 "manufacturer": "Grundfos",
 "manufacturer_slug": "grundfos",
 "model": "MP 204 motor protector with CIU 200 / CIU 500 (Modbus)",
 "model_slug": "mp-204-ciu-200-500",
 "short_model": "MP 204 Modbus",
 "aliases": [
  "MP 204",
  "CIU 200 Modbus RTU",
  "CIU 250 GSM/GPRS",
  "CIU 500 Modbus TCP",
  "98393513"
 ],
 "equipment_type": "Pump motor protection relay",
 "applies_to": "Grundfos MP 204 electronic motor protector connected over GENIbus to a CIU 200 (Modbus RTU), CIU 250 (GSM/GPRS) or CIU 500 (Modbus TCP) box; functional profile 98393513 (2014-11).",
 "summary": "The MP 204 is Grundfos's electronic motor protector for single- and three-phase pump motors. A CIU communication box talks GENIbus to the MP 204 and presents it as a Modbus slave, with blocks for CIU settings, CIU status, one control register, protector status and measured data. The map covers start/stop and trip commands, alarm and warning codes, phase voltages and currents, power factor, power, energy, run hours, start counters and insulation resistance.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "Registers are printed as 5-digit register numbers; the telegram examples address register X as X-1 (ControlRegister 00101 is written at address 0x0064). The RegisterOffset register 00002 shifts every address above 00100 if it is changed from its default 0."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Modbus for MP 204 - CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Ethernet for Modbus TCP - Functional profile and user manual",
  "doc_number": "98393513 1114",
  "revision_date": "2014-11",
  "url": "https://api.grundfos.com/literature/Grundfosliterature-6012935.pdf",
  "pages": "pp. 5-8 (RTU specs, DIP switches), 14-24 (function codes, register blocks), 30-33 (telegram examples)"
 },
 "notes": [
  "All registers can be read with function 03 or 04 (the same data is in both tables); they are listed here as holding registers. Control and configuration registers are written with 06 or 16.",
  "32-bit values are split into HI and LO registers with the HI (high-order) part at the lower address, so they are ABCD.",
  "A raw value of 65535 (0xFFFF) means 'not available'. Several values exist only for 1-phase or only for 3-phase motors, or need the optional sensors (Tempcon, Pt100).",
  "Motor temperatures are given in 0.01 K as printed; the manual does not say whether an offset of 273.15 applies, so no offset is set here.",
  "Left out: CIU 250-only registers (GSM real-time clock 00080-00097, GeneralStatus/PIN bits 00029, GSM battery 00033, NoDataActivityTimeout 00008, GSM signal and IP address 00236-00239) and the free user registers 00751-00800.",
  "Software-defined parity and stop-bit defaults (none / 1 stop bit) apply only in software-defined mode; the DIP-switch default is even parity, 1 stop bit."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "00001",
   "name": "SlaveMinimumReplyDelay",
   "description": "Extra reply delay, 0-10000 ms (default 0).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "00002",
   "name": "RegisterOffset",
   "description": "Offset added to every address above 00100; default 0, normally leave it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "00003",
   "name": "SoftwareDefinedModbusAddress",
   "description": "Slave address used only in software-defined mode (default 231).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "00004",
   "name": "SoftwareDefinedBitRate",
   "description": "Used only when SW4/SW5 select software-defined speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1200",
    "1": "2400",
    "2": "4800",
    "3": "9600",
    "4": "19200",
    "5": "38400"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "00005",
   "name": "AutoAckControlBits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (clear control bits yourself)",
    "1": "Enabled (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "00009",
   "name": "SoftwareDefinedParity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None (default)",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "00010",
   "name": "SoftwareDefinedStopBit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No stop bit",
    "1": "1 stop bit (default)",
    "2": "2 stop bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "00021",
   "name": "GENIbusCRCErrorCnt",
   "description": "CRC errors on the internal GENIbus link to the MP 204.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "00022",
   "name": "GENIbusDataErrorCnt",
   "description": "Data errors on the internal GENIbus link.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "00023",
   "name": "VersionNumber",
   "description": "Grundfos-specific version number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "00024",
   "name": "ActualModbusAddress",
   "description": "Slave address in use (1-247).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "00025",
   "name": "GENIbusTXcount",
   "description": "Telegrams sent to the MP 204 (HI/LO pair).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "00027",
   "name": "GENIbusRXcount",
   "description": "Telegrams received from the MP 204 (HI/LO pair).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "00030",
   "name": "UnitFamily",
   "description": "Grundfos product family.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "00031",
   "name": "UnitType",
   "description": "Grundfos product type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "00032",
   "name": "UnitVersion",
   "description": "Grundfos product version.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "00101",
   "name": "ControlRegister",
   "description": "Command bits; reset bits act on a 0 to 1 edge.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "ResetAlarm",
    "1": "CommandedTrip",
    "2": "OnOffReq (1 = on/start, 0 = off/stop)",
    "3": "ProtectionEnabled (1 = enabled)",
    "5": "ResetStartCounter",
    "6": "ResetRestartCounter",
    "7": "ResetLogs (min/max logs 00348-00352)",
    "8": "ResetHourCounter (operating-time trip counter)",
    "9": "ResetEnergyCounter (energy trip counter)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "00201",
   "name": "StatusRegister",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Rotation (motor consuming power)",
    "1": "Protection enabled",
    "2": "Ready",
    "3": "Unacknowledged fault pending",
    "4": "PTC open",
    "5": "Phase sequence left (L3-L2-L1)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "00202",
   "name": "OperatingMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Started (on)",
    "1": "Commanded trip",
    "2": "Actuator stop (off)",
    "3": "Protection stop (alarm trip)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "00203",
   "name": "SystemMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Power-up",
    "1": "Operating",
    "2": "MP 204 fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 203,
   "documented": "00204",
   "name": "AlarmCode",
   "description": "Cause of the last motor protection trip.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "2": "Missing phase",
    "3": "External alarm signal (PTC)",
    "4": "Too many automatic restarts per 24 h",
    "9": "Phase sequence reversal",
    "15": "Communication alarm, main system",
    "18": "Test trip",
    "20": "Insulation resistance low",
    "32": "Overvoltage",
    "40": "Undervoltage",
    "48": "Overload (current too high)",
    "56": "Underload (current too low)",
    "64": "Overtemperature, Tempcon",
    "71": "Overtemperature, Pt100",
    "111": "Current asymmetry",
    "112": "Cos phi too high",
    "113": "Cos phi too low",
    "120": "Auxiliary winding alarm",
    "123": "Start capacitor low",
    "124": "Run capacitor low"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "00205",
   "name": "WarningBits1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Overvoltage (32)",
    "1": "Undervoltage (40)",
    "2": "Overload (48)",
    "3": "Underload (56)",
    "4": "Current asymmetry (111)",
    "8": "Insulation resistance low (20)",
    "9": "Overtemperature Tempcon (64)",
    "10": "Overtemperature Pt100 (71)",
    "12": "Cos phi too high (112)",
    "13": "Cos phi too low (113)",
    "14": "Too many starts per hour (21)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 205,
   "documented": "00206",
   "name": "WarningBits2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Start capacitor low (123)",
    "1": "Run capacitor low (124)",
    "3": "Signal fault, Tempcon sensor (91)",
    "4": "Signal fault, Pt100 sensor (175)",
    "5": "Service warning (12)",
    "6": "Load continues with relay R1 off (26)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 206,
   "documented": "00207",
   "name": "Relays",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Motor control relay closed",
    "1": "Alarm signal relay closed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 207,
   "documented": "00208",
   "name": "AcknowledgeRegister",
   "description": "Command acknowledgements; used only when AutoAckControlBits = 0.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "ResetAlarmAck",
    "1": "TripAck",
    "5": "ResetStartCounterAck",
    "6": "ResetRestartCounterAck",
    "7": "ResetLogsAck",
    "8": "ResetHourCounterAck",
    "9": "ResetEnergyCounterAck"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "00301",
   "name": "PhaseVoltageL1",
   "description": "3-phase: L1 phase voltage; 1-phase: reference (0).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 301,
   "documented": "00302",
   "name": "PhaseVoltageL2",
   "description": "3-phase: L2 phase voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "00303",
   "name": "PhaseVoltageL3",
   "description": "3-phase: L3 phase voltage; 1-phase: auxiliary winding voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 303,
   "documented": "00304",
   "name": "PhaseVoltageMean",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "00305",
   "name": "LineVoltageL1L2",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 305,
   "documented": "00306",
   "name": "LineVoltageL2L3",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "00307",
   "name": "LineVoltageL3L1",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 307,
   "documented": "00308",
   "name": "LineVoltageMean",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "00309",
   "name": "LineCurrentL1",
   "description": "1-phase: neutral current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 309,
   "documented": "00310",
   "name": "LineCurrentL2",
   "description": "1-phase: mains winding current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "00311",
   "name": "LineCurrentL3",
   "description": "1-phase: auxiliary winding current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 311,
   "documented": "00312",
   "name": "LineCurrentMean",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 312,
   "documented": "00313",
   "name": "LineCurrentStart",
   "description": "Peak line current at the latest motor start.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 313,
   "documented": "00314",
   "name": "MotorTemp1",
   "description": "Motor temperature from Tempcon, in 0.01 K.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "00315",
   "name": "MotorTemp2",
   "description": "Motor temperature from the Pt sensor, in 0.01 K.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 315,
   "documented": "00316",
   "name": "LineCurrentAsym",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 316,
   "documented": "00317",
   "name": "CapacitorStart",
   "description": "1-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µF",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 317,
   "documented": "00318",
   "name": "CapacitorRun",
   "description": "1-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µF",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 318,
   "documented": "00319",
   "name": "CapacitorStartRef",
   "description": "1-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µF",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 319,
   "documented": "00320",
   "name": "CapacitorRunRef",
   "description": "1-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µF",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 320,
   "documented": "00321",
   "name": "LineFrequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 321,
   "documented": "00322",
   "name": "VoltageAngleL1L2",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 322,
   "documented": "00323",
   "name": "VoltageAngleL1L3",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 323,
   "documented": "00324",
   "name": "CosPhiL1",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 324,
   "documented": "00325",
   "name": "CosPhiL2",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 325,
   "documented": "00326",
   "name": "CosPhiL3",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 326,
   "documented": "00327",
   "name": "CosPhi",
   "description": "Mean power factor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 327,
   "documented": "00328",
   "name": "Power",
   "description": "Power consumption (HI/LO pair).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 329,
   "documented": "00330",
   "name": "Energy",
   "description": "Energy consumption (HI/LO pair).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 331,
   "documented": "00332",
   "name": "EnergyTripCounter",
   "description": "Resettable with ControlRegister bit 9.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 333,
   "documented": "00334",
   "name": "OperationTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 335,
   "documented": "00336",
   "name": "TotalPoweredTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 337,
   "documented": "00338",
   "name": "OperationTimeTripCounter",
   "description": "Resettable with ControlRegister bit 8.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 339,
   "documented": "00340",
   "name": "NumberOfStarts",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 341,
   "documented": "00342",
   "name": "NumberOfStartsTripCounter",
   "description": "Resettable with ControlRegister bit 5.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 343,
   "documented": "00344",
   "name": "AutoRestartsTripCounter",
   "description": "Resettable with ControlRegister bit 6.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 345,
   "documented": "00346",
   "name": "InsulationResistance",
   "description": "3-phase only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 10,
   "units": "kΩ",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 346,
   "documented": "00347",
   "name": "PhaseVoltageDistortion",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 347,
   "documented": "00348",
   "name": "VoltageMaxLog",
   "description": "Logged maximum line voltage; reset with bit 7.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 348,
   "documented": "00349",
   "name": "VoltageMinLog",
   "description": "Logged minimum line voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 349,
   "documented": "00350",
   "name": "CurrentLineMaxLog",
   "description": "Logged maximum line current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 350,
   "documented": "00351",
   "name": "CurrentLineMinLog",
   "description": "Logged minimum line current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 351,
   "documented": "00352",
   "name": "StartsHourMaxLog",
   "description": "Logged maximum starts per hour.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 352,
   "documented": "00353",
   "name": "StartsPerHour",
   "description": "Moving average.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 353,
   "documented": "00354",
   "name": "AutoRestartsPer24h",
   "description": "Moving average.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 700,
   "documented": "00701",
   "name": "SimulationWarningBits1",
   "description": "Simulated warnings/alarms, bits as in 00205/00206.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 701,
   "documented": "00702",
   "name": "SimulationWarningBits2",
   "description": "Simulated warnings/alarms, bits as in 00205/00206.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 702,
   "documented": "00703",
   "name": "SimulationAlarmBits1",
   "description": "Simulated warnings/alarms, bits as in 00205/00206.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 703,
   "documented": "00704",
   "name": "SimulationAlarmBits2",
   "description": "Simulated warnings/alarms, bits as in 00205/00206.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the CIU 200 slave address on the two hex switches, keep 19200 8E1, then poll 00201-00208 for status and alarm, and 00301-00354 for measurements. Start, stop and trip the pump through ControlRegister 00101.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 100,
    "why": "Start/stop, trip and reset commands"
   },
   {
    "table": "holding_register",
    "address": 200,
    "why": "Running, ready and fault flags"
   },
   {
    "table": "holding_register",
    "address": 201,
    "why": "Operating mode"
   },
   {
    "table": "holding_register",
    "address": 203,
    "why": "Alarm code"
   },
   {
    "table": "holding_register",
    "address": 204,
    "why": "Active warnings"
   },
   {
    "table": "holding_register",
    "address": 311,
    "why": "Mean line current"
   },
   {
    "table": "holding_register",
    "address": 327,
    "why": "Power consumption"
   },
   {
    "table": "holding_register",
    "address": 329,
    "why": "Energy counter"
   }
  ],
  "enable": "The MP 204 needs no setting for remote control; configure it with the R100, Grundfos GO or PC Tool first, then connect the CIU. OnOffReq (bit 2 of 00101) starts and stops the motor; the device acts on the last command from Modbus, remote or buttons.",
  "watchdog": null,
  "quirks": [
   "Reset and trip bits act on a rising edge. With AutoAckControlBits = 1 (default) the CIU clears them itself; with 0 you must clear them and watch 00208.",
   "Data block values are unsigned unless stated; 0xFFFF means not available."
  ],
  "setup": [
   "CIU 200: address on rotary switches SW6/SW7 (hex, high and low nibble), speed on SW4/SW5 (9600, 19200 default, 38400, or software-defined), parity on SW3 (even/1 stop default, or none/2 stop), termination on SW1/SW2.",
   "CIU 500: Modbus TCP on port 502."
  ],
  "gotchas": [
   "Changing RegisterOffset (00002) moves every register above 00100; leave it at 0.",
   "Single-phase motors report different meanings in the L1-L3 voltage and current registers (neutral, main winding, auxiliary winding)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/grundfos/mp-204-ciu-200-500",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}