspeed",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 227,
   "documented": "Bit227",
   "name": "Outdoor fan 2 error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 228,
   "documented": "Bit228",
   "name": "PG motor zero-crossing protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 229,
   "documented": "Bit229",
   "name": "Compressor suction temperature sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 230,
   "documented": "Bit230",
   "name": "Indoor fan tripping error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 231,
   "documented": "Bit231",
   "name": "Communication error between indoor unit and grid",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 232,
   "documented": "Bit232",
   "name": "Communication error between outdoor unit and grid",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 233,
   "documented": "Bit233",
   "name": "Main error at grid side",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 234,
   "documented": "Bit234",
   "name": "Indoor network address error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 235,
   "documented": "Bit235",
   "name": "IP address allocation overflow",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 236,
   "documented": "Bit236",
   "name": "Other error or protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "Word2",
   "name": "Unit On/Off",
   "description": "Write 0xAA (170) to switch on, 0x55 (85) to switch off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "170": "On",
    "85": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "Word4",
   "name": "Ambient temperature",
   "description": "Indoor ambient temperature in tenths of a degree.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "Word5",
   "name": "IDU address",
   "description": "Modbus address of this indoor unit, 1-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "Word17",
   "name": "Set mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Cooling",
    "2": "Heating",
    "3": "Drying",
    "4": "Fan only",
    "5": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "Word19",
   "name": "Set fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4",
    "5": "Speed 5",
    "6": "Turbo"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "Word20",
   "name": "Set temperature",
   "description": "Range 16-30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "Word22",
   "name": "Up and down swing",
   "description": "Vertical louvre: off, fixed position or swing between two positions.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Swing positions 1-5",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4",
    "6": "Position 5",
    "7": "Swing positions 3-5",
    "8": "Swing positions 2-5",
    "9": "Swing positions 2-4",
    "10": "Swing positions 1-4",
    "11": "Swing positions 1-3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "Word23",
   "name": "Left and right swing",
   "description": "Horizontal louvre; off is the default after power-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Swing in same direction",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4",
    "6": "Position 5",
    "12": "Printed as \"15 position\" (meaning not explained)",
    "13": "Swing in opposite direction"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "Word24",
   "name": "Fresh air valve",
   "description": "Fresh-air valve mode 0-10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "Word25",
   "name": "Sleep mode",
   "description": "Ignored in fan and auto modes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No sleep",
    "1": "Sleep mode 1",
    "2": "Sleep mode 2",
    "3": "Sleep mode 3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "Word35",
   "name": "Cooling energy-saving lower limit",
   "description": "Lowest setpoint allowed in cooling while energy saving is active, 16-30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "Word36",
   "name": "Heating energy-saving upper limit",
   "description": "Highest setpoint allowed in heating while energy saving is active, 16-30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "Word39",
   "name": "Ambient sensor selection",
   "description": "Which sensor gives room temperature in each mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Return-air sensor always",
    "2": "Wired-controller sensor always",
    "3": "Return air in cool/dry/fan, wired controller in heat/auto",
    "4": "Wired controller in cool/dry/fan, return air in heat/auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "Word49",
   "name": "Outdoor ambient temperature",
   "description": "Whole degrees.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "Word77",
   "name": "DRED function",
   "description": "Demand-response mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No DRED",
    "1": "DRED 1",
    "2": "DRED 2",
    "3": "DRED 3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "Word82",
   "name": "Return-air temperature",
   "description": "Temperature at the indoor-unit air return, tenths of a degree.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll words 2-25 for on/off, mode, fan, setpoint and louvres and words 4, 49 and 82 for temperatures; read coils 17-236 for status and fault bits. Write word 2 (0xAA on / 0x55 off), 17, 19 and 20 to control the unit.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 19,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 20,
    "why": "Setpoint"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Room temperature"
   },
   {
    "table": "holding_register",
    "address": 49,
    "why": "Outdoor temperature"
   },
   {
    "table": "coil",
    "address": 151,
    "why": "Compressor running"
   },
   {
    "table": "coil",
    "address": 122,
    "why": "Outdoor-unit communication fault"
   }
  ],
  "enable": "The Modbus interface is built into the indoor-unit controller or wired controller; each unit needs its own address (1-255) set before connecting the BMS. Power-cycle the unit after connecting the controller.",
  "watchdog": null,
  "quirks": [
   "On/off uses 0xAA and 0x55, not 1 and 0.",
   "The two energy-saving flags (bits 32 and 33) must be set or cleared together.",
   "A setpoint outside the active energy-saving limit is silently ignored; check by reading back.",
   "Exception code 03 is returned for an out-of-range read (for example 128 words; the maximum is 127 per request)."
  ],
  "setup": [
   "RS485, 9600 baud, 8 data bits, no parity, 1 stop bit.",
   "Use twisted pair kept at least 15 cm from power cables; repeaters may be needed on long lines.",
   "Match A to A and B to B; a constantly lit TX lamp on the converter points to swapped A/B."
  ],
  "gotchas": [
   "Sleep is ignored in fan and auto modes.",
   "The remote temperature shield is ignored in auto mode unless the unit allows setpoint adjustment in auto (bit 75).",
   "Heating commands to cooling-only units (bit 177 = 1) do nothing."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/gree/export-residential-ac-modbus",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}