 "manufacturer": "Hitachi",
 "manufacturer_slug": "hitachi",
 "model": "WJ-C1 series inverter (Modbus RTU)",
 "model_slug": "wj-c1",
 "short_model": "Hitachi WJ-C1",
 "aliases": [
  "WJ-C1",
  "WJ-C1 series"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Hitachi WJ-C1 inverters using the built-in RS485 port in Modbus-RTU mode; User's Guide NT361X, chapters 11 and 18.",
 "summary": "The WJ-C1 compact inverter has an RS485 port that speaks Modbus RTU. Coils give run/stop, direction, reset and the intelligent input and output signals; holding registers give status words, the frequency command, all d-group monitors, trip history and every parameter. This map covers control, the main monitors, the latest trip record and the communication parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The manual prints coil and register numbers in hex starting at 0001h and says the start number in the frame is the register number minus 1 (its coil read example asks for coil 0007h with 0006h). So wire address = printed number - 1: register 1001h is wire 0x1000."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "WJ-C1 Series Inverter User's Guide",
  "doc_number": "NT361X",
  "revision_date": null,
  "url": "https://www.hitachi-iesa.com/sites/default/files/supportingdocs/WJ-C1_UsersGuide_NT361X.pdf",
  "pages": "ch. 11 (RS485 communication, endian selection p. 11-2-14), ch. 18 pp. 18-1-1 to 18-2-4 (coils, special registers, d group, F group), A and C groups"
 },
 "notes": [
  "Two-register values are printed as (High) then (Low) register. With Endian selection [P400] = 00 Big endian (default) a two-register value 01020304h is sent as 01 02 03 04, which is ABCD. Little endian (01) and special endian (02) change the byte order; trip history registers 0012h-004Eh always read big endian.",
  "Only a working subset is listed: control coils, status words, main d-group monitors, trip monitor 1, F001-F004, A001/A002 and the C07x communication settings. Trip monitors 2-6 follow at 001Ch, 0026h, 0030h, 003Ah and 0044h with the same layout as trip monitor 1. The full parameter list is in chapter 18.",
  "Accumulated input power [d015] is in units of 1 kWh multiplied by the [b079] gain, so no fixed unit is given here.",
  "Inverter state A (0003h) has no code 1 in the source.",
  "Coils 0010h-0058h can also be read as packed words at 1E01h-1E05h, and coils 0001h-000Fh written via 1F01h; not listed separately.",
  "The rotation direction monitor [d003] is printed with keypad symbols only (F / o / r for 0-2); the exact code-to-symbol order is not stated, so no value list is given."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "Coil 0001h",
   "name": "RUN command",
   "description": "Works when [A002] = 03.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "Coil 0002h",
   "name": "Rotation direction command",
   "description": "Works when [A002] = 03.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Forward",
    "1": "Reverse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "Coil 0003h",
   "name": "External trip (EXT)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Trip"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "Coil 0004h",
   "name": "Reset (RS)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "Coil 0007h",
   "name": "Intelligent input terminal 1",
   "description": "OR-ed with the physical terminal.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "Coil 0008h",
   "name": "Intelligent input terminal 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "Coil 0009h",
   "name": "Intelligent input terminal 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "Coil 000Ah",
   "name": "Intelligent input terminal 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "Coil 000Bh",
   "name": "Intelligent input terminal 5",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "Coil 000Ch",
   "name": "Intelligent input terminal 6",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "Coil 000Dh",
   "name": "Intelligent input terminal 7",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 14,
   "documented": "Coil 000Fh",
   "name": "Operation status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 15,
   "documented": "Coil 0010h",
   "name": "Rotation direction",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Forward",
    "1": "Reverse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 16,
   "documented": "Coil 0011h",
   "name": "Inverter ready",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not ready",
    "1": "Ready"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 18,
   "documented": "Coil 0013h",
   "name": "RUN (running)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 19,
   "documented": "Coil 0014h",
   "name": "FA1 constant-frequency reached",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 21,
   "documented": "Coil 0016h",
   "name": "OL overload warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 23,
   "documented": "Coil 0018h",
   "name": "AL alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "Coil 001Ch",
   "name": "UV undervoltage",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 31,
   "documented": "Coil 0020h",
   "name": "THM motor electronic thermal alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 50,
   "documented": "Coil 0033h",
   "name": "NDc communication line disconnection",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 57,
   "documented": "Coil 003Ah",
   "name": "WAC capacitor life warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 58,
   "documented": "Coil 003Bh",
   "name": "WAF cooling-fan life warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 60,
   "documented": "Coil 003Dh",
   "name": "OHF cooling fin overheat warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 71,
   "documented": "Coil 0048h",
   "name": "MJA major failure",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 73,
   "documented": "Coil 004Ah",
   "name": "CRC error",
   "description": "Latched until an error reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "With error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 83,
   "documented": "Coil 0054h",
   "name": "FREF frequency reference by keypad",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Other than keypad",
    "1": "Keypad"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 84,
   "documented": "Coil 0055h",
   "name": "REF RUN command by keypad",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Other than keypad",
    "1": "Keypad"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0001h (High) / 0002h (Low)",
   "name": "Output frequency setting / monitor [F001]",
   "description": "Frequency command; 0.00 to max frequency (or PID % when PID on).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0003h",
   "name": "Inverter state A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Initial state",
    "2": "Stop",
    "3": "Running",
    "4": "Free run stop",
    "5": "Jogging",
    "6": "DC braking",
    "7": "Retry",
    "8": "Trip",
    "9": "Undervoltage"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0004h",
   "name": "Inverter status B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stop",
    "1": "Running",
    "2": "Trip"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0005h",
   "name": "Inverter status C",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "---",
    "1": "Stop",
    "2": "Decelerating",
    "3": "Constant speed",
    "4": "Accelerating",
    "5": "Forward",
    "6": "Reverse",
    "7": "Forward to reverse",
    "8": "Reverse to forward",
    "9": "Forward start",
    "10": "Reverse start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0006h",
   "name": "PID feedback",
   "description": "PID feedback written over Modbus, 0-100.00 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0011h",
   "name": "Trip count monitor [d080]",
   "description": "Number of trips, 0-65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "times",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0012h",
   "name": "Trip monitor 1: trip code [d081]",
   "description": "Latest trip code E01-E99.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0013h",
   "name": "Trip monitor 1: inverter status at trip",
   "description": "Status digit n (0-9) shown after the trip code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0014h (High) / 0015h (Low)",
   "name": "Trip monitor 1: output frequency at trip",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0016h",
   "name": "Trip monitor 1: output current at trip",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "0017h",
   "name": "Trip monitor 1: DC bus voltage at trip",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "004Eh",
   "name": "Warning monitor [d090]",
   "description": "Current warning code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2303,
   "documented": "0900h",
   "name": "Write EEPROM",
   "description": "0 = recalculate motor constants, 1 = store set values in EEPROM.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4096,
   "documented": "1001h (High) / 1002h (Low)",
   "name": "Output frequency monitor [d001]",
   "description": "0.00-590.00 Hz.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4098,
   "documented": "1003h",
   "name": "Output current monitor [d002]",
   "description": "0.00-655.35 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4099,
   "documented": "1004h",
   "name": "Rotation direction monitor [d003]",
   "description": "Codes 0-2; guide shows only keypad symbols F / o / r, not the mapping.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4100,
   "documented": "1005h (High) / 1006h (Low)",
   "name": "PID feedback value monitor [d004]",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4102,
   "documented": "1007h",
   "name": "Input terminal monitor [d005]",
   "description": "Bit per input terminal 1-8.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4103,
   "documented": "1008h",
   "name": "Output terminal monitor [d006]",
   "description": "Bits for outputs 11, 12 and relay.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4106,
   "documented": "100Bh (High) / 100Ch (Low)",
   "name": "Detect speed monitor [d008]",
   "description": "-590.00 to +590.00 Hz.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4108,
   "documented": "100Dh",
   "name": "Torque reference monitor [d009]",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4111,
   "documented": "1010h",
   "name": "Output torque monitor [d012]",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4112,
   "documented": "1011h",
   "name": "Output voltage monitor [d013]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4113,
   "documented": "1012h",
   "name": "Input power monitor [d014]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4114,
   "documented": "1013h (High) / 1014h (Low)",
   "name": "Accumulated input power monitor [d015]",
   "description": "Unit is 1 kWh times the [b079] gain.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4116,
   "documented": "1015h (High) / 1016h (Low)",
   "name": "Accumulated RUN time monitor [d016]",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4118,
   "documented": "1017h (High) / 1018h (Low)",
   "name": "Accumulated power-on time monitor [d017]",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4120,
   "documented": "1019h",
   "name": "Cooling fin temperature monitor [d018]",
   "description": "-20.0 to 150.0.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4133,
   "documented": "1026h",
   "name": "DC bus voltage monitor [d102]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4134,
   "documented": "1027h",
   "name": "BRD load ratio monitor [d103]",
   "description": "Braking resistor duty.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4135,
   "documented": "1028h",
   "name": "Electronic thermal load ratio monitor (motor) [d104]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4184,
   "documented": "1059h",
   "name": "Frequency input source monitor [d062]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Keypad (multi-speed 0)",
    "1": "Multi-speed 1",
    "2": "Multi-speed 2",
    "3": "Multi-speed 3",
    "4": "Multi-speed 4",
    "5": "Multi-speed 5",
    "6": "Multi-speed 6",
    "7": "Multi-speed 7",
    "8": "Multi-speed 8",
    "9": "Multi-speed 9",
    "10": "Multi-speed 10",
    "11": "Multi-speed 11",
    "12": "Multi-speed 12",
    "13": "Multi-speed 13",
    "14": "Multi-speed 14",
    "15": "Multi-speed 15",
    "16": "Jogging",
    "18": "Modbus communication",
    "19": "Option",
    "21": "External POT",
    "22": "Pulse input",
    "23": "Calculation function result",
    "24": "EzSQ",
    "25": "[Ai1] input",
    "26": "[Ai2] input",
    "27": "[Ai1] + [Ai2] input"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4185,
   "documented": "105Ah",
   "name": "RUN command input source monitor [d063]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Control terminal",
    "2": "Keypad (RUN key)",
    "3": "Modbus communication",
    "4": "Option"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4237,
   "documented": "108Eh",
   "name": "Analog input [Ai1] monitor [d130]",
   "description": "Raw 0-1023.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4238,
   "documented": "108Fh",
   "name": "Analog input [Ai2] monitor [d131]",
   "description": "Raw 0-1023.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4354,
   "documented": "1103h (High) / 1104h (Low)",
   "name": "Acceleration time 1, 1st motor [F002]",
   "description": "0.00-3600.00 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4356,
   "documented": "1105h (High) / 1106h (Low)",
   "name": "Deceleration time 1, 1st motor [F003]",
   "description": "0.00-3600.00 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4358,
   "documented": "1107h",
   "name": "RUN-key rotation direction [F004]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Forward",
    "1": "Reverse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4608,
   "documented": "1201h",
   "name": "Frequency input source, 1st motor [A001]",
   "description": "Set 03 to take the frequency from Modbus.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "External operator POT",
    "1": "Control terminal",
    "2": "Parameter setting",
    "3": "Modbus communication",
    "4": "Option",
    "6": "Pulse input",
    "7": "Program function (EzSQ)",
    "10": "Calculation function result"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4609,
   "documented": "1202h",
   "name": "RUN command source, 1st motor [A002]",
   "description": "Set 03 to run/stop from Modbus.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Control terminal",
    "2": "Keypad (RUN key)",
    "3": "Modbus communication",
    "4": "Option"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5194,
   "documented": "144Bh",
   "name": "RS485 baud rate [C071]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "3": "2400 bps",
    "4": "4800 bps",
    "5": "9600 bps",
    "6": "19.2 kbps",
    "7": "38.4 kbps",
    "8": "57.6 kbps",
    "9": "76.8 kbps",
    "10": "115.2 kbps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5195,
   "documented": "144Ch",
   "name": "RS485 node address [C072]",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5197,
   "documented": "144Eh",
   "name": "RS485 parity [C074]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity",
    "1": "Even parity",
    "2": "Odd parity"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5198,
   "documented": "144Fh",
   "name": "RS485 stop bits [C075]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1 bit",
    "2": "2 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5199,
   "documented": "1450h",
   "name": "RS485 communication error action [C076]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Trip",
    "1": "Trip after deceleration stop",
    "2": "Ignore",
    "3": "Free run stop",
    "4": "Deceleration stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5200,
   "documented": "1451h",
   "name": "RS485 communication timeout [C077]",
   "description": "0.00 = disabled, 0.01-99.99 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5201,
   "documented": "1452h",
   "name": "RS485 communication wait time [C078]",
   "description": "Extra reply delay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set C096 to Modbus-RTU and the C07x serial settings, then set A001 = 03 and A002 = 03 so the frequency and run command come from Modbus. Write the frequency to 0001h/0002h, start and stop with coil 0001h, and poll 0003h-0005h plus the d-group monitors from 1001h.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Frequency command F001"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "Run/stop"
   },
   {
    "table": "coil",
    "address": 3,
    "why": "Fault reset"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Inverter state A"
   },
   {
    "table": "holding_register",
    "address": 4096,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 4098,
    "why": "Output current"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Latest trip code"
   },
   {
    "table": "holding_register",
    "address": 4133,
    "why": "DC bus voltage"
   }
  ],
  "enable": "Set RS485 communication mode [C096] to Modbus-RTU, then A001 = 03 (frequency from Modbus) and A002 = 03 (run command from Modbus). Coils 0001h/0002h only act when A002 = 03.",
  "watchdog": "C077 sets a communication timeout (0.00 = off, up to 99.99 s); C076 selects the action on a comm error: trip, trip after deceleration, ignore (default), free run or deceleration stop.",
  "quirks": [
   "Wire address is the printed hex number minus 1.",
   "F001 is a two-register value (0001h high, 0002h low). Reading or writing only the low word 0002h is allowed; accessing only the high word is rejected with exception 27h.",
   "Byte order of the data field follows [P400]; keep it at 00 Big endian unless the master needs otherwise.",
   "Parameter writes over Modbus are not stored in EEPROM unless 0900h is written with 1 (or the EEPROM write mode is set)."
  ],
  "setup": [
   "C071 baud (default 05 = 9600), C072 node address 1-247 (default 1), C074 parity (default none), C075 stop bits (default 1).",
   "Turn on the built-in 120 ohm termination switch on the inverter at the end of the line.",
   "Connect SP/SN for the RS485 pair and L as signal ground."
  ],
  "gotchas": [
   "The intelligent input coils are OR-ed with the physical terminals; the [d005] monitor shows only the physical terminals, not the Modbus-driven state.",
   "Communication error coils (004Ah-004Eh) latch until an error reset."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/hitachi/wj-c1",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}