 "manufacturer": "Grundfos",
 "manufacturer_slug": "grundfos",
 "model": "SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)",
 "model_slug": "seg-autoadapt-ciu-202-502",
 "short_model": "SEG AUTOADAPT Modbus",
 "aliases": [
  "SEG AUTOADAPT",
  "CIU 202",
  "CIU 262",
  "CIU 502",
  "96846341"
 ],
 "equipment_type": "Pump (submersible grinder pump pit)",
 "applies_to": "Up to four Grundfos SEG AUTOADAPT grinder pumps in one or more pits, connected to a CIU 202 (Modbus RTU), CIU 262 (cellular) or CIU 502 (Modbus TCP); functional profile 96846341 (2019-01).",
 "summary": "SEG AUTOADAPT grinder pumps carry their own level sensing and control; a CIU box links up to four of them to a Modbus master. The map covers the pit commands and start/stop levels for single-pit and multi-pit operation, pit state and alarm bits, pit energy and run-time counters, and a 50-register block per pump with temperatures, voltage, current, power, energy, starts, level and alarm/warning bits.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual says registers numbered X are addressed in telegrams as X - 1 (00104 is sent as 103). Pump n's block starts at 00401 + 50 x (n-1)."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Modbus for SEG AUTOADAPT - CIU 202 Modbus RTU, CIU 262 3G/4G Cellular, CIU 502 Ethernet for Modbus TCP - Functional profile and user manual",
  "doc_number": "96846341 0119",
  "revision_date": "2019-01",
  "url": "https://api.grundfos.com/literature/Grundfosliterature-6012945.pdf",
  "pages": "p. 16 (block overview), pp. 17-19 (CIM blocks), pp. 20-26 (pit control and status), p. 27 (pit data), pp. 28-35 (pump blocks), p. 43 (telegram addressing)"
 },
 "notes": [
  "32-bit values are HI/LO register pairs with the HI part at the lower address, so they are ABCD.",
  "All registers can be read with function 03 or 04 and are listed as holding registers. 0xFFFF means not available.",
  "Pumps 2-4 repeat the pump 1 layout at +50 (00451, 00501, 00551); checked against the printed pump 2-4 tables.",
  "Left out: register 00202, because its bit names (bit 0 AlarmInPumpOrPit, bit 1 WarningInPumpOrPit) contradict their descriptions; 00235 carries the same main status consistently and is listed instead. Also left out: the acknowledge register 00201, CIU 262-only cellular registers (RTC, 00236-00239) and user registers.",
  "Motor and electronics temperatures are printed in 0.01 K; no 273.15 offset is applied here."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "00001",
   "name": "SlaveMinimumReplyDelay",
   "description": "Extra reply delay 0-10000 ms (default 0).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "00002",
   "name": "RegisterOffset",
   "description": "Offset added to addresses above 00100; default 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "00005",
   "name": "AutoAckControlBits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "00024",
   "name": "ActualModbusAddress",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "00030",
   "name": "UnitFamily",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "00031",
   "name": "UnitType",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "00032",
   "name": "UnitVersion",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "00101",
   "name": "PitControl",
   "description": "Command bits, act on a 0 to 1 edge.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "ResetAlarm",
    "1": "ResetHistory",
    "2": "PitPump1ResetHistory",
    "6": "PitPump1ResetAlarm",
    "10": "PitPump1PumpDown (pump down once, then level control stops it)",
    "3": "PitPump2ResetHistory",
    "7": "PitPump2ResetAlarm",
    "11": "PitPump2PumpDown (pump down once, then level control stops it)",
    "4": "PitPump3ResetHistory",
    "8": "PitPump3ResetAlarm",
    "12": "PitPump3PumpDown (pump down once, then level control stops it)",
    "5": "PitPump4ResetHistory",
    "9": "PitPump4ResetAlarm",
    "13": "PitPump4PumpDown (pump down once, then level control stops it)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "00102",
   "name": "SetSinglePitStopLevel",
   "description": "Single-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "00103",
   "name": "SetSinglePitStartLevelMax",
   "description": "Single-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "00104",
   "name": "SetSinglePitStartLevelBand",
   "description": "Single-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "00105",
   "name": "SetSinglePitHighWaterLevel",
   "description": "Single-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "00106",
   "name": "SetMultiPitPump1StopLevel",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "00107",
   "name": "SetMultiPitPump1StartLevelMax",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "00108",
   "name": "SetMultiPitPump1StartLevelBand",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "00109",
   "name": "SetMultiPitPump1HighWaterLevel",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "00110",
   "name": "SetMultiPitPump2StopLevel",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "00111",
   "name": "SetMultiPitPump2StartLevelMax",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "00112",
   "name": "SetMultiPitPump2StartLevelBand",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "00113",
   "name": "SetMultiPitPump2HighWaterLevel",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "00114",
   "name": "SetMultiPitPump3StopLevel",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "00115",
   "name": "SetMultiPitPump3StartLevelMax",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "00116",
   "name": "SetMultiPitPump3StartLevelBand",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 116,
   "documented": "00117",
   "name": "SetMultiPitPump3HighWaterLevel",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "00118",
   "name": "SetMultiPitPump4StopLevel",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "00119",
   "name": "SetMultiPitPump4StartLevelMax",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "00120",
   "name": "SetMultiPitPump4StartLevelBand",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "00121",
   "name": "SetMultiPitPump4HighWaterLevel",
   "description": "Multi-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 121,
   "documented": "00122",
   "name": "PitPump1Control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Forced start",
    "2": "Forced stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "00123",
   "name": "PitPump2Control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Forced start",
    "2": "Forced stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "00124",
   "name": "PitPump3Control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Forced start",
    "2": "Forced stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "00125",
   "name": "PitPump4Control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Forced start",
    "2": "Forced stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "00203",
   "name": "PitMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Single-pit",
    "1": "Multi-pit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 203,
   "documented": "00204",
   "name": "SinglePitStopLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "00205",
   "name": "SinglePitStartLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 205,
   "documented": "00206",
   "name": "SinglePitStartLevelBand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 206,
   "documented": "00207",
   "name": "SinglePitHighWaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 207,
   "documented": "00208",
   "name": "MultiPitPump1StopLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "00209",
   "name": "MultiPitPump1StartLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 209,
   "documented": "00210",
   "name": "MultiPitPump1StartLevelBand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "00211",
   "name": "MultiPitPump1HighWaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 211,
   "documented": "00212",
   "name": "MultiPitPump2StopLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 212,
   "documented": "00213",
   "name": "MultiPitPump2StartLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 213,
   "documented": "00214",
   "name": "MultiPitPump2StartLevelBand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 214,
   "documented": "00215",
   "name": "MultiPitPump2HighWaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 215,
   "documented": "00216",
   "name": "MultiPitPump3StopLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 216,
   "documented": "00217",
   "name": "MultiPitPump3StartLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 217,
   "documented": "00218",
   "name": "MultiPitPump3StartLevelBand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 218,
   "documented": "00219",
   "name": "MultiPitPump3HighWaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 219,
   "documented": "00220",
   "name": "MultiPitPump4StopLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 220,
   "documented": "00221",
   "name": "MultiPitPump4StartLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 221,
   "documented": "00222",
   "name": "MultiPitPump4StartLevelBand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 222,
   "documented": "00223",
   "name": "MultiPitPump4HighWaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 223,
   "documented": "00224",
   "name": "PitPump1OperationMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto",
    "1": "Started",
    "2": "Stopped"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 224,
   "documented": "00225",
   "name": "PitPump2OperationMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto",
    "1": "Started",
    "2": "Stopped"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 225,
   "documented": "00226",
   "name": "PitPump3OperationMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto",
    "1": "Started",
    "2": "Stopped"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 226,
   "documented": "00227",
   "name": "PitPump4OperationMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto",
    "1": "Started",
    "2": "Stopped"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 227,
   "documented": "00228",
   "name": "AlarmCode",
   "description": "Grundfos alarm code of the pit (see manual section 14.2).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 228,
   "documented": "00229",
   "name": "WarningCode",
   "description": "Grundfos warning code of the pit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 229,
   "documented": "00230",
   "name": "PitPumpsPresent",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Pump 1 present",
    "1": "Pump 2 present",
    "2": "Pump 3 present",
    "3": "Pump 4 present"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 230,
   "documented": "00231",
   "name": "PitPumpsRunning",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Pump 1 running",
    "1": "Pump 2 running",
    "2": "Pump 3 running",
    "3": "Pump 4 running"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 231,
   "documented": "00232",
   "name": "PitPumpsAlarm",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Pump 1 alarm",
    "1": "Pump 2 alarm",
    "2": "Pump 3 alarm",
    "3": "Pump 4 alarm"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 232,
   "documented": "00233",
   "name": "PitPumpsCommFault",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Pump 1 communication fault",
    "1": "Pump 2 communication fault",
    "2": "Pump 3 communication fault",
    "3": "Pump 4 communication fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 233,
   "documented": "00234",
   "name": "OperatingMode",
   "description": "Single-pit mode only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Standby",
    "1": "Startup delay",
    "2": "Pumping (level control)",
    "5": "Stopped (level control)",
    "9": "Manual control",
    "11": "Mains supply failure",
    "13": "Alarm on all enabled pumps",
    "14": "All pumps out of operation"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 234,
   "documented": "00235",
   "name": "MainStatus",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Warning in pump or pit",
    "1": "Alarm in pump or pit",
    "3": "Manual pump control enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 239,
   "documented": "00240",
   "name": "AlarmBits",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "External fault signal",
    "1": "Communication fault, pump",
    "3": "Pump 1 fault",
    "4": "Pump 2 fault",
    "5": "Pump 3 fault",
    "6": "Pump 4 fault",
    "7": "Sensor limit 2 exceeded (high level)",
    "8": "Setup conflict"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 240,
   "documented": "00241",
   "name": "WarningBits",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "Communication fault, pump",
    "2": "Verification error (ROM, FLASH)",
    "8": "Setup conflict"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "00301",
   "name": "WaterLevel",
   "description": "Pit level estimated by the pumps; single-pit mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 301,
   "documented": "00302",
   "name": "MaxWaterLevel",
   "description": "Highest level seen; reset with ResetHistory.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "00303",
   "name": "Power",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "00305",
   "name": "EnergyTripCnt",
   "description": "Resettable with ResetHistory.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "00307",
   "name": "OnTimeCnt",
   "description": "CIU power-on time; cannot be reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "00309",
   "name": "OprTimeTripCnt",
   "description": "Time with one or more pumps running.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "00311",
   "name": "PumpOperationTimePct",
   "description": "Share of time pumping, last 30 days.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 311,
   "documented": "00312",
   "name": "MultiPumpOperationTimePct",
   "description": "Share of pumping time with several pumps, 30 days.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 312,
   "documented": "00313",
   "name": "MultiPumpOperationTimeMax",
   "description": "Longest multi-pump run, last 30 days.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 313,
   "documented": "00314",
   "name": "DigitalInput",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "00401",
   "name": "Pump1.MotorTemperature",
   "description": "In 0.01 K (kelvin).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "00402",
   "name": "Pump1.ElectronicTemperature",
   "description": "In 0.01 K (kelvin).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "00403",
   "name": "Pump1.AverageLineVoltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 403,
   "documented": "00404",
   "name": "Pump1.AverageLineCurrent",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 404,
   "documented": "00405",
   "name": "Pump1.AverageLineCurrentLatest",
   "description": "Current during the last run.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 405,
   "documented": "00406",
   "name": "Pump1.LineFrequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 406,
   "documented": "00407",
   "name": "Pump1.PhaseSequence",
   "description": "Boolean phase-sequence state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 407,
   "documented": "00408",
   "name": "Pump1.CosPhi",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 408,
   "documented": "00409",
   "name": "Pump1.Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 409,
   "documented": "00410",
   "name": "Pump1.EnergyTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 411,
   "documented": "00412",
   "name": "Pump1.WaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "00413",
   "name": "Pump1.WaterLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 413,
   "documented": "00414",
   "name": "Pump1.MaxContinousTime",
   "description": "Longest continuous run, last 30 days.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 414,
   "documented": "00415",
   "name": "Pump1.TotalPoweredTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 416,
   "documented": "00417",
   "name": "Pump1.OperationTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 418,
   "documented": "00419",
   "name": "Pump1.OperationTimeTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 420,
   "documented": "00421",
   "name": "Pump1.NumberOfStarts",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 422,
   "documented": "00423",
   "name": "Pump1.NumberOfStartsTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 424,
   "documented": "00425",
   "name": "Pump1.AlarmCode",
   "description": "Grundfos alarm code (manual section 14.2).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 425,
   "documented": "00426",
   "name": "Pump1.WarningCode",
   "description": "Grundfos warning code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 426,
   "documented": "00427",
   "name": "Pump1.OperatingMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto (power-on default)",
    "1": "Forced start",
    "2": "Forced stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 427,
   "documented": "00428",
   "name": "Pump1.Alarms",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase sequence reversed",
    "1": "Overvoltage",
    "2": "Undervoltage",
    "3": "Overload",
    "4": "Blocked motor/pump",
    "6": "Motor temperature",
    "7": "Control electronics temperature",
    "8": "Temperature relay 1 (e.g. Klixon)",
    "9": "Temperature relay 2 (e.g. thermistor)",
    "10": "Verification error (ROM, FLASH)",
    "12": "Sensor fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 428,
   "documented": "00429",
   "name": "Pump1.Warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase sequence reversed",
    "1": "Overvoltage",
    "2": "Undervoltage",
    "3": "Overload",
    "4": "Blocked motor/pump",
    "6": "Motor temperature",
    "7": "Control electronics temperature",
    "8": "Temperature relay 1 (e.g. Klixon)",
    "9": "Temperature relay 2 (e.g. thermistor)",
    "10": "Verification error (ROM, FLASH)",
    "12": "Sensor fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 450,
   "documented": "00451",
   "name": "Pump2.MotorTemperature",
   "description": "In 0.01 K (kelvin).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 451,
   "documented": "00452",
   "name": "Pump2.ElectronicTemperature",
   "description": "In 0.01 K (kelvin).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 452,
   "documented": "00453",
   "name": "Pump2.AverageLineVoltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 453,
   "documented": "00454",
   "name": "Pump2.AverageLineCurrent",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 454,
   "documented": "00455",
   "name": "Pump2.AverageLineCurrentLatest",
   "description": "Current during the last run.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 455,
   "documented": "00456",
   "name": "Pump2.LineFrequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 456,
   "documented": "00457",
   "name": "Pump2.PhaseSequence",
   "description": "Boolean phase-sequence state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 457,
   "documented": "00458",
   "name": "Pump2.CosPhi",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 458,
   "documented": "00459",
   "name": "Pump2.Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 459,
   "documented": "00460",
   "name": "Pump2.EnergyTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 461,
   "documented": "00462",
   "name": "Pump2.WaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 462,
   "documented": "00463",
   "name": "Pump2.WaterLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 463,
   "documented": "00464",
   "name": "Pump2.MaxContinousTime",
   "description": "Longest continuous run, last 30 days.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 464,
   "documented": "00465",
   "name": "Pump2.TotalPoweredTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 466,
   "documented": "00467",
   "name": "Pump2.OperationTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 468,
   "documented": "00469",
   "name": "Pump2.OperationTimeTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 470,
   "documented": "00471",
   "name": "Pump2.NumberOfStarts",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 472,
   "documented": "00473",
   "name": "Pump2.NumberOfStartsTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 474,
   "documented": "00475",
   "name": "Pump2.AlarmCode",
   "description": "Grundfos alarm code (manual section 14.2).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 475,
   "documented": "00476",
   "name": "Pump2.WarningCode",
   "description": "Grundfos warning code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 476,
   "documented": "00477",
   "name": "Pump2.OperatingMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto (power-on default)",
    "1": "Forced start",
    "2": "Forced stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 477,
   "documented": "00478",
   "name": "Pump2.Alarms",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase sequence reversed",
    "1": "Overvoltage",
    "2": "Undervoltage",
    "3": "Overload",
    "4": "Blocked motor/pump",
    "6": "Motor temperature",
    "7": "Control electronics temperature",
    "8": "Temperature relay 1 (e.g. Klixon)",
    "9": "Temperature relay 2 (e.g. thermistor)",
    "10": "Verification error (ROM, FLASH)",
    "12": "Sensor fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 478,
   "documented": "00479",
   "name": "Pump2.Warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase sequence reversed",
    "1": "Overvoltage",
    "2": "Undervoltage",
    "3": "Overload",
    "4": "Blocked motor/pump",
    "6": "Motor temperature",
    "7": "Control electronics temperature",
    "8": "Temperature relay 1 (e.g. Klixon)",
    "9": "Temperature relay 2 (e.g. thermistor)",
    "10": "Verification error (ROM, FLASH)",
    "12": "Sensor fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "00501",
   "name": "Pump3.MotorTemperature",
   "description": "In 0.01 K (kelvin).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 501,
   "documented": "00502",
   "name": "Pump3.ElectronicTemperature",
   "description": "In 0.01 K (kelvin).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 502,
   "documented": "00503",
   "name": "Pump3.AverageLineVoltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 503,
   "documented": "00504",
   "name": "Pump3.AverageLineCurrent",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 504,
   "documented": "00505",
   "name": "Pump3.AverageLineCurrentLatest",
   "description": "Current during the last run.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 505,
   "documented": "00506",
   "name": "Pump3.LineFrequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 506,
   "documented": "00507",
   "name": "Pump3.PhaseSequence",
   "description": "Boolean phase-sequence state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 507,
   "documented": "00508",
   "name": "Pump3.CosPhi",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 508,
   "documented": "00509",
   "name": "Pump3.Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 509,
   "documented": "00510",
   "name": "Pump3.EnergyTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 511,
   "documented": "00512",
   "name": "Pump3.WaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "00513",
   "name": "Pump3.WaterLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 513,
   "documented": "00514",
   "name": "Pump3.MaxContinousTime",
   "description": "Longest continuous run, last 30 days.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 514,
   "documented": "00515",
   "name": "Pump3.TotalPoweredTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 516,
   "documented": "00517",
   "name": "Pump3.OperationTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 518,
   "documented": "00519",
   "name": "Pump3.OperationTimeTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 520,
   "documented": "00521",
   "name": "Pump3.NumberOfStarts",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 522,
   "documented": "00523",
   "name": "Pump3.NumberOfStartsTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 524,
   "documented": "00525",
   "name": "Pump3.AlarmCode",
   "description": "Grundfos alarm code (manual section 14.2).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 525,
   "documented": "00526",
   "name": "Pump3.WarningCode",
   "description": "Grundfos warning code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 526,
   "documented": "00527",
   "name": "Pump3.OperatingMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto (power-on default)",
    "1": "Forced start",
    "2": "Forced stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 527,
   "documented": "00528",
   "name": "Pump3.Alarms",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase sequence reversed",
    "1": "Overvoltage",
    "2": "Undervoltage",
    "3": "Overload",
    "4": "Blocked motor/pump",
    "6": "Motor temperature",
    "7": "Control electronics temperature",
    "8": "Temperature relay 1 (e.g. Klixon)",
    "9": "Temperature relay 2 (e.g. thermistor)",
    "10": "Verification error (ROM, FLASH)",
    "12": "Sensor fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 528,
   "documented": "00529",
   "name": "Pump3.Warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase sequence reversed",
    "1": "Overvoltage",
    "2": "Undervoltage",
    "3": "Overload",
    "4": "Blocked motor/pump",
    "6": "Motor temperature",
    "7": "Control electronics temperature",
    "8": "Temperature relay 1 (e.g. Klixon)",
    "9": "Temperature relay 2 (e.g. thermistor)",
    "10": "Verification error (ROM, FLASH)",
    "12": "Sensor fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 550,
   "documented": "00551",
   "name": "Pump4.MotorTemperature",
   "description": "In 0.01 K (kelvin).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 551,
   "documented": "00552",
   "name": "Pump4.ElectronicTemperature",
   "description": "In 0.01 K (kelvin).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 552,
   "documented": "00553",
   "name": "Pump4.AverageLineVoltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 553,
   "documented": "00554",
   "name": "Pump4.AverageLineCurrent",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 554,
   "documented": "00555",
   "name": "Pump4.AverageLineCurrentLatest",
   "description": "Current during the last run.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 555,
   "documented": "00556",
   "name": "Pump4.LineFrequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 556,
   "documented": "00557",
   "name": "Pump4.PhaseSequence",
   "description": "Boolean phase-sequence state.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 557,
   "documented": "00558",
   "name": "Pump4.CosPhi",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 558,
   "documented": "00559",
   "name": "Pump4.Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 559,
   "documented": "00560",
   "name": "Pump4.EnergyTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 561,
   "documented": "00562",
   "name": "Pump4.WaterLevel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 562,
   "documented": "00563",
   "name": "Pump4.WaterLevelMax",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "m",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 563,
   "documented": "00564",
   "name": "Pump4.MaxContinousTime",
   "description": "Longest continuous run, last 30 days.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 564,
   "documented": "00565",
   "name": "Pump4.TotalPoweredTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 566,
   "documented": "00567",
   "name": "Pump4.OperationTime",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 568,
   "documented": "00569",
   "name": "Pump4.OperationTimeTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 570,
   "documented": "00571",
   "name": "Pump4.NumberOfStarts",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 572,
   "documented": "00573",
   "name": "Pump4.NumberOfStartsTripCounter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 574,
   "documented": "00575",
   "name": "Pump4.AlarmCode",
   "description": "Grundfos alarm code (manual section 14.2).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 575,
   "documented": "00576",
   "name": "Pump4.WarningCode",
   "description": "Grundfos warning code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 576,
   "documented": "00577",
   "name": "Pump4.OperatingMode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Auto (power-on default)",
    "1": "Forced start",
    "2": "Forced stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 577,
   "documented": "00578",
   "name": "Pump4.Alarms",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase sequence reversed",
    "1": "Overvoltage",
    "2": "Undervoltage",
    "3": "Overload",
    "4": "Blocked motor/pump",
    "6": "Motor temperature",
    "7": "Control electronics temperature",
    "8": "Temperature relay 1 (e.g. Klixon)",
    "9": "Temperature relay 2 (e.g. thermistor)",
    "10": "Verification error (ROM, FLASH)",
    "12": "Sensor fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 578,
   "documented": "00579",
   "name": "Pump4.Warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase sequence reversed",
    "1": "Overvoltage",
    "2": "Undervoltage",
    "3": "Overload",
    "4": "Blocked motor/pump",
    "6": "Motor temperature",
    "7": "Control electronics temperature",
    "8": "Temperature relay 1 (e.g. Klixon)",
    "9": "Temperature relay 2 (e.g. thermistor)",
    "10": "Verification error (ROM, FLASH)",
    "12": "Sensor fault"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 00230-00235 for pump presence, running, alarm and the pit main status, 00301 for the pit level, and each pump block for current, power and alarm bits. Force pumps with 00122-00125 or use the PumpDown bits of PitControl 00101.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 230,
    "why": "Pumps running bits"
   },
   {
    "table": "holding_register",
    "address": 231,
    "why": "Pumps in alarm bits"
   },
   {
    "table": "holding_register",
    "address": 234,
    "why": "Warning / alarm / manual summary"
   },
   {
    "table": "holding_register",
    "address": 300,
    "why": "Pit water level"
   },
   {
    "table": "holding_register",
    "address": 100,
    "why": "Reset and pump-down commands"
   },
   {
    "table": "holding_register",
    "address": 403,
    "why": "Pump 1 current"
   },
   {
    "table": "holding_register",
    "address": 427,
    "why": "Pump 1 alarm bits"
   }
  ],
  "enable": "Set the CIU 202 address with the hex rotary switches and the speed and parity with the DIP switches; no setting is needed in the pumps. Write the pit levels only in the mode selected by PitMode (00203).",
  "watchdog": null,
  "quirks": [
   "Control bits are rising-edge commands; with AutoAckControlBits = 1 (default) the CIU clears them.",
   "Single-pit and multi-pit level registers are separate; the unused set is ignored."
  ],
  "setup": [
   "CIU 202 default 19200 baud, even parity, 1 stop bit.",
   "CIU 502: Modbus TCP on port 502."
  ],
  "gotchas": [
   "A changed RegisterOffset (00002) shifts all addresses above 00100."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/grundfos/seg-autoadapt-ciu-202-502",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}