 "manufacturer": "Honeywell",
 "manufacturer_slug": "honeywell",
 "model": "SOLA hydronic boiler control (Modbus interface)",
 "model_slug": "sola-hydronic-control",
 "short_model": "SOLA",
 "aliases": [
  "R7910",
  "R7911",
  "Honeywell SOLA",
  "SOLA ICP"
 ],
 "equipment_type": "Boiler controller",
 "applies_to": "Honeywell SOLA (R7910/R7911) integrated boiler controls, status registers 0-173 of the SOLA Modbus Interface specification Rev 4.1.1 (2013-10-14). Used inside many OEM condensing boilers.",
 "summary": "SOLA is Honeywell's integrated burner and hydronic control used by many boiler OEMs. Its RS-485 Modbus RTU port exposes everything as 16-bit holding registers, with digital signals packed into bit-map registers. This map covers the status area: change flags, digital I/O, limits, demand source, temperatures, firing rate, flame signal, burner control status and lockout codes, sensor states, CH/DHW/lead-lag status and pump status.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The specification says register addresses start at 0 per the Modbus specification; add 40001 to the decimal address for traditional 4xxxx numbering. Register 7 (outlet temperature) is requested as address 7 (40008)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Software Interface Specification - SOLA Modbus Interface",
  "doc_number": "Rev. 4.1.1",
  "revision_date": "2013-10-14",
  "url": "https://www.ccontrols.com/support/dp/OEMModbusSIS4_1_1_1_1.pdf",
  "unofficial": true,
  "pages": "physical layer pp. 13-14; function codes and register rules pp. 14-15; addressing p. 18; status registers pp. 18-31"
 },
 "notes": [
  "Source host: Honeywell's specification as hosted by Contemporary Controls (a Honeywell integration partner); Honeywell does not host it publicly that we could find.",
  "All temperatures are in 0.1 °C regardless of the display unit setting. The specification lists these registers as U16 even though the range is -40 to 130 °C; check how sub-zero values arrive on site. A temperature that does not apply (function not enabled) reads 0x8FFF; sensor faults replace the reading with the codes in table 4 of the source (0x7FFF, 0x8000-0x8500).",
  "Firing-rate type registers carry either RPM or a 0.1 % value; the most significant bit tells which (0 = RPM, 1 = %), as set by the modulation output parameter (register 192).",
  "Left out: the 32-bit statistics counters (128-147); the specification says 32-bit items use two consecutive registers but does not state the word order. Also left out: configuration registers above 173, alert/lockout history, lead-lag slave tables and the variable-length data items.",
  "Pump status coding depends on application build (before/after 1600); see tables 13-14 in the source.",
  "Up to 125 registers per read and 20 per write; variable-length items must be read on their own."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0000",
   "name": "Status Change",
   "description": "Cleared after read; flags which register groups changed.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "10": "Alert log",
    "9": "Lockout history",
    "8": "Lead Lag status",
    "7": "Statistics",
    "6": "Pump status",
    "5": "DHW status",
    "4": "CH status",
    "3": "Demand&Modulation status",
    "2": "Sensor status",
    "1": "Burner control status",
    "0": "Active Lockout"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001",
   "name": "Configuration Change",
   "description": "Cleared after read; flags which register groups changed.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "PCB configuration",
    "14": "PM configuration",
    "12": "Lead Lag configuration",
    "11": "Frost protection configuration",
    "10": "Outdoor reset configuration",
    "9": "Anti-condensation configuration",
    "8": "Limits configuration",
    "7": "DHW configuration",
    "6": "Annunciation configuration",
    "5": "Pump configuration",
    "4": "Fan configuration",
    "3": "Burner control configuration",
    "2": "CH configuration",
    "1": "Modulation configuration",
    "0": "System configuration"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002",
   "name": "Digital I/O",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Safety relay",
    "14": "Time of Day",
    "13": "STAT (Demand)",
    "12": "High Fire Switch (HFS)",
    "11": "Low Fire Switch (LFS)",
    "10": "Load Control Input(LCI)",
    "9": "Pre-ignition interlock (PII)",
    "8": "Interlock (ILK)",
    "7": "Alarm",
    "6": "Main valve",
    "5": "Pilot valve",
    "4": "External ignition",
    "3": "Blower motor/HSI",
    "2": "Pump C",
    "1": "Pump B",
    "0": "Pump A"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003",
   "name": "Annunciation I/O",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "7": "Annunciator 8/LFS",
    "6": "Annunciator 7/HFS",
    "5": "Annunciator 6",
    "4": "Annunciator 5",
    "3": "Annunciator 4",
    "2": "Annunciator 3",
    "1": "Annunciator 2",
    "0": "Annunciator 1/IAS"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004",
   "name": "Limits",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "11": "Heat exchanger high limit",
    "10": "Exchanger T-rise limit",
    "9": "Outlet T-rise limit",
    "8": "Inversion inlet/exchanger limit",
    "7": "Inversion exchanger/outlet limit",
    "6": "Inversion inlet/outlet limit",
    "5": "Delta T inlet/exchanger limit",
    "4": "Delta T exchanger/outlet limit",
    "3": "Delta T inlet/outlet limit",
    "2": "Stack limit",
    "1": "DHW high limit",
    "0": "Outlet high limit"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005",
   "name": "Program Module (PM) status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "10": "OEM alert PCB stored in PM",
    "9": "OEM range PCB stored in PM",
    "8": "OEM parameter PCB stored in PM",
    "2": "Valid copyright",
    "1": "Lead/Lag enabled",
    "0": "PM installed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006",
   "name": "Demand source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Unknown",
    "1": "No source demand",
    "2": "CH",
    "3": "DHW",
    "4": "Lead Lag slave",
    "5": "Lead Lag master",
    "6": "CH frost protection",
    "7": "DHW frost protection",
    "8": "No demand due to burner switch (register 199) turned off",
    "9": "DHW storage",
    "11": "Warm weather shutdown",
    "12": "Hot standby"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0007",
   "name": "Outlet (S3S4) or Outlet limit (S3) sensor",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008",
   "name": "Firing rate",
   "description": "Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009",
   "name": "Fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "RPM",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "0010",
   "name": "Flame signal",
   "description": "0.01 V or 0.01 uA, depending on flame sensor (0.00-50.00).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "0011",
   "name": "Inlet (S1) sensor",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "0012",
   "name": "DHW (S6S7) or DHW limit (S6) sensor",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "0013",
   "name": "S5 sensor",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "0014",
   "name": "Stack (S8S9) or Stack limit (S8) sensor",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "0015",
   "name": "4-20 mA remote control input (S2) terminal",
   "description": "0.1 mA units when S2 is a 4-20 mA input; other uses per register 609.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0016",
   "name": "Active CH setpoint",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0017",
   "name": "Active DHW setpoint",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0018",
   "name": "Active LL setpoint",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0019",
   "name": "Register Access Status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No register writes allowed",
    "1": "Installer register writes allowed",
    "2": "OEM register writes allowed",
    "3": "All register writes allowed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "0020",
   "name": "Steam pressure",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "psi",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0021",
   "name": "Analog modulation input",
   "description": "0 = no signal, else 4-20 mA (0.1 mA); mirrors register 15 for 4-20 mA S2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "0022",
   "name": "Active CH pressure setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "psi",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "0023",
   "name": "Extended Status Change",
   "description": "Cleared after read; flags which register groups changed.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "4": "DHW plate heat exchanger configuration",
    "3": "DHW plate heat exchanger status"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "0025",
   "name": "Active CH operating point",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "0026",
   "name": "Active DHW operating point",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "0027",
   "name": "Active Lead Lag operating point",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "0028",
   "name": "Active system operating point",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "0029",
   "name": "Active system setpoint",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "0030",
   "name": "Active system on hysteresis",
   "description": "0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "0031",
   "name": "Active system off hysteresis",
   "description": "0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "0032",
   "name": "Burner control status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Disabled",
    "1": "Locked out",
    "4": "Anti-short cycle",
    "5": "Unconfigured safety data",
    "34": "Standby Hold",
    "35": "Standby Delay",
    "48": "Normal Standby",
    "49": "Preparing",
    "50": "Ignition",
    "51": "Firing",
    "52": "Postpurge"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "0033",
   "name": "Burner control state",
   "description": "Sequence state code, see table 12 in the source.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "0034",
   "name": "Lockout code",
   "description": "1-4096 = lockout number (table 9 in the source).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No lockout"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "0035",
   "name": "Alarm reason",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Lockout (see Lockout code, register 34)",
    "2": "Alert (see Table 11)",
    "3": "Other"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "0036",
   "name": "Annunciator first out",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None or undetermined",
    "1": "ILK",
    "2": "PII",
    "11": "Annunciator 1",
    "12": "Annunciator 2",
    "13": "Annunciator 3",
    "14": "Annunciator 4",
    "15": "Annunciator 5",
    "16": "Annunciator 6",
    "17": "Annunciator 7",
    "18": "Annunciator 8"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "0037",
   "name": "Annunciator hold",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None or undetermined",
    "1": "ILK",
    "2": "PII",
    "3": "LCI",
    "11": "Annunciator 1",
    "12": "Annunciator 2",
    "13": "Annunciator 3",
    "14": "Annunciator 4",
    "15": "Annunciator 5",
    "16": "Annunciator 6",
    "17": "Annunciator 7",
    "18": "Annunciator 8"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "0038",
   "name": "Sequence time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "0039",
   "name": "Delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "0040",
   "name": "Hold code",
   "description": "Hold reason; same codes as lockout (table 8 in the source).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "0041",
   "name": "Burner control flags",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "Blocked condensate detected",
    "1": "DHW remote STAT demand indicated",
    "0": "Flame detected"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "0042",
   "name": "CH remote Stat",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No remote STAT demand",
    "1": "Remote STAT demand indicated"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "0043",
   "name": "Outlet operation (S4=J8-10) terminal",
   "description": "0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 610.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "0044",
   "name": "DHW operation (S7=J9-3) terminal",
   "description": "0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 612.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "0045",
   "name": "Stack or Heat exchanger operation (S9=J9-6) terminal",
   "description": "0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 613.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "0046",
   "name": "Outlet operation sensor (S4=J8-10) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "0047",
   "name": "DHW operation sensor (S7=J9-3) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "0048",
   "name": "Outlet limit sensor (S3=J8-8) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "0049",
   "name": "Inlet sensor (S1=J8-4) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "0050",
   "name": "DHW limit sensor (S7=J9-1) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "0051",
   "name": "Stack limit sensor (S8=J9-4) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "0052",
   "name": "S5 (J8-11) sensor state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "0053",
   "name": "4-20mA remote control input (S2=J8-6) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "0054",
   "name": "Pressure sensor (S1=J8-4) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "0055",
   "name": "Stack operation or Heat exchanger sensor (S9=J9-6) state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "0056",
   "name": "Active rate limiter",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Outlet high limit",
    "2": "Delta T limit",
    "3": "Stack limit",
    "4": "Slow start limit",
    "5": "Anti-condensation",
    "6": "Minimum modulation",
    "7": "Forced rate",
    "8": "IAS is open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "0057",
   "name": "Limited rate",
   "description": "Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "0058",
   "name": "Active rate override",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Burner control default",
    "2": "Burner control",
    "3": "Manual firing rate",
    "4": "Manual firing rate off",
    "5": "Fan on during off cycle",
    "6": "Assured low fire cutoff"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "0059",
   "name": "Override rate",
   "description": "Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "0060",
   "name": "Demand rate",
   "description": "Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "0061",
   "name": "Active system sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No active sensor",
    "1": "DHW (S6S7) sensor",
    "2": "Outlet (S3S4) sensor",
    "3": "Inlet (S1) sensor",
    "4": "4-20mA input (S2)",
    "5": "S5 sensor",
    "6": "S10 sensor",
    "7": "Steam (S1) sensor",
    "8": "DHW (S6S7) and Inlet (S1) sensor",
    "9": "DHW (S6S7) and S5 sensor",
    "10": "Outlet (S3S4) and Inlet (S1) sensor",
    "11": "Outlet (S3S4) and S5 sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "0062",
   "name": "Active Lead Lag sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No active sensor",
    "2": "Outlet (S3S4) sensor",
    "5": "S5 sensor",
    "6": "S10 sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "0064",
   "name": "CH status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Unknown",
    "1": "Disabled",
    "2": "Normal",
    "3": "Suspended"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "0065",
   "name": "CH setpoint source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Unknown",
    "1": "Normal setpoint",
    "2": "TOD setpoint",
    "3": "Outdoor reset",
    "4": "Remote control",
    "7": "Outdoor reset time of day",
    "9": "Outdoor boost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "0066",
   "name": "CH heat demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "0067",
   "name": "CH burner demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "0068",
   "name": "CH requested rate",
   "description": "Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "0069",
   "name": "CH frost heat demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "0070",
   "name": "CH frost burner demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "0071",
   "name": "Active CH on hysteresis",
   "description": "0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "0072",
   "name": "Active CH off hysteresis",
   "description": "0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "0073",
   "name": "Active CH pressure on hysteresis",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "psi",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "0074",
   "name": "Active CH pressure off hysteresis",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "psi",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "0075",
   "name": "Active CH pressure operating point",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "psi",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "0076",
   "name": "Active CH sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No active sensor",
    "2": "Outlet (S3S4) sensor",
    "3": "Inlet (S1) sensor",
    "4": "4-20mA input (S2)",
    "5": "S5 sensor",
    "6": "S10 sensor",
    "7": "Steam (S1) sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "0077",
   "name": "Heat Demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "0078",
   "name": "BURNER DEMAND",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 79,
   "documented": "0079",
   "name": "Active DHW sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No active sensor",
    "1": "DHW (S6S7) sensor",
    "2": "Outlet (S3S4) sensor",
    "3": "Inlet (S1) sensor"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "0080",
   "name": "DHW status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Unknown",
    "1": "Disabled",
    "2": "Normal",
    "3": "Suspended"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "0081",
   "name": "DHW setpoint source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Unknown",
    "1": "Normal setpoint",
    "2": "TOD setpoint",
    "5": "DHW tap setpoint",
    "6": "DHW preheat setpoint"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "0082",
   "name": "DHW priority count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "0083",
   "name": "DHW heat demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "0084",
   "name": "DHW burner demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 85,
   "documented": "0085",
   "name": "DHW requested rate",
   "description": "Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "0086",
   "name": "DHW frost heat demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 87,
   "documented": "0087",
   "name": "DHW frost burner demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "0088",
   "name": "Active DHW on hysteresis",
   "description": "0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "0089",
   "name": "Active DHW off hysteresis",
   "description": "0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 90,
   "documented": "0090",
   "name": "DHW storage time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "0091",
   "name": "DHW storage heat demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 92,
   "documented": "0092",
   "name": "DHW storage burner demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 93,
   "documented": "0093",
   "name": "Pump A status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "13": "Auxiliary 2 pump demand",
    "12": "Auxiliary 1 pump demand",
    "11": "System pump demand",
    "10": "Boiler pump demand",
    "9": "DHW pump demand",
    "8": "CH pump demand",
    "6": "Pump assigned to logical pump",
    "5": "Pump exercise requested",
    "4": "On due to exercise",
    "3": "On due to overrun",
    "2": "Forced off",
    "1": "Forced on",
    "0": "On due to normal demand"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 94,
   "documented": "0094",
   "name": "Pump B status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "13": "Auxiliary 2 pump demand",
    "12": "Auxiliary 1 pump demand",
    "11": "System pump demand",
    "10": "Boiler pump demand",
    "9": "DHW pump demand",
    "8": "CH pump demand",
    "6": "Pump assigned to logical pump",
    "5": "Pump exercise requested",
    "4": "On due to exercise",
    "3": "On due to overrun",
    "2": "Forced off",
    "1": "Forced on",
    "0": "On due to normal demand"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 95,
   "documented": "0095",
   "name": "CH pump start delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "0096",
   "name": "CH pump status",
   "description": "Coding depends on application build (tables 13/14 in the source).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 97,
   "documented": "0097",
   "name": "CH pump overrun time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "0098",
   "name": "CH FP overrun time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 99,
   "documented": "0099",
   "name": "CH pump idle days count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "0100",
   "name": "DHW pump status",
   "description": "Coding depends on application build (tables 13/14 in the source).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "0101",
   "name": "DHW pump start delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "0102",
   "name": "DHW pump overrun time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "0103",
   "name": "DHW FP overrun time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "0104",
   "name": "DHW pump idle days count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "0105",
   "name": "System pump status",
   "description": "Coding depends on application build (tables 13/14 in the source).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "0106",
   "name": "System pump overrun time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "0107",
   "name": "System pump idle days count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "0108",
   "name": "Boiler pump status",
   "description": "Coding depends on application build (tables 13/14 in the source).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "0109",
   "name": "Boiler pump overrun time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "0110",
   "name": "Boiler pump idle days count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "0111",
   "name": "Auxiliary 1 pump status",
   "description": "Coding depends on application build (tables 13/14 in the source).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "0112",
   "name": "Auxiliary 1 pump idle days count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "0113",
   "name": "Auxiliary 2 pump status",
   "description": "See table 14 in the source.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "0114",
   "name": "Auxiliary 2 pump overrun time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "0115",
   "name": "Auxiliary 2 pump idle days count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "0119",
   "name": "Auxiliary 1 pump overrun time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 148,
   "documented": "0148",
   "name": "Auxiliary 2 pump start delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 149,
   "documented": "0149",
   "name": "Boiler pump start delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 150,
   "documented": "0150",
   "name": "System pump start delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 151,
   "documented": "0151",
   "name": "Auxiliary 1 pump start delay time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 152,
   "documented": "0152",
   "name": "DHW tap heat demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 153,
   "documented": "0153",
   "name": "DHW preheat demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 154,
   "documented": "0154",
   "name": "DHW change rate",
   "description": "Rate of change, 0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 155,
   "documented": "0155",
   "name": "DHW tap on recognition time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 156,
   "documented": "0156",
   "name": "DHW tap on time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 157,
   "documented": "0157",
   "name": "DHW preheat delay after tap time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "0158",
   "name": "DHW preheat on recognition time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 159,
   "documented": "0159",
   "name": "DHW preheat on time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "0160",
   "name": "Lead Lag master status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Unknown",
    "1": "Disabled",
    "2": "Normal",
    "3": "Suspended"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "0161",
   "name": "Lead Lag slave status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "15": "Slave command received",
    "14": "Slave mode has priority over CH & DHW",
    "13": "Slave is modulating",
    "12": "CH frost protection request",
    "11": "DHW frost protection request",
    "10": "Frost protection burner request",
    "9": "Local frost protection request"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "0162",
   "name": "Lead Lag master setpoint source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Unknown",
    "1": "CH setpoint",
    "2": "CH TOD setpoint",
    "3": "Outdoor reset",
    "4": "Remote control (4-20mA or Modbus)",
    "7": "Outdoor reset time of day",
    "9": "Outdoor boost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 163,
   "documented": "0163",
   "name": "Lead Lag master heat demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 164,
   "documented": "0164",
   "name": "Lead Lag slave burner demand",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 165,
   "documented": "0165",
   "name": "Lead Lag slave requested rate",
   "description": "Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 166,
   "documented": "0166",
   "name": "Active Lead Lag on hysteresis",
   "description": "0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 167,
   "documented": "0167",
   "name": "Active Lead Lag off hysteresis",
   "description": "0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 168,
   "documented": "0168",
   "name": "Pump C status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "13": "Auxiliary 2 pump demand",
    "12": "Auxiliary 1 pump demand",
    "11": "System pump demand",
    "10": "Boiler pump demand",
    "9": "DHW pump demand",
    "8": "CH pump demand",
    "6": "Pump assigned to logical pump",
    "5": "Pump exercise requested",
    "4": "On due to exercise",
    "3": "On due to overrun",
    "2": "Forced off",
    "1": "Forced on",
    "0": "On due to normal demand"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 170,
   "documented": "0170",
   "name": "Outdoor temperature",
   "description": "0.1 °C units; register listed as U16 although the range starts at -40 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 171,
   "documented": "0171",
   "name": "Outdoor sensor state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Normal",
    "2": "Open",
    "3": "Shorted",
    "4": "Outside high range",
    "5": "Outside low range",
    "6": "Not reliable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 172,
   "documented": "0172",
   "name": "Outlet T-rise rate",
   "description": "Rate of change, 0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 173,
   "documented": "0173",
   "name": "Exchanger T-rise rate",
   "description": "Rate of change, 0.1 °C units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect to the SOLA's 3-pin RS-485 Modbus port (38400 8N1) and read holding registers with FC 03 from address 0. Temperatures are 0.1 °C integers; burner status is at 32, lockout code at 34.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 7,
    "why": "Outlet temperature"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Firing rate"
   },
   {
    "table": "holding_register",
    "address": 10,
    "why": "Flame signal"
   },
   {
    "table": "holding_register",
    "address": 32,
    "why": "Burner control status"
   },
   {
    "table": "holding_register",
    "address": 34,
    "why": "Lockout code"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Demand source"
   },
   {
    "table": "holding_register",
    "address": 16,
    "why": "Active CH setpoint"
   }
  ],
  "enable": "Use one of the SOLA's RS-485 Modbus ports (MB1 or MB2); the control answers to a single Modbus address. Register writes are limited by the access level shown in register 19 (none, installer, OEM or all).",
  "watchdog": null,
  "quirks": [
   "Addresses are 0-based; add 40001 for 4xxxx tools.",
   "Status-change registers 0, 1 and 23 clear when read.",
   "Digital signals are bits inside holding registers, not coils."
  ],
  "setup": [
   "RS-485 terminals: 1 = Data+ (a), 2 = Data- (b), 3 = common.",
   "Fixed format: 38400 bps, 8 data bits, no parity, 1 stop bit."
  ],
  "gotchas": [
   "OEM boilers may disable or relabel some SOLA functions; confirm with the boiler maker's documentation.",
   "0x8FFF in a temperature register means that function is not enabled; 0x7FFF and 0x8000-0x8500 are sensor fault codes."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/honeywell/sola-hydronic-control",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}