 "manufacturer": "Hitachi",
 "manufacturer_slug": "hitachi",
 "model": "SJ700-2 series inverter (Modbus RTU)",
 "model_slug": "sj700-2",
 "short_model": "SJ700-2",
 "aliases": [
  "SJ700",
  "SJ700-2",
  "SJ700 series"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Hitachi SJ700-2 series inverters using the built-in RS485 port (TM2) in Modbus-RTU mode (C079), per instruction manual NT204DX.",
 "summary": "The SJ700-2 is Hitachi's general-purpose sensorless-vector inverter with a built-in RS485 port that speaks Hitachi ASCII or Modbus RTU. Commands and status flags are coils, the frequency reference and monitors are holding registers, and 32-bit values are split into high and low registers. This map covers the run and terminal coils, status coils, frequency command, key d-monitors and accel/decel times.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Coil and register numbers are printed in hex (0001h). The manual says the starting number in a request is 1 less than the coil or register number, e.g. reading coils from 0007h sends 00 06. So wire address = printed number - 1."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Hitachi Inverter SJ700-2 Series Instruction Manual",
  "doc_number": "NT204DX",
  "revision_date": "2009-02",
  "url": "https://www.hitachi-iesa.com/sites/default/files/support/inverter/docs/NT204DX_1.pdf",
  "pages": "4-114 (comm specs), 4-131 to 4-139 (Modbus function examples), 4-140 to 4-145 (coil and register lists)"
 },
 "notes": [
  "32-bit values are two registers labelled (high) then (low), so ABCD.",
  "The trip-monitoring block 0010h-004Eh (trip counter, six trip records, programming error code) is documented but not included in this map.",
  "Inverter status A (0003h) is left out because its value list is cut off in the table, and cumulative RUN time (1015h) because its 0.1 resolution has no unit printed.",
  "Cumulative power (1013h) is listed raw with 0.1 resolution as printed; the manual gives the value as input power divided by the b079 display gain, so no fixed unit is assigned.",
  "Function-mode parameter registers (1201h and up) are documented in the manual but not listed here.",
  "Communication error coils 004Ah-004Eh stay set until an error reset.",
  "Coil 0013h is left out: the table names it RUN (running) but its setting column reads 1 = tripping, 0 = normal.",
  "Coil 0049h (data writing in progress) is left out: the Enter-command note points to coil 001Ah for that flag, while the coil table puts OTQ at 001Ah and data writing at 0049h."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "0001h",
   "name": "Operation command",
   "description": "1 = run, 0 = stop (when A002 = 03).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "0002h",
   "name": "Rotation direction command",
   "description": "1 = reverse, 0 = forward (when A002 = 03).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "0003h",
   "name": "External trip (EXT)",
   "description": "1 = trip.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "0004h",
   "name": "Trip reset (RS)",
   "description": "1 = reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "0007h",
   "name": "Intelligent input terminal [1]",
   "description": "Turns the input on over the network; the physical terminal has priority.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "0008h",
   "name": "Intelligent input terminal [2]",
   "description": "Turns the input on over the network; the physical terminal has priority.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "0009h",
   "name": "Intelligent input terminal [3]",
   "description": "Turns the input on over the network; the physical terminal has priority.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "000Ah",
   "name": "Intelligent input terminal [4]",
   "description": "Turns the input on over the network; the physical terminal has priority.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "000Bh",
   "name": "Intelligent input terminal [5]",
   "description": "Turns the input on over the network; the physical terminal has priority.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "000Ch",
   "name": "Intelligent input terminal [6]",
   "description": "Turns the input on over the network; the physical terminal has priority.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "000Dh",
   "name": "Intelligent input terminal [7]",
   "description": "Turns the input on over the network; the physical terminal has priority.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "000Eh",
   "name": "Intelligent input terminal [8]",
   "description": "Turns the input on over the network; the physical terminal has priority.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 14,
   "documented": "000Fh",
   "name": "Operation status",
   "description": "1 = run, 0 = stop.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 15,
   "documented": "0010h",
   "name": "Rotation direction",
   "description": "1 = reverse, 0 = forward.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 16,
   "documented": "0011h",
   "name": "Inverter ready",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 19,
   "documented": "0014h",
   "name": "FA1 constant-speed reached",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 20,
   "documented": "0015h",
   "name": "FA2 set frequency overreached",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 21,
   "documented": "0016h",
   "name": "OL overload notice advance signal 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 22,
   "documented": "0017h",
   "name": "OD output deviation for PID",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 23,
   "documented": "0018h",
   "name": "AL alarm signal",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 24,
   "documented": "0019h",
   "name": "FA3 set frequency reached",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 25,
   "documented": "001Ah",
   "name": "OTQ over-torque",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 26,
   "documented": "001Bh",
   "name": "IP instantaneous power failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "001Ch",
   "name": "UV undervoltage",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 28,
   "documented": "001Dh",
   "name": "TRQ torque limited",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 29,
   "documented": "001Eh",
   "name": "RNT operation time over",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 30,
   "documented": "001Fh",
   "name": "ONT plug-in time over",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 31,
   "documented": "0020h",
   "name": "THM thermal alarm signal",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 50,
   "documented": "0033h",
   "name": "NDc communication train disconnection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 57,
   "documented": "003Ah",
   "name": "WAC capacitor life warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 58,
   "documented": "003Bh",
   "name": "WAF cooling-fan speed drop",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 60,
   "documented": "003Dh",
   "name": "OHF heat sink overheat warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 68,
   "documented": "0045h",
   "name": "IRDY inverter ready",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 69,
   "documented": "0046h",
   "name": "FWR forward rotation",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 70,
   "documented": "0047h",
   "name": "RVR reverse rotation",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 71,
   "documented": "0048h",
   "name": "MJA major failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 73,
   "documented": "004Ah",
   "name": "CRC error",
   "description": "Kept until an error reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 74,
   "documented": "004Bh",
   "name": "Overrun",
   "description": "Kept until an error reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 75,
   "documented": "004Ch",
   "name": "Framing error",
   "description": "Kept until an error reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 76,
   "documented": "004Dh",
   "name": "Parity error",
   "description": "Kept until an error reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 77,
   "documented": "004Eh",
   "name": "Sum check error",
   "description": "Kept until an error reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0001h-0002h",
   "name": "Frequency source setting (F001)",
   "description": "0-40000; used when A001 = 03.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0004h",
   "name": "Inverter status B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stopping",
    "1": "Running",
    "2": "Tripping"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0005h",
   "name": "Inverter status C",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "---",
    "1": "Stopping",
    "2": "Decelerating",
    "3": "Constant-speed operation",
    "4": "Accelerating",
    "5": "Forward rotation",
    "6": "Reverse rotation",
    "7": "Switching forward to reverse",
    "8": "Switching reverse to forward",
    "9": "Starting forward rotation",
    "10": "Starting reverse rotation"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0006h",
   "name": "PID feedback",
   "description": "0-10000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2303,
   "documented": "0900h",
   "name": "Writing to EEPROM",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": {
    "0": "Motor constant recalculation",
    "1": "Store set data in EEPROM"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4096,
   "documented": "1001h-1002h",
   "name": "Output frequency (d001)",
   "description": "0-40000.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4098,
   "documented": "1003h",
   "name": "Output current (d002)",
   "description": "0-9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4099,
   "documented": "1004h",
   "name": "Rotation direction (d003)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stopping",
    "1": "Forward rotation",
    "2": "Reverse rotation"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4100,
   "documented": "1005h-1006h",
   "name": "PV / PID feedback (d004)",
   "description": "0-9990.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4102,
   "documented": "1007h",
   "name": "Intelligent input terminal status (d005)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Terminal 1",
    "1": "Terminal 2",
    "2": "Terminal 3",
    "3": "Terminal 4",
    "4": "Terminal 5",
    "5": "Terminal 6",
    "6": "Terminal 7",
    "7": "Terminal 8"
   }
  },
  {
   "table": "holding_register",
   "address": 4103,
   "documented": "1008h",
   "name": "Intelligent output terminal status (d006)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Terminal 11",
    "1": "Terminal 12",
    "2": "Terminal 13",
    "3": "Terminal 14",
    "4": "Terminal 15"
   }
  },
  {
   "table": "holding_register",
   "address": 4104,
   "documented": "1009h-100Ah",
   "name": "Scaled output frequency (d007)",
   "description": "0-39960.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4106,
   "documented": "100Bh-100Ch",
   "name": "Actual frequency (d008)",
   "description": "-40000 to +40000.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4108,
   "documented": "100Dh",
   "name": "Torque command (d009)",
   "description": "-200 to +200.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4109,
   "documented": "100Eh",
   "name": "Torque bias (d010)",
   "description": "-200 to +200.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4111,
   "documented": "1010h",
   "name": "Torque (d012)",
   "description": "-200 to +200.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4112,
   "documented": "1011h",
   "name": "Output voltage (d013)",
   "description": "0-6000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4113,
   "documented": "1012h",
   "name": "Power (d014)",
   "description": "0-9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4114,
   "documented": "1013h-1014h",
   "name": "Cumulative power (d015)",
   "description": "0-9999999; input power divided by the b079 display gain.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4118,
   "documented": "1017h-1018h",
   "name": "Cumulative power-on time (d017)",
   "description": "0-999900.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4120,
   "documented": "1019h",
   "name": "Heat sink temperature (d018)",
   "description": "-200 to 2000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4121,
   "documented": "101Ah",
   "name": "Motor temperature (d019)",
   "description": "-200 to 2000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4124,
   "documented": "101Dh",
   "name": "Life-check (d022)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Main circuit capacitor",
    "1": "Low cooling-fan speed"
   }
  },
  {
   "table": "holding_register",
   "address": 4133,
   "documented": "1026h",
   "name": "DC voltage P-N (d102)",
   "description": "0-9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4134,
   "documented": "1027h",
   "name": "BRD load factor (d103)",
   "description": "0-1000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4135,
   "documented": "1028h",
   "name": "Electronic thermal overload (d104)",
   "description": "0-1000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4354,
   "documented": "1103h-1104h",
   "name": "Acceleration (1) time (F002)",
   "description": "1-360000.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4356,
   "documented": "1105h-1106h",
   "name": "Deceleration (1) time (F003)",
   "description": "1-360000.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4358,
   "documented": "1107h",
   "name": "Keypad Run key routing (F004)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Forward rotation",
    "1": "Reverse rotation"
   },
   "bits": null
  }
 ],
 "integration": {
  "summary": "Set A001 = 03 and A002 = 03, write the frequency to registers 0001h-0002h (wire 0-1, 0.01 Hz) and run with coil 0001h (wire 0). Read output frequency at 1001h-1002h and current at 1003h.",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 0,
    "why": "Run/stop command"
   },
   {
    "table": "coil",
    "address": 1,
    "why": "Direction command"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Frequency command (F001)"
   },
   {
    "table": "holding_register",
    "address": 4096,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 4098,
    "why": "Output current"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Inverter status B (run/trip)"
   }
  ],
  "enable": "Set C079 (communication mode) to Modbus-RTU, C071 speed, C072 node address, C074 parity, C075 stop bits and C078 wait time on the keypad; set A001 = 03 and A002 = 03 to take frequency and run commands over the network.",
  "watchdog": "C077 sets the reception timeout (0.00-99.99 s) and C076 picks the action after a timeout (trip, decelerate and trip, ignore, free-run stop, or decelerate and stop); the NDc output (coil 0033h) signals the disconnection.",
  "quirks": [
   "Requests use the printed number minus 1.",
   "32-bit values are high word first."
  ],
  "setup": [
   "RS485 on terminal block TM2 (SP, SN); use RP-SN to enable the terminating resistor.",
   "2400-19200 bps, 8 data bits in Modbus-RTU mode, up to 32 inverters."
  ],
  "gotchas": [
   "The physical intelligent input terminals override the input coils.",
   "Register writes are lost at power-off unless 1 is written to 0900h to store them in EEPROM."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/hitachi/sj700-2",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}