 "manufacturer": "Honeywell",
 "manufacturer_slug": "honeywell",
 "model": "Midas S2 extractive gas transmitter (Modbus/TCP)",
 "model_slug": "midas-s2",
 "short_model": "Midas S2",
 "aliases": [
  "Midas S2",
  "MIDAS-S2",
  "Midas S2 gas detector"
 ],
 "equipment_type": "Sensor (extractive gas detector)",
 "applies_to": "Honeywell Midas S2 single-point extractive gas transmitters with Ethernet/PoE, user manual 3023M5001 Rev A, Modbus/TCP register map (Table 6-1).",
 "summary": "The Midas S2 is a Honeywell pumped single-point gas transmitter for toxic, flammable and oxygen gases. Its Ethernet port is a Modbus/TCP server: holding registers 40001-40122 give a packed status word, the gas reading, decimal point and units, temperature, cell life, flow, alarm and fault flags. This map covers the 16-bit registers; float, time and text registers are left out.",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The table lists reference addresses 40001-40122 (Modicon style), so 40001 (status) is wire address 0 and 40005 (gas reading) is wire address 4."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Midas S2 Fixed single-point extractive gas transmitter User Manual",
  "doc_number": "3023M5001 Rev A",
  "revision_date": "2023-08-31",
  "url": "https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/hgas/en-us/products/high-tech-and-semiconductor/midass2/documents/hon-ia-dmc-3023m5001-midas-a-001-rev-a-midas-s2-um-en.pdf",
  "pages": "pp. 55-57 (section 6.8, Table 6-1)"
 },
 "notes": [
  "Left out: float registers (concentration 40003-40004, alarm thresholds 40013-40016, high scale 40019-40020). The manual only says floats are \"little-endian or Intel format\", which does not pin down the word order on the wire.",
  "Left out: 32-bit UNIX time registers 40061-40062, 40065-40068 (word order not stated) and the ASCII serial-number and gas-name registers (character order within a register not stated).",
  "Left out: user command registers 40021-40022 (CMD1 0x015E-0x0B5E with CMD2 0x3626 for reset, inhibit and relay control): the manual says only function 03 is supported, so how they are written is unclear.",
  "Status register 40001 packs numbers: bits 0-3 monitoring state (0 warm-up, 1 monitor, 2 alarms inhibited, 3 alarms and faults inhibited, 4 fully inhibited, 5 alarm/fault simulation, 6 bump test, 7 4-20 mA calibration, 8 other calibration); bits 4-5 fault state (0 none, 1 maintenance fault, 2 instrument fault).",
  "The manual mentions an older 40082 duplicate in the sensor serial list (typo for 40092); text registers are excluded anyway.",
  "Only function 03 (read holding registers) is supported.",
  "The manual does not state the TCP port; Modbus/TCP normally uses 502."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Status (STTS)",
   "description": "Bits 0-3 monitoring state, bits 4-5 fault state; flags below.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "6": "Alarm 1 active",
    "7": "Alarm 2 active",
    "8": "Relay 1 energized",
    "9": "Relay 2 energized",
    "10": "Relay 3 energized",
    "11": "Heartbeat (toggles every second)",
    "12": "Relays under remote Modbus/TCP control",
    "13": "Last zero calibration succeeded",
    "14": "Last span calibration succeeded"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Gas selection (GASS)",
   "description": "Low byte gas ID, high byte cartridge type.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Gas concentration integer (CONC)",
   "description": "Divide by 10^decimal (40007 bits 0-2); ppm for ppm/ppb gases.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Most important active fault number (NOFT)",
   "description": "Fault code; see the troubleshooting table in the manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "Decimal point and units (DPUN)",
   "description": "Bits 0-2 decimals; high byte units: 1 ppm, 2 ppb, 4 %vol, 8 %LEL, 16 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40008",
   "name": "Temperature (TEMP)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "Cell life remaining (CLRH)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Heartbeat counter (HRTB)",
   "description": "Low 16 bits of time in seconds.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "40011",
   "name": "Sample flow (FLOW)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "cc/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40017",
   "name": "Alarm status (ASI)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 active",
    "1": "Alarm 2 active"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "40018",
   "name": "Fault status (FSI)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Maintenance fault",
    "1": "Instrument fault",
    "2": "Flow fault",
    "3": "Internal communication fault",
    "4": "Pyrolyzer fault",
    "5": "Sensor fault",
    "6": "Range over fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "40063",
   "name": "Transmitter serial number prefix",
   "description": "First four digits of the S-number as a decimal value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "40064",
   "name": "Transmitter serial number suffix",
   "description": "Last digits of the S-number as a decimal value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "40081",
   "name": "Mode status (MSI)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Warm-up",
    "1": "Monitor mode",
    "2": "Test mode",
    "3": "Maintenance mode"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect to the Midas S2 IP and read holding registers 0-17 with function 03; gas = 40005 / 10^(40007 bits 0-2).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 4,
    "why": "Gas concentration"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Decimal point and units"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Status and alarms"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Fault flags"
   },
   {
    "table": "holding_register",
    "address": 10,
    "why": "Sample flow"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Cell life"
   }
  ],
  "enable": "Modbus/TCP is part of the Ethernet interface; set the network address in the transmitter setup.",
  "watchdog": null,
  "quirks": [
   "Gas reading is in ppm for ppm and ppb gases, otherwise in display units.",
   "In bump test mode the Modbus outputs are not inhibited."
  ],
  "setup": [
   "Ethernet or PoE.",
   "Modbus TCP has no authentication; isolate it on a secure network.",
   "Factory default IP address is 192.168.0.14; without DHCP, put the PC on the same subnet."
  ],
  "gotchas": [
   "Read 40007 together with 40005 to apply the right decimal point."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/honeywell/midas-s2",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}