 "manufacturer": "Inovance",
 "manufacturer_slug": "inovance",
 "model": "MD500-PLUS series AC drive",
 "model_slug": "md500-plus",
 "short_model": "MD500-PLUS",
 "aliases": [
  "MD500-PLUS",
  "MD500 PLUS",
  "MD500T-PLUS",
  "Inovance MD500-PLUS"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Inovance MD500-PLUS drives with the MD38TX1 RS-485 extension card, Modbus RTU slave, per software guide 19011580 rev. A04.",
 "summary": "Inovance's general-purpose vector drive for asynchronous and permanent-magnet motors. With the MD38TX1 RS-485 card it acts as a Modbus RTU slave. Speed goes to 1000H as a signed percentage of maximum frequency, run commands to 2000H, status and fault codes come from 3000H and 8000H, and every parameter has its own hex address (F/A groups at FxxxH/AxxxH, U0 monitors at 70xxH). This map covers the control block, the core U0 monitors with their data types and units, and the FD communication parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Addresses are hex and go on the wire unchanged: the guide's reverse-run example is 01 06 20 00 00 02, writing 2 to 2000H. Parameter addresses are the group code (F0-FE, A0-AC, 70 for U0) followed by the parameter number in hex (F3-12 = 0xF30C)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "MD500-PLUS Series General-Purpose AC Drive Software Guide",
  "doc_number": "19011580 A04",
  "revision_date": "2021-11",
  "url": "https://inovance.eu/fileadmin/downloads/Manuals/EN/MD500-PLUS/MD500-PLUS_Software_Guide_EN_A04_19011580.pdf",
  "pages": "PDF pp. 8-10, 40, 57 (parameter list F0, F9, FD), pp. 89-90 (Table 1-1 monitoring parameters, basic units), U0 parameter descriptions (data types), printed pp. 692-705 (appendix: communication data addresses, Fd group)"
 },
 "notes": [
  "Every register is one 16-bit word. Scales come from the 'Basic Unit' column of Table 1-1; signedness comes from the data type printed in each U0 parameter description.",
  "Left out: U0-14 (unit printed differently in the two tables), U0-22/U0-23, U0-32/U0-33/U0-36/U0-38 (position/debug values) and everything from U0-58 on, because Table 1-1 and the parameter descriptions give different addresses for those rows (e.g. U0-59 at 0x7035 vs 0x703B).",
  "The 1000H-1020H 'stop/run parameter' block is listed without units, so it is left out; read the U0 group instead.",
  "F9-14 holds the same fault code as 8000H; the guide prints the 8000H codes in hex (001AH = 26).",
  "Function codes: 03H read, 06H write, 10H multi-write; up to 12 consecutive registers per request, and a request must not run past the end of a parameter group."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 4096,
   "documented": "1000H",
   "name": "Communication reference",
   "description": "-10000 to 10000 = -100.00 to 100.00 % of F0-10 (or torque limit).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 7936,
   "documented": "1F00H",
   "name": "Password verification",
   "description": "Write the user password before 1F01H; reads 0000H when no password is set.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 7937,
   "documented": "1F01H",
   "name": "Parameter initialization",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": {
    "0": "No operation",
    "1": "Restore default settings (mode 1)",
    "2": "Clear records",
    "4": "Back up current user parameters",
    "501": "Restore user backup parameters",
    "503": "Restore default settings (mode 2)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "2000H",
   "name": "Control command",
   "description": "Needs F0-02 = 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": {
    "1": "Forward running",
    "2": "Reverse running",
    "3": "Forward jogging",
    "4": "Reverse jogging",
    "5": "Coast to stop",
    "6": "Decelerate to stop",
    "7": "Fault reset"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "2001H",
   "name": "DO control",
   "description": "Outputs must be assigned function 20 (communication).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "DO1",
    "1": "DO2",
    "2": "RELAY1",
    "3": "RELAY2",
    "4": "FMR",
    "5": "VDO1",
    "6": "VDO2",
    "7": "VDO3",
    "8": "VDO4",
    "9": "VDO5"
   }
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "2002H",
   "name": "AO1 control",
   "description": "0-7FFF = 0-100 %; AO1 must be assigned function 12.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8195,
   "documented": "2003H",
   "name": "AO2 control",
   "description": "0-7FFF = 0-100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8196,
   "documented": "2004H",
   "name": "Pulse output (FMP) control",
   "description": "0-7FFF = 0-100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12288,
   "documented": "3000H",
   "name": "AC drive state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Forward running",
    "2": "Reverse running",
    "3": "Stop"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28672,
   "documented": "U0-00 (0x7000)",
   "name": "U0-00 Running frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28673,
   "documented": "U0-01 (0x7001)",
   "name": "U0-01 Frequency reference",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28674,
   "documented": "U0-02 (0x7002)",
   "name": "U0-02 Bus voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28675,
   "documented": "U0-03 (0x7003)",
   "name": "U0-03 Output voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28676,
   "documented": "U0-04 (0x7004)",
   "name": "U0-04 Output current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28677,
   "documented": "U0-05 (0x7005)",
   "name": "U0-05 Output power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28678,
   "documented": "U0-06 (0x7006)",
   "name": "U0-06 Output torque",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28679,
   "documented": "U0-07 (0x7007)",
   "name": "U0-07 DI state",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28680,
   "documented": "U0-08 (0x7008)",
   "name": "U0-08 DO state",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28681,
   "documented": "U0-09 (0x7009)",
   "name": "U0-09 AI1 voltage",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28682,
   "documented": "U0-10 (0x700A)",
   "name": "U0-10 AI2 voltage",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28683,
   "documented": "U0-11 (0x700B)",
   "name": "U0-11 AI3 voltage",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28684,
   "documented": "U0-12 (0x700C)",
   "name": "U0-12 Count value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28685,
   "documented": "U0-13 (0x700D)",
   "name": "U0-13 Length value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28687,
   "documented": "U0-15 (0x700F)",
   "name": "U0-15 PID reference",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28688,
   "documented": "U0-16 (0x7010)",
   "name": "U0-16 PID feedback",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28689,
   "documented": "U0-17 (0x7011)",
   "name": "U0-17 PLC stage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28690,
   "documented": "U0-18 (0x7012)",
   "name": "U0-18 Pulse input frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "kHz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28691,
   "documented": "U0-19 (0x7013)",
   "name": "U0-19 Feedback speed",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28692,
   "documented": "U0-20 (0x7014)",
   "name": "U0-20 Remaining running time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28693,
   "documented": "U0-21 (0x7015)",
   "name": "U0-21 AI1 voltage before correction",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28697,
   "documented": "U0-25 (0x7019)",
   "name": "U0-25 Current power-on time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28698,
   "documented": "U0-26 (0x701A)",
   "name": "U0-26 Current running time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28699,
   "documented": "U0-27 (0x701B)",
   "name": "U0-27 Pulse input frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28700,
   "documented": "U0-28 (0x701C)",
   "name": "U0-28 Communication reference read-back",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28701,
   "documented": "U0-29 (0x701D)",
   "name": "U0-29 Encoder feedback speed",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28702,
   "documented": "U0-30 (0x701E)",
   "name": "U0-30 Main frequency X",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28703,
   "documented": "U0-31 (0x701F)",
   "name": "U0-31 Auxiliary frequency Y",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28706,
   "documented": "U0-34 (0x7022)",
   "name": "U0-34 Motor temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28707,
   "documented": "U0-35 (0x7023)",
   "name": "U0-35 Target torque",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28709,
   "documented": "U0-37 (0x7025)",
   "name": "U0-37 Power factor angle",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28711,
   "documented": "U0-39 (0x7027)",
   "name": "U0-39 Target voltage upon V/f separation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28712,
   "documented": "U0-40 (0x7028)",
   "name": "U0-40 Output voltage upon V/f separation",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28717,
   "documented": "U0-45 (0x702D)",
   "name": "U0-45 Fault subcode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 28718,
   "documented": "U0-46 (0x702E)",
   "name": "U0-46 Inverter unit temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 32768,
   "documented": "8000H",
   "name": "AC drive fault",
   "description": "Fault code; codes printed in hex in the guide.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "2": "Overcurrent during acceleration",
    "3": "Overcurrent during deceleration",
    "4": "Overcurrent during operation at constant speed",
    "5": "Overvoltage during acceleration",
    "6": "Overvoltage during deceleration",
    "7": "Overvoltage during operation at constant speed",
    "8": "Snubber resistor overload",
    "9": "Undervoltage fault",
    "10": "AC drive overload",
    "11": "Motor overload",
    "12": "Input phase loss",
    "13": "Output phase loss",
    "14": "IGBT overtemperature",
    "15": "External fault",
    "16": "Communication fault",
    "17": "Contactor fault",
    "18": "Current detection fault",
    "19": "Motor auto-tuning fault",
    "20": "Encoder/PG card fault",
    "21": "Parameter read-write error",
    "22": "AC drive hardware fault",
    "23": "Motor short circuit to ground",
    "26": "Running time reached",
    "27": "User-defined fault 1",
    "28": "User-defined fault 2",
    "29": "Power-on time reached",
    "30": "Load lost",
    "31": "PID feedback loss during operation",
    "40": "Fast current limit timeout",
    "41": "Motor switchover fault during operation",
    "42": "Excessive speed deviation",
    "43": "Motor overspeed",
    "45": "Motor overtemperature",
    "90": "Encoder PPR reference error",
    "91": "Encoder not connected",
    "92": "Initial position error",
    "94": "Speed feedback error"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61442,
   "documented": "F0-02 (0xF002)",
   "name": "F0-02 Command source selection",
   "description": "Set 2 so 2000H commands are accepted.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Operating panel / software",
    "1": "Terminal",
    "2": "Communication"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61443,
   "documented": "F0-03 (0xF003)",
   "name": "F0-03 Main frequency source X",
   "description": "Set 9 so 1000H sets the speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Digital setting (non-retentive)",
    "1": "Digital setting (retentive)",
    "2": "AI1",
    "3": "AI2",
    "4": "AI3",
    "5": "Pulse reference (DI5)",
    "6": "Multi-reference",
    "7": "Simple PLC",
    "8": "PID",
    "9": "Communication"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61450,
   "documented": "F0-10 (0xF00A)",
   "name": "F0-10 Maximum frequency",
   "description": "5.00-599.00 Hz; 1000H is a percentage of this.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 63758,
   "documented": "F9-14 (0xF90E)",
   "name": "F9-14 1st fault type",
   "description": "0-99; most recent fault, same codes as 8000H.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64768,
   "documented": "FD-00 (0xFD00)",
   "name": "FD-00 Baud rate",
   "description": "Default 5 (9600 bit/s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "300 bit/s",
    "1": "600 bit/s",
    "2": "1200 bit/s",
    "3": "2400 bit/s",
    "4": "4800 bit/s",
    "5": "9600 bit/s",
    "6": "19200 bit/s",
    "7": "38400 bit/s",
    "8": "57600 bit/s",
    "9": "115200 bit/s"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64769,
   "documented": "FD-01 (0xFD01)",
   "name": "FD-01 Modbus data format",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No check (8-N-2)",
    "1": "Even parity (8-E-1)",
    "2": "Odd parity (8-O-1)",
    "3": "No check (8-N-1)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64770,
   "documented": "FD-02 (0xFD02)",
   "name": "FD-02 Local address",
   "description": "1-247, default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64771,
   "documented": "FD-03 (0xFD03)",
   "name": "FD-03 Response delay",
   "description": "0-20 ms, default 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64772,
   "documented": "FD-04 (0xFD04)",
   "name": "FD-04 Modbus communication timeout",
   "description": "0.0-60.0 s; 0.0 = off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64774,
   "documented": "FD-06 (0xFD06)",
   "name": "FD-06 Communication fault reset",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null
  }
 ],
 "integration": {
  "summary": "Fit the MD38TX1 card, set F0-02 = 2 and F0-03 = 9, then write a signed percentage of F0-10 to 1000H (10000 = 100.00 %) and a run code to 2000H. Poll 3000H for run state, 8000H for faults and 7000H-7006H for frequency, voltage, current, power and torque.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8192,
    "why": "Run / stop / reset command"
   },
   {
    "table": "holding_register",
    "address": 4096,
    "why": "Speed reference as % of max frequency"
   },
   {
    "table": "holding_register",
    "address": 12288,
    "why": "Forward / reverse / stopped"
   },
   {
    "table": "holding_register",
    "address": 32768,
    "why": "Fault code"
   },
   {
    "table": "holding_register",
    "address": 28672,
    "why": "Running frequency"
   },
   {
    "table": "holding_register",
    "address": 28676,
    "why": "Output current"
   },
   {
    "table": "holding_register",
    "address": 28674,
    "why": "DC bus voltage"
   }
  ],
  "enable": "RS-485 needs the MD38TX1 extension card. F0-02 = 2 accepts run commands over communication; F0-03 = 9 makes 1000H the main frequency. FD-00..FD-02 set baud, data format and address.",
  "watchdog": "FD-04 sets a Modbus timeout (0.0 s = off); when messages stop for longer the drive reports a communication fault (Err16).",
  "quirks": [
   "1000H is a percentage, not Hz: 10000 = +100.00 % of F0-10, negative values reverse.",
   "Default serial format is 8-N-2 (FD-01 = 0).",
   "To change F-group parameters without wearing the EEPROM, replace the leading F with 0 (F3-12 -> 030CH); A-group uses 4x. Those RAM addresses are write-only."
  ],
  "setup": [
   "FD-02 address (default 1), FD-00 baud (default 5 = 9600 bit/s), FD-01 data format (default 0 = 8-N-2).",
   "Restore defaults over Modbus by writing the user password to 1F00H, then 1 to 1F01H within 30 s."
  ],
  "gotchas": [
   "Reads longer than 12 registers, or reads that cross the end of a parameter group, return an error.",
   "No reply is sent for a frame with a CRC error."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/inovance/md500-plus",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}