 "manufacturer": "Gree",
 "manufacturer_slug": "gree",
 "model": "Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems",
 "model_slug": "modbus-gateway-mini-me30-24-e6m",
 "short_model": "Gree ME30-24/E6(M)",
 "aliases": [
  "ME30-24/E6(M)",
  "Modbus Gateway(Mini)",
  "GMV5 Modbus gateway"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "Gree Modbus Gateway (Mini) on CAN-bus multi VRF systems (GMV5, GMV5 C/E/HR/MAX/MINI/SLIM, GMV Water, energy-recovery ventilation); Communication Protocol V2.0, multi VRF part only.",
 "summary": "The Gree Modbus Gateway (Mini) sits on the CAN bus of a GMV multi VRF system and serves up to 16 outdoor systems and 128 indoor units to a BMS over Modbus RTU. Holding registers carry per-indoor-unit on/off, mode, setpoint, fan speed and temperatures plus per-system outdoor data; coils carry feature flags, shields, locks and fault bits. Every indoor unit and system has an identical block, so this map lists indoor unit 1 and system 1 and gives the address rule for the rest.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The protocol numbers words from 0 and coils (bits) from 0, and its example frames send the printed number unchanged (read word 1 sends 00 01, read coil 5 sends 00 05). Word n and Bit n are wire address n. Indoor unit n uses words from 102+25*(n-1) and coils from 288+64*(n-1); system m uses words from 3302+10*(m-1) and coils from 8488+48*(m-1)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Modbus Gateway(Mini) Communication Protocol V2.0",
  "doc_number": "V2.0",
  "revision_date": null,
  "url": "https://www.asami.lt/uploads/Products/product_78/me30-24_e6-m-_mini_modbus_variable_list_en_1708354351.pdf",
  "pages": "p. 8 serial settings, pp. 8-12 frames and addressing, pp. 13-17 BMS precautions, pp. 17-27 words (multi VRF), pp. 27-42 bits (multi VRF), pp. 85-91 DIP switches",
  "unofficial": true
 },
 "notes": [
  "Gree does not host this protocol publicly; the link is a copy on a Lithuanian distributor's site (Asami) and appears to be the unaltered Gree document.",
  "Only indoor unit 1 and outdoor system 1 are listed. The source prints identical blocks for indoor units 2-128 (words +25 per unit, coils +64 per unit), systems 2-16 (words +10, coils +48) and the 'subway' on/off blocks (coils +8 per unit or system).",
  "Left out: indoor ambient temperature (word 116) and outdoor ambient temperature (word 3307). Both are sent as x10 with negative ranges, but word 116 is typed 'floating-point' and word 3307 has no data type at all, so the 16-bit encoding is not settled.",
  "Words the source skips with '...' (for example 109-114 and 120-122) are not printed there and are not listed.",
  "Mode and fan words use one set of codes for writing and another for reading; the values list shows both.",
  "The fresh air unit sections (words 4200-13159, bits 11200-27583) are not included in this map.",
  "The protocol lists function codes 0x01, 0x03, 0x0F and 0x10 only; single writes (0x05/0x06) are not listed.",
  "The ME30-24/E6(M) part number comes from the distributor's product listing; the protocol document itself only calls the device 'Modbus Gateway(Mini)'."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 88,
   "documented": "Bit 88",
   "name": "System 1 present",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Without",
    "1": "With"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 120,
   "documented": "Bit 120",
   "name": "IDU 1 present",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Without",
    "1": "With"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 248,
   "documented": "Bit 248",
   "name": "System 1 remote emergency stop",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 280,
   "documented": "Bit 280",
   "name": "Set all IDUs on",
   "description": "Group command.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 281,
   "documented": "Bit 281",
   "name": "Set all IDUs off",
   "description": "Group command.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 282,
   "documented": "Bit 282",
   "name": "Set all IDUs remotely locked",
   "description": "Group command.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 288,
   "documented": "Bit 288",
   "name": "IDU 1 remote shield: energy saving",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not shielded",
    "1": "Shielded"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 289,
   "documented": "Bit 289",
   "name": "IDU 1 remote shield: temperature setting",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not shielded",
    "1": "Shielded"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 290,
   "documented": "Bit 290",
   "name": "IDU 1 remote shield: mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not shielded",
    "1": "Shielded"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 291,
   "documented": "Bit 291",
   "name": "IDU 1 remote shield: on/off",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not shielded",
    "1": "Shielded"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 292,
   "documented": "Bit 292",
   "name": "IDU 1 remote lock",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlocked",
    "1": "Locked"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 293,
   "documented": "Bit 293",
   "name": "IDU 1 priority power supply",
   "description": "Used in the power-shortage mode of the supply system.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 294,
   "documented": "Bit 294",
   "name": "IDU 1 up-down swing",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 295,
   "documented": "Bit 295",
   "name": "IDU 1 left-right swing",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 296,
   "documented": "Bit 296",
   "name": "IDU 1 energy saving",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 297,
   "documented": "Bit 297",
   "name": "IDU 1 forbid auxiliary heater",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auxiliary heater allowed",
    "1": "Auxiliary heater forbidden"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 298,
   "documented": "Bit 298",
   "name": "IDU 1 power failure memory",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Standby after power loss",
    "1": "Power failure memory"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 299,
   "documented": "Bit 299",
   "name": "IDU 1 cancel filter cleaning reminder",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 300,
   "documented": "Bit 300",
   "name": "IDU 1 dry (X-fan)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 301,
   "documented": "Bit 301",
   "name": "IDU 1 sleep",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 302,
   "documented": "Bit 302",
   "name": "IDU 1 quiet",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 303,
   "documented": "Bit 303",
   "name": "IDU 1 ventilation (air)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 304,
   "documented": "Bit 304",
   "name": "IDU 1 low-temperature dehumidification",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cancel",
    "1": "Start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 305,
   "documented": "Bit 305",
   "name": "IDU 1 shield on command",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No shielding",
    "1": "Shielding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 306,
   "documented": "Bit 306",
   "name": "IDU 1 shield off command",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No shielding",
    "1": "Shielding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 307,
   "documented": "Bit 307",
   "name": "IDU 1 shield timer",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No shielding",
    "1": "Shielding"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 308,
   "documented": "Bit 308",
   "name": "IDU 1 8 °C heating (absence) function",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cancel",
    "1": "Start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 315,
   "documented": "Bit 315",
   "name": "IDU 1 master/slave",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Slave IDU",
    "1": "Master IDU"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 316,
   "documented": "Bit 316",
   "name": "IDU 1 auxiliary electric heater",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 318,
   "documented": "Bit 318",
   "name": "IDU 1 air outlet temperature sensor error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 319,
   "documented": "Bit 319",
   "name": "IDU 1 general error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8488,
   "documented": "Bit 8488",
   "name": "System 1 communication error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8489,
   "documented": "Bit 8489",
   "name": "System 1 refrigerant loss protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8491,
   "documented": "Bit 8491",
   "name": "System 1 power phase sequence protection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8492,
   "documented": "Bit 8492",
   "name": "System 1 VIP power supply mode started",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8493,
   "documented": "Bit 8493",
   "name": "System 1 unit debugging status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Debugging"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8494,
   "documented": "Bit 8494",
   "name": "System 1 compressor operation status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8495,
   "documented": "Bit 8495",
   "name": "System 1 general outdoor unit error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8526,
   "documented": "Bit 8526",
   "name": "System 1 outdoor EEPROM read/write error",
   "description": "Often a poorly connected outdoor main board.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9776,
   "documented": "Bit 9776",
   "name": "Subway IDU 1 on/off status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9777,
   "documented": "Bit 9777",
   "name": "Subway IDU 1 error status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10800,
   "documented": "Bit 10800",
   "name": "Subway system 1 ODU on/off / remote emergency stop",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10801,
   "documented": "Bit 10801",
   "name": "Subway system 1 ODU error status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "Word 101",
   "name": "Project no. of starting indoor unit",
   "description": "First indoor unit number served by this gateway: 1 or 129.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "Word 102",
   "name": "IDU 1 power on/off",
   "description": "0xAA (170) = on, 0x55 (85) = off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "170": "On (0xAA)",
    "85": "Off (0x55)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "Word 103",
   "name": "IDU 1 operation mode",
   "description": "Write and read codes differ; see values.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Write: invalid",
    "1": "Cooling (write and read)",
    "2": "Dehumidifying (write and read)",
    "3": "Fan / air supply (write and read)",
    "4": "Heating (write and read)",
    "5": "Write: auto / read: auto cooling",
    "6": "Write: floor heating / read: auto heating",
    "7": "Write: fast heat / read: floor heating",
    "8": "Write: heat supply / read: fast heat",
    "9": "Read: heat supply",
    "10": "Read: clothes drying",
    "11": "Read: air discharge",
    "12": "Read: cool",
    "13": "Read: auto dehumidifying"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "Word 104",
   "name": "IDU 1 temperature setpoint",
   "description": "Value x10, 16.0-30.0 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "Word 105",
   "name": "IDU 1 fan speed",
   "description": "Write and read codes differ; see values.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Write: invalid",
    "1": "Write: auto / read: fan stopped",
    "2": "Write: low / read: super low",
    "3": "Write: medium-low / read: low",
    "4": "Write: medium / read: medium-low",
    "5": "Write: medium-high / read: medium",
    "6": "Write: high / read: medium-high",
    "7": "Write: turbo / read: high",
    "8": "Read: super high",
    "9": "Read: quiet R1",
    "10": "Read: quiet R2",
    "11": "Read: quiet R3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "Word 106",
   "name": "IDU 1 cooling energy-saving lower limit",
   "description": "Value x10, 16.0-30.0 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "Word 107",
   "name": "IDU 1 heating energy-saving upper limit",
   "description": "Value x10, 16.0-30.0 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "Word 108",
   "name": "IDU 1 dehumidifying energy-saving lower limit",
   "description": "Value x10, 16.0-30.0 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "Word 115",
   "name": "IDU 1 air outlet temperature",
   "description": "Sent as actual + 100; range -30 to 138 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": -100
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "Word 117",
   "name": "IDU 1 gate (key card) control status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Invalid",
    "1": "No gate control",
    "2": "Card inserted",
    "3": "Card removed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "Word 118",
   "name": "IDU 1 outdoor unit number",
   "description": "Outdoor system (1-16) this indoor unit belongs to.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "Word 119",
   "name": "IDU 1 indoor unit category",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Duct type",
    "2": "Cassette",
    "3": "Wall mounted",
    "4": "Floor ceiling",
    "5": "Floor standing",
    "6": "Multi VRF fresh air indoor unit",
    "7": "Water heater",
    "8": "Water adaptor",
    "9": "Total heat recovery fresh air",
    "10": "Total heat recovery fresh air + heat exchanger",
    "11": "AHU-KIT",
    "12": "Air handler",
    "13": "Console type",
    "14": "Concealed floor standing type",
    "255": "Other (0xFF)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "Word 123",
   "name": "IDU 1 rated capacity",
   "description": "Rated capacity in hectowatts (22, 25 ... 560).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "hW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "Word 124",
   "name": "IDU 1 static pressure (AC fan motor)",
   "description": "Static pressure step for AC-motor models.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Invalid",
    "1": "Static pressure 1",
    "2": "Static pressure 2",
    "3": "Static pressure 3",
    "4": "Static pressure 4",
    "5": "Static pressure 5",
    "6": "Static pressure 6",
    "7": "Static pressure 7",
    "8": "Static pressure 8",
    "9": "Static pressure 9"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 125,
   "documented": "Word 125",
   "name": "IDU 1 static pressure (DC fan motor)",
   "description": "Static pressure step for DC-motor models.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Invalid",
    "1": "Static pressure 1",
    "2": "Static pressure 2",
    "3": "Static pressure 3",
    "4": "Static pressure 4",
    "5": "Static pressure 5",
    "6": "Static pressure 6",
    "7": "Static pressure 7",
    "8": "Static pressure 8",
    "9": "Static pressure 9",
    "10": "Static pressure 10",
    "11": "Static pressure 11",
    "12": "Static pressure 12",
    "13": "Static pressure 13"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3302,
   "documented": "Word 3302",
   "name": "System 1 outdoor capacity upper limit",
   "description": "Upper capacity limit of outdoor system 1, 30-100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3303,
   "documented": "Word 3303",
   "name": "System 1 running indoor unit count",
   "description": "Number of general indoor units started, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3306,
   "documented": "Word 3306",
   "name": "System 1 cooling/heating capability",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Invalid",
    "1": "Cooling only",
    "2": "Heating",
    "3": "Cooling and heating",
    "4": "Fan"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3308,
   "documented": "Word 3308",
   "name": "System 1 emergency operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Invalid",
    "1": "No emergency operation",
    "2": "Compressor emergency operation",
    "3": "Fan emergency operation",
    "4": "Module emergency operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3463,
   "documented": "Word 3463",
   "name": "All indoor units: mode setting",
   "description": "Group command to every indoor unit on the gateway.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Invalid (no change)",
    "1": "Cooling",
    "2": "Dehumidifying",
    "3": "Fan / air supply",
    "4": "Heating",
    "5": "Auto",
    "6": "Floor heating",
    "7": "Fast heat",
    "8": "Heat supply"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3464,
   "documented": "Word 3464",
   "name": "All indoor units: setpoint",
   "description": "Group command, value x10, 16.0-30.0 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3465,
   "documented": "Word 3465",
   "name": "All indoor units: fan speed",
   "description": "Group command to every indoor unit on the gateway.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Invalid (no change)",
    "1": "Auto",
    "2": "Low",
    "3": "Medium-low",
    "4": "Medium",
    "5": "Medium-high",
    "6": "High",
    "7": "Turbo"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the gateway address on DIP switches S1/S2, wire RS485 at 9600 8N1, then read coils from 120 to see which indoor units exist. Control each unit with its on/off, mode, setpoint and fan words (102-105 for unit 1) using function 0x10, and read fault coils 318-319 and system coils 8488-8495.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 102,
    "why": "IDU 1 on/off"
   },
   {
    "table": "holding_register",
    "address": 103,
    "why": "IDU 1 mode"
   },
   {
    "table": "holding_register",
    "address": 104,
    "why": "IDU 1 setpoint"
   },
   {
    "table": "holding_register",
    "address": 105,
    "why": "IDU 1 fan speed"
   },
   {
    "table": "coil",
    "address": 120,
    "why": "IDU 1 present"
   },
   {
    "table": "coil",
    "address": 319,
    "why": "IDU 1 general error"
   },
   {
    "table": "coil",
    "address": 8495,
    "why": "System 1 outdoor error"
   },
   {
    "table": "coil",
    "address": 8494,
    "why": "System 1 compressor running"
   }
  ],
  "enable": "No software enable: set the Modbus address (1-255) on DIP switches S1 and S2 inside the gateway, and S3 switch 4 for the CAN2 terminating resistor, before use.",
  "watchdog": null,
  "quirks": [
   "Power on/off uses 0xAA (on) and 0x55 (off), not 1/0.",
   "Exception code 0x04 means the gateway has no contact with the air-conditioning units; it is also returned after power-up until valid data has been collected.",
   "A read of more than 127 words is refused with exception 0x03.",
   "Writes that conflict with the outdoor unit capability, the master indoor unit mode or active energy-saving limits are ignored; read back to confirm."
  ],
  "setup": [
   "RS485, 9600 baud, 8 data bits, no parity, 1 stop bit (fixed in the protocol).",
   "Gateway address 1-255 on DIP switches S1/S2; address 0 is broadcast (writes only, no reply).",
   "One gateway serves up to 16 outdoor systems and 128 indoor units; beyond 128 indoor units use a second gateway (starting unit 129).",
   "S3 switch 2 sets the first indoor unit the gateway serves: engineering code 1 (units 1-128) or 129 (units 129-255); word 101 reports the setting.",
   "S3 switch 3 switches in the gateway's own RS485 terminating resistor; normally the BMS master end carries it and the gateway is left without.",
   "If the gateway is at either end of the CAN2 bus, set S3 switch 4 to 0 to switch in the terminating resistor."
  ],
  "gotchas": [
   "Re-commission the gateway whenever the unit engineering data (addresses, number of units) changes.",
   "Keep communication wiring at least 15 cm from power cabling."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/gree/modbus-gateway-mini-me30-24-e6m",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}