 "manufacturer": "ICP DAS",
 "manufacturer_slug": "icp-das",
 "model": "M-7088 8-channel PWM output / counter input module (Modbus RTU)",
 "model_slug": "m-7088",
 "short_model": "M-7088",
 "aliases": [
  "M-7088",
  "M7088"
 ],
 "equipment_type": "Sensor (PWM output and counter input module)",
 "applies_to": "ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.",
 "summary": "The M-7088 is an RS-485 remote I/O module with eight PWM outputs and eight digital inputs that also count pulses. Over Modbus RTU the PWM duty cycle, frequency and burst settings are holding registers, PWM start/stop and modes are coils, and the 32-bit input counts are input registers stored low word first.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The table is titled 'M-7000 Address Mapping (Base 1)': 00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers. Subtract the table base for the wire address (40001 = holding register 0)."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "M-7000 Series Address Mapping Table",
  "doc_number": "V1.18",
  "revision_date": "2025-09",
  "url": "https://www.icpdas.com/en/download/file.php?num=19906",
  "pages": "pp. 78-80"
 },
 "notes": [
  "The table states low word then high word for the DI counts, maximum counts and PWM frequency, so these are CDAB.",
  "Preset values (40097-40112) are left out: the table's example pairs 40097 with 40104, which contradicts the low/high pattern.",
  "Defaults come from the table: address 1 (40485) and baud/parity code 6 = 9600 bps, no parity, 1 stop bit (40486).",
  "PWM trigger, synchronisation, burst count readback, LED and EEPROM-save items are left out."
 ],
 "integration": {
  "summary": "Set a channel's frequency (40737+, 32-bit low word first) and duty cycle (40705+, 0.1 % steps), then start it with its PWM status coil (00001+). Read input registers 0-15 for the eight 32-bit pulse counts.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 704,
    "why": "PWM duty channel 0"
   },
   {
    "table": "holding_register",
    "address": 736,
    "why": "PWM frequency channel 0"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "PWM start/stop channel 0"
   },
   {
    "table": "coil",
    "address": 864,
    "why": "PWM burst/continuous channel 0"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "DI count channel 0"
   },
   {
    "table": "discrete_input",
    "address": 32,
    "why": "DI status channel 0"
   }
  ],
  "enable": "The module must run the Modbus RTU protocol (coil 00257 = 1, factory default 1).",
  "watchdog": "Host watchdog: enable with coil 00261, timeout in 40489 (0.1 s steps, factory 25.5 s); coil 00270 shows and clears a timeout.",
  "quirks": [
   "32-bit values are low word first (CDAB).",
   "Duty cycle is in 0.1 % steps (500 = 50.0 %)."
  ],
  "setup": [
   "Module address in 40485 (1-247); baud and parity code in 40486."
  ],
  "gotchas": [
   "Coil 00260 picks the host watchdog mode: in the new mode an AO or DO command also clears the watchdog timeout status."
  ]
 },
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "00001",
   "name": "PWM status channel 0",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Started"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "00002",
   "name": "PWM status channel 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Started"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "00003",
   "name": "PWM status channel 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Started"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "00004",
   "name": "PWM status channel 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Started"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "00005",
   "name": "PWM status channel 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Started"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "00006",
   "name": "PWM status channel 5",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Started"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "00007",
   "name": "PWM status channel 6",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Started"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "00008",
   "name": "PWM status channel 7",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Started"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 64,
   "documented": "00065",
   "name": "DI counter overflow channel 0",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 65,
   "documented": "00066",
   "name": "DI counter overflow channel 1",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 66,
   "documented": "00067",
   "name": "DI counter overflow channel 2",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 67,
   "documented": "00068",
   "name": "DI counter overflow channel 3",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 68,
   "documented": "00069",
   "name": "DI counter overflow channel 4",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 69,
   "documented": "00070",
   "name": "DI counter overflow channel 5",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 70,
   "documented": "00071",
   "name": "DI counter overflow channel 6",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 71,
   "documented": "00072",
   "name": "DI counter overflow channel 7",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Overflow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 260,
   "documented": "00261",
   "name": "Host watchdog enable",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 265,
   "documented": "00266",
   "name": "Clear all DI counters",
   "description": "Write 1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 269,
   "documented": "00270",
   "name": "Host watchdog timeout status",
   "description": "Write 1 to clear.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal",
    "1": "Host watchdog timeout"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 864,
   "documented": "00865",
   "name": "PWM mode channel 0",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Burst",
    "1": "Continuous"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 865,
   "documented": "00866",
   "name": "PWM mode channel 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Burst",
    "1": "Continuous"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 866,
   "documented": "00867",
   "name": "PWM mode channel 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Burst",
    "1": "Continuous"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 867,
   "documented": "00868",
   "name": "PWM mode channel 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Burst",
    "1": "Continuous"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 868,
   "documented": "00869",
   "name": "PWM mode channel 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Burst",
    "1": "Continuous"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 869,
   "documented": "00870",
   "name": "PWM mode channel 5",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Burst",
    "1": "Continuous"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 870,
   "documented": "00871",
   "name": "PWM mode channel 6",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Burst",
    "1": "Continuous"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 871,
   "documented": "00872",
   "name": "PWM mode channel 7",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Burst",
    "1": "Continuous"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 32,
   "documented": "10033",
   "name": "DI status channel 0",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 33,
   "documented": "10034",
   "name": "DI status channel 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 34,
   "documented": "10035",
   "name": "DI status channel 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 35,
   "documented": "10036",
   "name": "DI status channel 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 36,
   "documented": "10037",
   "name": "DI status channel 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 37,
   "documented": "10038",
   "name": "DI status channel 5",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 38,
   "documented": "10039",
   "name": "DI status channel 6",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 39,
   "documented": "10040",
   "name": "DI status channel 7",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 272,
   "documented": "10273",
   "name": "Reset status",
   "description": "1 on the first read after power-on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not first read",
    "1": "First read after power-on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "DI count channel 0",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "30003",
   "name": "DI count channel 1",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "30005",
   "name": "DI count channel 2",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "30007",
   "name": "DI count channel 3",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "30009",
   "name": "DI count channel 4",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "30011",
   "name": "DI count channel 5",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "30013",
   "name": "DI count channel 6",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "30015",
   "name": "DI count channel 7",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "40065",
   "name": "Max DI count channel 0",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "40067",
   "name": "Max DI count channel 1",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "40069",
   "name": "Max DI count channel 2",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "40071",
   "name": "Max DI count channel 3",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "40073",
   "name": "Max DI count channel 4",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "40075",
   "name": "Max DI count channel 5",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "40077",
   "name": "Max DI count channel 6",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "40079",
   "name": "Max DI count channel 7",
   "description": "Low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 484,
   "documented": "40485",
   "name": "Module address",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 485,
   "documented": "40486",
   "name": "Baud rate and parity",
   "description": "Bits 0-5 baud code (03 = 1200 ... 06 = 9600 ... 0A = 115200); bits 6-7 parity/stop.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 487,
   "documented": "40488",
   "name": "Modbus response delay",
   "description": "0-30 ms.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 488,
   "documented": "40489",
   "name": "Host watchdog timeout",
   "description": "0-25.5 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 704,
   "documented": "40705",
   "name": "PWM duty cycle channel 0",
   "description": "0.1-99.9 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 705,
   "documented": "40706",
   "name": "PWM duty cycle channel 1",
   "description": "0.1-99.9 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 706,
   "documented": "40707",
   "name": "PWM duty cycle channel 2",
   "description": "0.1-99.9 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 707,
   "documented": "40708",
   "name": "PWM duty cycle channel 3",
   "description": "0.1-99.9 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 708,
   "documented": "40709",
   "name": "PWM duty cycle channel 4",
   "description": "0.1-99.9 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 709,
   "documented": "40710",
   "name": "PWM duty cycle channel 5",
   "description": "0.1-99.9 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 710,
   "documented": "40711",
   "name": "PWM duty cycle channel 6",
   "description": "0.1-99.9 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 711,
   "documented": "40712",
   "name": "PWM duty cycle channel 7",
   "description": "0.1-99.9 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 736,
   "documented": "40737",
   "name": "PWM frequency channel 0",
   "description": "1-500000; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 738,
   "documented": "40739",
   "name": "PWM frequency channel 1",
   "description": "1-500000; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 740,
   "documented": "40741",
   "name": "PWM frequency channel 2",
   "description": "1-500000; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 742,
   "documented": "40743",
   "name": "PWM frequency channel 3",
   "description": "1-500000; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 744,
   "documented": "40745",
   "name": "PWM frequency channel 4",
   "description": "1-500000; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 746,
   "documented": "40747",
   "name": "PWM frequency channel 5",
   "description": "1-500000; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 748,
   "documented": "40749",
   "name": "PWM frequency channel 6",
   "description": "1-500000; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 750,
   "documented": "40751",
   "name": "PWM frequency channel 7",
   "description": "1-500000; low word at the lower address.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 800,
   "documented": "40801",
   "name": "PWM burst steps channel 0",
   "description": "1-65535; used in burst mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 801,
   "documented": "40802",
   "name": "PWM burst steps channel 1",
   "description": "1-65535; used in burst mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 802,
   "documented": "40803",
   "name": "PWM burst steps channel 2",
   "description": "1-65535; used in burst mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 803,
   "documented": "40804",
   "name": "PWM burst steps channel 3",
   "description": "1-65535; used in burst mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 804,
   "documented": "40805",
   "name": "PWM burst steps channel 4",
   "description": "1-65535; used in burst mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 805,
   "documented": "40806",
   "name": "PWM burst steps channel 5",
   "description": "1-65535; used in burst mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 806,
   "documented": "40807",
   "name": "PWM burst steps channel 6",
   "description": "1-65535; used in burst mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 807,
   "documented": "40808",
   "name": "PWM burst steps channel 7",
   "description": "1-65535; used in burst mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/icp-das/m-7088",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}