 "manufacturer": "ICP DAS",
 "manufacturer_slug": "icp-das",
 "model": "M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)",
 "model_slug": "m-7080",
 "short_model": "M-7080",
 "aliases": [
  "M-7080",
  "M-7080B",
  "M7080",
  "M7080B"
 ],
 "equipment_type": "Sensor (counter/frequency input module)",
 "applies_to": "ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.",
 "summary": "The M-7080 and M-7080B are RS-485 remote I/O modules that count pulses or measure frequency on two inputs and drive two digital outputs. In Modbus RTU mode the 32-bit counts sit in holding registers as low/high word pairs, and configuration flags are coils. This map covers the count/frequency values, maximum and preset values, input thresholds, outputs and counter control.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The table is titled 'M-7000 Address Mapping (Base 1)': 00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers. Subtract the table base for the wire address (40001 = holding register 0)."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "M-7000 Series Address Mapping Table",
  "doc_number": "V1.18",
  "revision_date": "2025-09",
  "url": "https://www.icpdas.com/en/download/file.php?num=19906",
  "pages": "M-7080 pp. 72-73; M-7080B pp. 74-75"
 },
 "notes": [
  "Each 32-bit value is listed as a low word followed by a high word, so read two registers and treat them as low word first (CDAB).",
  "Whether channel values are counts or frequency depends on the module type code, which this table does not map; frequency units are not stated.",
  "The M-7080B table has no set-to-preset coils (00133/00134); on the M-7080B, writing the preset registers with type code 52 also loads them into the counters.",
  "The M-7080 counter-mode coils 00145/00146 need firmware 0A24 or later and are left out, as are the module name, address and baud registers not printed for these models."
 ],
 "integration": {
  "summary": "Read holding registers 0-3 for both 32-bit counts (low word first). Start or stop each counter with coils 00135/00136 and drive the outputs with coils 00001/00002.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Channel 0 count/frequency"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Channel 1 count/frequency"
   },
   {
    "table": "coil",
    "address": 64,
    "why": "Counter 0 overflow"
   },
   {
    "table": "coil",
    "address": 134,
    "why": "Start/stop counter 0"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "DO 0"
   }
  ],
  "enable": "The module must be in Modbus RTU mode (ICP DAS modules also speak DCON); see the module's user manual for switching protocol.",
  "watchdog": null,
  "quirks": [
   "32-bit values are low word first (CDAB).",
   "Counters are started by default (coils 00135/00136 default 1)."
  ],
  "setup": [
   "Voltage trigger levels are in 0.1 V steps (factory 0.8 V low, 2.4 V high)."
  ],
  "gotchas": [
   "On the M-7080B, writing the preset registers 40097-40100 with type code 52 also loads them into the counters."
  ]
 },
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "00001",
   "name": "DO 0",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "00002",
   "name": "DO 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 64,
   "documented": "00065",
   "name": "Overflow flag of counter 0",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 65,
   "documented": "00066",
   "name": "Overflow flag of counter 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 128,
   "documented": "00129",
   "name": "Input mode channel 0",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Non-isolated",
    "1": "Isolated"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 129,
   "documented": "00130",
   "name": "Input mode channel 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Non-isolated",
    "1": "Isolated"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 130,
   "documented": "00131",
   "name": "Gate active level",
   "description": "Used when gate control is enabled.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Low active",
    "1": "High active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 132,
   "documented": "00133",
   "name": "Set counter 0 to preset",
   "description": "M-7080 only. Write 1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 133,
   "documented": "00134",
   "name": "Set counter 1 to preset",
   "description": "M-7080 only. Write 1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 134,
   "documented": "00135",
   "name": "Start/stop counter 0",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 135,
   "documented": "00136",
   "name": "Start/stop counter 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 138,
   "documented": "00139",
   "name": "Digital filter enable",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 141,
   "documented": "00142",
   "name": "Frequency gate time",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0.1 s",
    "1": "1.0 s"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 142,
   "documented": "00143",
   "name": "LED configuration",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Channel 0",
    "1": "Channel 1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Counter/frequency value channel 0",
   "description": "Counter or frequency per the channel type code; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Counter/frequency value channel 1",
   "description": "Counter or frequency per the channel type code; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "40065",
   "name": "Max value of counter 0",
   "description": "Factory 65535 in each word.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "40067",
   "name": "Max value of counter 1",
   "description": "Factory 65535 in each word.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "40097",
   "name": "Preset value of counter 0",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "40099",
   "name": "Preset value of counter 1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "40161",
   "name": "Low level width threshold",
   "description": "2-65535 us.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "us",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "40162",
   "name": "High level width threshold",
   "description": "2-65535 us.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "us",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "40163",
   "name": "Low voltage trigger value",
   "description": "0-5.0 V; factory 0.8 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 163,
   "documented": "40164",
   "name": "High voltage trigger value",
   "description": "0-5.0 V; factory 2.4 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/icp-das/m-7080",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}