 "manufacturer": "IME",
 "manufacturer_slug": "ime",
 "equipment_type": "Power meter",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Addresses are the hex word addresses sent as 'first WORD address' in the function 03 request, so they go on the wire unchanged."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "notes": [
  "Double-word values (UD_WORD/SD_WORD) are sent most significant word first; the protocol notes the meter can be set to big endian, little endian or swapped words, so check that setting if values look wrong.",
  "Left out: all power and energy registers, including the 0x15xx block; in this protocol their units depend on footnotes tied to the CT x VT ratio.",
  "Left out: setup parameters, device configuration words, the per-slot data areas, and any row whose printed unit does not fit the quantity (for example apparent power printed in W)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 4096,
   "documented": "0x1000",
   "name": "Phase 1: phase voltage",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4098,
   "documented": "0x1002",
   "name": "Phase 2: phase voltage",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4100,
   "documented": "0x1004",
   "name": "Phase 3: phase voltage",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4102,
   "documented": "0x1006",
   "name": "Phase 1: current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4104,
   "documented": "0x1008",
   "name": "Phase 2: current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4106,
   "documented": "0x100a",
   "name": "Phase 3: current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4108,
   "documented": "0x100c",
   "name": "Neutral current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4110,
   "documented": "0x100e",
   "name": "Chained voltage: L1-L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4112,
   "documented": "0x1010",
   "name": "Chained voltage: L2-L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4114,
   "documented": "0x1012",
   "name": "Chained voltage: L3-L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4132,
   "documented": "0x1024",
   "name": "3-phase: power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4133,
   "documented": "0x1025",
   "name": "3-phase: sector of power factor (cap or ind)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "PF = 1",
    "1": "Inductive",
    "2": "Capacitive"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4134,
   "documented": "0x1026",
   "name": "Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4139,
   "documented": "0x102b",
   "name": "Time counter for average power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4164,
   "documented": "0x1044",
   "name": "Phase 1: power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4165,
   "documented": "0x1045",
   "name": "Phase 2: power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4166,
   "documented": "0x1046",
   "name": "Phase 3: power factor",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4167,
   "documented": "0x1047",
   "name": "Phase 1: power factor sector",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "PF = 1",
    "1": "Inductive",
    "2": "Capacitive"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4168,
   "documented": "0x1048",
   "name": "Phase 2: power factor sector",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "PF = 1",
    "1": "Inductive",
    "2": "Capacitive"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4169,
   "documented": "0x1049",
   "name": "Phase 3: power factor sector",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "PF = 1",
    "1": "Inductive",
    "2": "Capacitive"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4170,
   "documented": "0x104a",
   "name": "Phase 1: THD V1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4171,
   "documented": "0x104b",
   "name": "Phase 2: THD V2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4172,
   "documented": "0x104c",
   "name": "Phase 3: THD V3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4173,
   "documented": "0x104d",
   "name": "Phase 1: THD I1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4174,
   "documented": "0x104e",
   "name": "Phase 2: THD I2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4175,
   "documented": "0x104f",
   "name": "Phase 3: THD I3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4176,
   "documented": "0x1050",
   "name": "Phase 1: I1 average",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4178,
   "documented": "0x1052",
   "name": "Phase 2: I2 average",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4180,
   "documented": "0x1054",
   "name": "Phase 3: I3 average",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4182,
   "documented": "0x1056",
   "name": "Phase 1: I1 peak maximum",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4184,
   "documented": "0x1058",
   "name": "Phase 2: I2 peak maximum",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4186,
   "documented": "0x105a",
   "name": "Phase 3: I3 peak maximum",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4188,
   "documented": "0x105c",
   "name": "(I1+I2+I3)/3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4190,
   "documented": "0x105e",
   "name": "Phase 1: V1 min",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4192,
   "documented": "0x1060",
   "name": "Phase 2: V2 min",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4194,
   "documented": "0x1062",
   "name": "Phase 3: V3 min",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4196,
   "documented": "0x1064",
   "name": "Phase 1: V1 max",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4198,
   "documented": "0x1066",
   "name": "Phase 2: V2 max",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4200,
   "documented": "0x1068",
   "name": "Phase 3: V3 max",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4613,
   "documented": "0x1205",
   "name": "Voltages sequence diagnostic",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "OK",
    "2": "Error"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers (function 03) from 0x1000 for voltages and currents in mV/mA, power factor, frequency and THD. Double words are high word first.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 4096,
    "why": "Phase 1 voltage"
   },
   {
    "table": "holding_register",
    "address": 4102,
    "why": "Phase 1 current"
   },
   {
    "table": "holding_register",
    "address": 4134,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 4132,
    "why": "3-phase power factor"
   }
  ],
  "enable": "Set the address, baud rate and parity on the meter (both are programmable). Only functions 03 and 0x10 are used. Setup writes need the unlock key 0x5AA5 written to 0x2700 first.",
  "watchdog": null,
  "quirks": [
   "Only functions 03 and 0x10 are supported (no function 04).",
   "A single request may ask for at most 240 bytes of data (100 bytes on software older than 1.09).",
   "Voltages and currents are in mV and mA."
  ],
  "setup": [
   "Baud rate and parity are programmable on the device; 8 data bits and 1 stop bit."
  ],
  "gotchas": [
   "Power and energy values are not in this map because their scale depends on the CT/VT ratio; see the protocol footnotes before using them."
  ]
 },
 "model": "Nemo 96HD multifunction meter (MF96001 / MF96021)",
 "model_slug": "nemo-96hd",
 "short_model": "Nemo 96HD",
 "aliases": [
  "MF96001",
  "MF96021",
  "Nemo 96HD"
 ],
 "applies_to": "IME Nemo 96HD panel meters MF96001 and MF96021 with an RS-485 module, per protocol PR106 (software 3.18).",
 "summary": "The Nemo 96HD is a modular 96x96 multifunction meter; with an RS-485 module it speaks Modbus/JBUS with functions 03 and 0x10. This map lists the integer measurement registers with fixed units: voltages and currents in mV/mA, power factor, frequency, THD and status values.",
 "source": {
  "title": "Communication Modbus protocol PR106 - MF96001/021 Nemo 96HD",
  "doc_number": "PR106 rev. B",
  "revision_date": "2016-10-20",
  "url": "https://assets.legrand.com/pim/NP-FT-GT/PR106FR.pdf",
  "pages": "Data format p. 4; variables pp. 8-14"
 },
 "page": "https://easymodbus.com/modbus-register-maps/ime/nemo-96hd",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}