 "manufacturer": "IME",
 "manufacturer_slug": "ime",
 "model": "Conto D1 single-phase energy meter (CE111)",
 "model_slug": "conto-d1",
 "short_model": "Conto D1",
 "aliases": [
  "CE111",
  "Conto D1"
 ],
 "equipment_type": "Energy meter (DIN-rail, single-phase)",
 "applies_to": "IME Conto D1 single-phase meter, code CE111, per protocol PR133 (2025-02-24).",
 "summary": "The Conto D1 is a one-module single-phase energy meter with an RS-485 Modbus/JBUS port. Its map is short: voltage, current, frequency and powers as scaled 16-bit words, two 32-bit energy totals, and the baud rate and node address.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Addresses are the hex word addresses sent as 'first WORD address' in the request, so 0x07 is wire address 7."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Communication Modbus protocol PR133 - CE111 Conto D1",
  "doc_number": "PR133",
  "revision_date": "2025-02-24",
  "url": "https://assets.legrand.com/pim/NP-FT-GT/PR133FR.pdf",
  "pages": "Data format p. 4; commands p. 7; variables p. 8"
 },
 "notes": [
  "Double words are sent most significant word first, as stated in the data format section with a worked example.",
  "Scaling is taken from the printed formats: xxx,x V and A (tenths), xx,xx Hz (hundredths), energy 'Wh * 10' and 'varh * 10'.",
  "Left out: 0x06 power factor, whose unit and access columns are blank ('-')."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0x00",
   "name": "Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0x01",
   "name": "Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0x02",
   "name": "Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0x03",
   "name": "Active power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0x04",
   "name": "Reactive power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0x05",
   "name": "Apparent power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0x07",
   "name": "Total active energy",
   "description": "Counts in steps of 10 Wh.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 10,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0x11",
   "name": "Total reactive energy",
   "description": "Counts in steps of 10 varh.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 10,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "0x2A",
   "name": "Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1200",
    "2": "2400",
    "3": "4800",
    "4": "9600"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "0x2B",
   "name": "Node address",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 6 holding registers from 0x00 (function 03) for V, A, Hz and powers, then 2 from 0x07 for active energy and 2 from 0x11 for reactive energy.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Voltage"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Current"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Active power"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Active energy"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Reactive energy"
   }
  ],
  "enable": "Set node address and baud rate on the meter or through 0x2A/0x2B.",
  "watchdog": null,
  "quirks": [
   "A request may ask for at most 14 bytes of data (7 registers).",
   "Only functions 03 and 0x10 are supported."
  ],
  "setup": [
   "Baud rate choices are 1200, 2400, 4800 and 9600; slave response time is at least 20 ms."
  ],
  "gotchas": [
   "Energy registers count in tens of Wh/varh."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/ime/conto-d1",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}