 "manufacturer": "Hitachi",
 "manufacturer_slug": "hitachi",
 "model": "SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)",
 "model_slug": "sj-p1",
 "short_model": "Hitachi SJ-P1",
 "aliases": [
  "SJ-P1",
  "P1-xxxxx-L",
  "P1-xxxxx-H"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Hitachi SJ-P1 inverters on the built-in RS485 port in Modbus-RTU mode, register layout of firmware Ver. 2.00 (User's Guide NT251BX-2, Rev. 6).",
 "summary": "The SJ-P1 high-function inverter answers Modbus RTU on its RS485 terminals. Coils carry run/stop, direction, reset and the input/output terminals; holding registers carry the dA/db/dC monitors, trip history, RS485 frequency, torque and PID commands and every parameter. This map lists the control set, main monitors, trip monitor 1 and the CF communication parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The guide prints register and coil numbers in decimal and hex and says the start number in the frame is the number minus 1; its examples read trip monitor 1 (register 03E9h) with start 03E8h and write coil 1 with start 0000h. So wire address = printed number - 1."
 },
 "default_word_order": "ABCD",
 "firmware": "Ver. 2.00 register layout (several register numbers differ in Ver. 1.xx)",
 "source": {
  "title": "SJ-P1 Series Inverter User's Guide (chapters 1-20)",
  "doc_number": "NT251BX-2 Rev. 6",
  "revision_date": null,
  "url": "https://www.hitachi-iesa.com/sites/default/files/supportdocs/SJ-P1_Users_guide_chapter1-20_Rev06_NT251BX-2.pdf",
  "pages": "pp. 14-5 (CF parameters), 14-11/14-12 (read examples), 14-26 to 14-41 (coil and register lists)"
 },
 "notes": [
  "Two-register values are printed as (High) then (Low) register; the guide's read example returns 60.00 Hz as 0000h then 1770h, so the high word comes first (ABCD).",
  "This register layout is for firmware Ver. 2.00. The guide lists items whose register number or range changed from Ver. 1.xx (for example dA-04 was one unsigned register in Ver. 1.xx).",
  "Only a working subset is listed. Later trip monitors repeat the trip monitor 1 block every 20 registers (trip monitor 2 at 1021, 3 at 1041 ...). The full parameter list is in chapter 14.6.",
  "AA101/AA111 are listed without full value tables; the guide states 08 = RS485 for AA101 and 03 = RS485 for AA111. CF-08 (communication method) is left out because its printed codes (00-02) and register range (1-3) disagree.",
  "Monitor and setting ranges assume CF-11 register data selection = 00 (A, V). With 01 (%), current and voltage items read as % of rating.",
  "The single-register input/output power monitors (dA-30, dA-34) are left out: their printed resolution changes with drive size and is given in kWh for a power value."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "Coil 1 (0001h)",
   "name": "Operation command",
   "description": "Works when AA111/AA211 = 03.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "Coil 2 (0002h)",
   "name": "Rotation direction command",
   "description": "Works when AA111/AA211 = 03.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal (forward)",
    "1": "Reverse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "Coil 3 (0003h)",
   "name": "External trip [EXT]",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not trip",
    "1": "Trip"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "Coil 4 (0004h)",
   "name": "Trip reset [RS]",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not reset",
    "1": "Reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "Coil 5 (0005h)",
   "name": "Input terminal 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "Coil 6 (0006h)",
   "name": "Input terminal 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "Coil 7 (0007h)",
   "name": "Input terminal 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "Coil 8 (0008h)",
   "name": "Input terminal 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "Coil 9 (0009h)",
   "name": "Input terminal 5",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "Coil 10 (000Ah)",
   "name": "Input terminal 6",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "Coil 11 (000Bh)",
   "name": "Input terminal 7",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "Coil 12 (000Ch)",
   "name": "Input terminal 8",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "Coil 13 (000Dh)",
   "name": "Input terminal 9",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "Coil 14 (000Eh)",
   "name": "Input terminal A",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 14,
   "documented": "Coil 15 (000Fh)",
   "name": "Input terminal B",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 20,
   "documented": "Coil 21 (0015h)",
   "name": "Operating status",
   "description": "1 while rotating forward or reverse (linked with dA-03).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not rotating",
    "1": "Rotating"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 21,
   "documented": "Coil 22 (0016h)",
   "name": "Rotation direction",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal direction",
    "1": "Reverse direction"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 22,
   "documented": "Coil 23 (0017h)",
   "name": "Inverter operation ready",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not ready",
    "1": "Ready"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 24,
   "documented": "Coil 25 (0019h)",
   "name": "Output terminal 11",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 25,
   "documented": "Coil 26 (001Ah)",
   "name": "Output terminal 12",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 26,
   "documented": "Coil 27 (001Bh)",
   "name": "Output terminal 13",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "Coil 28 (001Ch)",
   "name": "Output terminal 14",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 28,
   "documented": "Coil 29 (001Dh)",
   "name": "Output terminal 15",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 29,
   "documented": "Coil 30 (001Eh)",
   "name": "Output terminal 16",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 30,
   "documented": "Coil 31 (001Fh)",
   "name": "Output terminal AL",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 72,
   "documented": "Coil 73 (0049h)",
   "name": "Data being written",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal state",
    "1": "Being written"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 73,
   "documented": "Coil 74 (004Ah)",
   "name": "CRC error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "With error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 74,
   "documented": "Coil 75 (004Bh)",
   "name": "Overrun error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "With error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 75,
   "documented": "Coil 76 (004Ch)",
   "name": "Framing error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "With error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 76,
   "documented": "Coil 77 (004Dh)",
   "name": "Parity error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "With error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 77,
   "documented": "Coil 78 (004Eh)",
   "name": "Sum check error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "With error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 999,
   "documented": "1000 (03E8h)",
   "name": "Trip count monitor (dE-01)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "times",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "1001 (03E9h)",
   "name": "Trip monitor 1 factor",
   "description": "Trip cause code, 1-255 (e.g. 7 = overvoltage E007).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "1002 / 1003 (03EAh high, 03EBh low)",
   "name": "Trip monitor 1 output frequency",
   "description": "Signed.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "1004 (03ECh)",
   "name": "Trip monitor 1 output current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "1005 (03EDh)",
   "name": "Trip monitor 1 P-N DC voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1011,
   "documented": "1012 / 1013 (03F4h high, 03F5h low)",
   "name": "Trip monitor 1 RUN time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1013,
   "documented": "1014 / 1015 (03F6h high, 03F7h low)",
   "name": "Trip monitor 1 power-on time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10000,
   "documented": "10001 (2711h)",
   "name": "Output frequency monitor (dA-01)",
   "description": "0-590.00 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10001,
   "documented": "10002 (2712h)",
   "name": "Output current monitor (dA-02)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10002,
   "documented": "10003 (2713h)",
   "name": "Operation direction monitor (dA-03)",
   "description": "0-3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10003,
   "documented": "10004 / 10005 (2714h high, 2715h low)",
   "name": "Frequency command after calculation (dA-04)",
   "description": "Signed, Ver. 2.00 layout.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10007,
   "documented": "10008 / 10009 (2718h high, 2719h low)",
   "name": "Speed detection value monitor (dA-08)",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10011,
   "documented": "10012 / 10013 (271Ch high, 271Dh low)",
   "name": "Output frequency monitor with sign (dA-12)",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10014,
   "documented": "10015 (271Fh)",
   "name": "Torque command monitor after calculation (dA-15)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10016,
   "documented": "10017 (2721h)",
   "name": "Output torque monitor (dA-17)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10017,
   "documented": "10018 (2722h)",
   "name": "Output voltage monitor (dA-18)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10031,
   "documented": "10032 / 10033 (2730h high, 2731h low)",
   "name": "Integrated input power monitor (dA-32)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10035,
   "documented": "10036 / 10037 (2734h high, 2735h low)",
   "name": "Integrated output power monitor (dA-36)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10037,
   "documented": "10038 (2736h)",
   "name": "Motor temperature monitor (dA-38)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10039,
   "documented": "10040 (2738h)",
   "name": "DC voltage monitor (dA-40)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10040,
   "documented": "10041 (2739h)",
   "name": "BRD load factor monitor (dA-41)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10041,
   "documented": "10042 (273Ah)",
   "name": "Electronic thermal load factor, motor (dA-42)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10042,
   "documented": "10043 (273Bh)",
   "name": "Electronic thermal load factor, controller (dA-43)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10050,
   "documented": "10051 (2743h)",
   "name": "Input terminal monitor (dA-51)",
   "description": "Packed input terminal states.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10053,
   "documented": "10054 (2746h)",
   "name": "Output terminal monitor (dA-54)",
   "description": "Packed output terminal states.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10060,
   "documented": "10061 (274Dh)",
   "name": "Analog input [Ai1] monitor (dA-61)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10061,
   "documented": "10062 (274Eh)",
   "name": "Analog input [Ai2] monitor (dA-62)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10062,
   "documented": "10063 (274Fh)",
   "name": "Analog input [Ai3] monitor (dA-63)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10149,
   "documented": "10150 (27A6h)",
   "name": "PID1 output monitor (db-50)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10150,
   "documented": "10151 (27A7h)",
   "name": "PID1 deviation monitor (db-51)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10201,
   "documented": "10202 (27DAh)",
   "name": "Rated current monitor (dC-02)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10214,
   "documented": "10215 (27E7h)",
   "name": "Cooling fin temperature monitor (dC-15)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10215,
   "documented": "10216 (27E8h)",
   "name": "Life diagnostic monitor (dC-16)",
   "description": "Packed life warning flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10219,
   "documented": "10220 (27ECh)",
   "name": "Total start-up count (dC-20)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10220,
   "documented": "10221 (27EDh)",
   "name": "Power-on count (dC-21)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10221,
   "documented": "10222 / 10223 (27EEh high, 27EFh low)",
   "name": "Cumulative operating hours during RUN (dC-22)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10223,
   "documented": "10224 / 10225 (27F0h high, 27F1h low)",
   "name": "Cumulative power-on time (dC-24)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10225,
   "documented": "10226 / 10227 (27F2h high, 27F3h low)",
   "name": "Cumulative cooling fan operating time (dC-26)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10249,
   "documented": "10250 (280Ah)",
   "name": "Firmware version monitor (dC-50)",
   "description": "High byte major, low byte minor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10501,
   "documented": "10502 / 10503 (2906h high, 2907h low)",
   "name": "RS485 set frequency",
   "description": "Signed frequency command for main and auxiliary speed.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10525,
   "documented": "10526 (291Eh)",
   "name": "RS485 torque command",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10545,
   "documented": "10546 / 10547 (2932h high, 2933h low)",
   "name": "RS485 PID target value",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10553,
   "documented": "10554 / 10555 (293Ah high, 293Bh low)",
   "name": "RS485 PID feedback data",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11000,
   "documented": "11001 (2AF9h)",
   "name": "Main speed command (FA-01)",
   "description": "Monitor and setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11009,
   "documented": "11010 / 11011 (2B02h high, 2B03h low)",
   "name": "Acceleration time (FA-10)",
   "description": "Monitor and setting.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11011,
   "documented": "11012 / 11013 (2B04h high, 2B05h low)",
   "name": "Deceleration time (FA-12)",
   "description": "Monitor and setting.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12000,
   "documented": "12001 (2EE1h)",
   "name": "First main speed command selection (AA101)",
   "description": "Range 1-16; 08 = command from RS485.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12010,
   "documented": "12011 (2EEBh)",
   "name": "First operation command selection (AA111)",
   "description": "Range 0-6; 03 = run command from RS485.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12219,
   "documented": "12220 / 12221 (2FBCh high, 2FBDh low)",
   "name": "First acceleration time 1 (AC120)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12221,
   "documented": "12222 / 12223 (2FBEh high, 2FBFh low)",
   "name": "First deceleration time 1 (AC122)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14500,
   "documented": "14501 (38A5h)",
   "name": "Communication baud rate (CF-01)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "3": "2400 bps",
    "4": "4800 bps",
    "5": "9600 bps",
    "6": "19200 bps",
    "7": "38400 bps",
    "8": "57600 bps",
    "9": "76800 bps",
    "10": "115200 bps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14501,
   "documented": "14502 (38A6h)",
   "name": "Communication station number (CF-02)",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14502,
   "documented": "14503 (38A7h)",
   "name": "Communication parity (CF-03)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity",
    "1": "Even parity",
    "2": "Odd parity"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14503,
   "documented": "14504 (38A8h)",
   "name": "Communication stop bits (CF-04)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1 bit",
    "2": "2 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14504,
   "documented": "14505 (38A9h)",
   "name": "Communication error selection (CF-05)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Trip",
    "1": "Trip after decelerating and stopping",
    "2": "Ignore",
    "3": "Free-run stop",
    "4": "Deceleration stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14505,
   "documented": "14506 (38AAh)",
   "name": "Communication timeout time (CF-06)",
   "description": "0.00-100.00 s; loss longer than this raises E041.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14506,
   "documented": "14507 (38ABh)",
   "name": "Communication waiting time (CF-07)",
   "description": "Reply delay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16059,
   "documented": "16060 (3EBCh)",
   "name": "Coil data 0 (coils 0001h-000Fh)",
   "description": "Packed control coils as one word.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16060,
   "documented": "16061 (3EBDh)",
   "name": "Coil data 1 (coils 0010h-001Fh)",
   "description": "Packed status coils as one word.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set CF-01 to CF-04 for the serial line and CF-08 to Modbus-RTU, then AA101 = 08 and AA111 = 03. Write the signed frequency to 10502/10503, run and stop with coil 1, and poll dA-01, dA-02, dA-40 and the trip monitor.",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 0,
    "why": "Run/stop"
   },
   {
    "table": "coil",
    "address": 3,
    "why": "Trip reset"
   },
   {
    "table": "holding_register",
    "address": 10501,
    "why": "RS485 set frequency"
   },
   {
    "table": "holding_register",
    "address": 10000,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 10001,
    "why": "Output current"
   },
   {
    "table": "holding_register",
    "address": 10039,
    "why": "DC bus voltage"
   },
   {
    "table": "holding_register",
    "address": 1000,
    "why": "Latest trip factor"
   },
   {
    "table": "coil",
    "address": 22,
    "why": "Inverter ready"
   }
  ],
  "enable": "Select Modbus-RTU with CF-08, then set AA101 = 08 (speed from RS485) and AA111 = 03 (run command from RS485). Coils 1 and 2 only act when AA111 = 03.",
  "watchdog": "CF-06 sets the communication timeout (0.00-100.00 s); when it expires error E041 is raised, and CF-05 picks the action (trip, trip after stop, ignore, free-run stop or deceleration stop).",
  "quirks": [
   "Wire address is the printed number minus 1.",
   "Two-register values are high word first.",
   "Register numbers changed between firmware Ver. 1.xx and 2.00; check the firmware with dC-50 before using this map."
  ],
  "setup": [
   "CF-01 baud (03-10 = 2400-115200 bps), CF-02 station 1-247, CF-03 parity, CF-04 stop bits; CF-07 adds a reply delay.",
   "One request handles at most 32 coils or 16 registers; a coil read of 0 or more than 32 coils returns exception 03h."
  ],
  "gotchas": [
   "The [NDc] output signal can be assigned to an output terminal to flag a communication loss."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/hitachi/sj-p1",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}