 "manufacturer": "Intesis (HMS Networks)",
 "manufacturer_slug": "intesis",
 "model": "IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)",
 "model_slug": "in770air-bosch-vrf",
 "short_model": "IN770AIR Bosch",
 "aliases": [
  "IN770AIR00MO000",
  "IN770AIR00SO000",
  "IN770AIRXXSO000"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).",
 "summary": "Intesis 700 Series gateway on the XYE bus of Bosch commercial / VRF systems serving Modbus RTU and TCP. Each unit index gets a 100-register block with on/off, mode, setpoint, fan, vanes, room temperature, errors and locks; low addresses hold all-unit commands.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual states no address base and gives no example frame; the first all-unit register is printed at Modbus address 0 and nothing in the tables contradicts that, so printed addresses are taken as wire addresses. Unit index n (1..N, as shown in MAPS) uses n x 100 + offset; outdoor index n uses n x 10000 + offset. This file lists unit 1 (100..134) and outdoor unit 1 (10000..10001)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "700 Series Air Gateway - IN770AIR***O000, Bosch to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual",
  "doc_number": "User Manual Version 1.0.13",
  "revision_date": "2025-12-09",
  "url": "https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770bosxxxo000.pdf",
  "pages": "pp. 27-29 (Modbus registers)"
 },
 "notes": [
  "For unit index n add (n-1) x 100 to the listed indoor addresses (unit 2 on/off = 200).",
  "Mode codes in the per-unit block (0 Heat, 1 Cool, 2 Fan, 3 Dry, 4 Auto) differ from the order of the all-unit mode commands.",
  "The manual prints 'Fan Speed Extended' (0 Auto, 1..7) and 'Unit Error Code Extended' (1..260) at the same addresses as fan speed (+3) and error code (+6); it says some registers exist only on specific unit models but does not say which.",
  "One manual covers the three licence sizes of the same hardware: IN770AIRXXSO000 (up to 4 indoor units), IN770AIR00SO000 (16) and IN770AIR00MO000 (64). The brand application is chosen in Intesis MAPS.",
  "The manual states no data type for any register. INT16 is used only where it prints a negative range (room temperature); everything else is listed as UINT16.",
  "The consumption registers (yesterday / today / total, also per heat and cool) are left out: each takes two addresses, but the manual gives no word order, and the unit is printed as Wh/kWh (selectable).",
  "Reads use FC03 or FC04; writes use FC06 only. 'T' registers are trigger-only: write the printed value (1, or the setpoint / speed) to send the command.",
  "Addressing: the manual has no addressing statement or example frame; 0-based is taken from the global On register printed at Modbus address 0 (no 1-based scheme has a register 0), with no overlap against the unit blocks.",
  "Temperature ranges are printed in both °C and °F; the manual's Modbus section does not say how the unit is chosen. °C is listed here."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "On (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Set the units on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Off (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Set the units off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Mode Auto (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3",
   "name": "Mode Heat (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Mode Dry (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "5",
   "name": "Mode Fan (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Mode Cool (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7",
   "name": "Fan speed Auto (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Fan speed Low (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "9",
   "name": "Fan speed Mid (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Fan speed High (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "11",
   "name": "Swing on (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "12",
   "name": "Swing off (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Execute"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "13",
   "name": "Temperature setpoint (all units)",
   "description": "Tenths of °C, 17..30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "14",
   "name": "Operating mode force on (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Force operating mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "15",
   "name": "Operating mode force off (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Unforce operating mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "16",
   "name": "Remote control lock on (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Lock remote control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "17",
   "name": "Remote control lock off (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Unlock remote control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "18",
   "name": "Fan speed (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Auto",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4",
    "5": "Speed 5",
    "6": "Speed 6",
    "7": "Speed 7"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "19",
   "name": "Vane left/right (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Stop",
    "1": "Step 1",
    "2": "Step 2",
    "3": "Step 3",
    "4": "Step 4",
    "5": "Step 5",
    "6": "Swing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "20",
   "name": "Vane up/down (all units)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Stop",
    "1": "Step 1",
    "2": "Step 2",
    "3": "Step 3",
    "4": "Step 4",
    "5": "Step 5",
    "6": "Swing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "(IU address[1..N] × 100) + 0",
   "name": "IU on/off",
   "description": "Unit index 1 shown; see notes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "(IU address[1..N] × 100) + 1",
   "name": "IU operation mode",
   "description": "Codes 5..8 are read-only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Heat",
    "1": "Cool",
    "2": "Fan",
    "3": "Dry",
    "4": "Auto",
    "5": "AutoHeat",
    "6": "AutoCool",
    "7": "AutoDry",
    "8": "AutoFan"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "(IU address[1..N] × 100) + 2",
   "name": "IU temperature setpoint",
   "description": "Tenths of °C, 17..30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "(IU address[1..N] × 100) + 3",
   "name": "IU fan speed",
   "description": "The manual also prints an extended set (0 Auto, 1..7) at this address.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Low",
    "2": "Med",
    "3": "High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "(IU address[1..N] × 100) + 4",
   "name": "IU vane swing",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Swing off",
    "1": "Swing on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "(IU address[1..N] × 100) + 5",
   "name": "IU room temperature",
   "description": "Tenths of °C, -20..100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "(IU address[1..N] × 100) + 6",
   "name": "IU unit error code",
   "description": "0 = no error; 1..255 (extended signal 1..260) = error.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "(IU address[1..N] × 100) + 7",
   "name": "IU communication error",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "(IU address[1..N] × 100) + 8",
   "name": "IU remote control lock",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "(IU address[1..N] × 100) + 9",
   "name": "IU force operating mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No force",
    "1": "Force"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "(IU address[1..N] × 100) + 28",
   "name": "IU vane left/right",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Step 1",
    "2": "Step 2",
    "3": "Step 3",
    "4": "Step 4",
    "5": "Step 5",
    "6": "Swing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 129,
   "documented": "(IU address[1..N] × 100) + 29",
   "name": "IU vane up/down",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Step 1",
    "2": "Step 2",
    "3": "Step 3",
    "4": "Step 4",
    "5": "Step 5",
    "6": "Swing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 132,
   "documented": "(IU address[1..N] × 100) + 32",
   "name": "IU control lock, mode Heat",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 133,
   "documented": "(IU address[1..N] × 100) + 33",
   "name": "IU control lock, mode Cool",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 134,
   "documented": "(IU address[1..N] × 100) + 34",
   "name": "IU control lock, mode Fan",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10000,
   "documented": "(OU address[1..N] × 10000) + 0",
   "name": "OU 1 error code",
   "description": "0 = no error, 1..260 = error. Outdoor index 1 shown.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10001,
   "documented": "(OU address[1..N] × 10000) + 1",
   "name": "OU 1 communication error",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Pick the Bosch application and the Modbus interface in Intesis MAPS, discover or add the units, send the project, then read and write each unit's block.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 100,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 101,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 102,
    "why": "Setpoint (x10)"
   },
   {
    "table": "holding_register",
    "address": 103,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 105,
    "why": "Room temperature (x10)"
   },
   {
    "table": "holding_register",
    "address": 106,
    "why": "Error code"
   },
   {
    "table": "holding_register",
    "address": 107,
    "why": "Communication error"
   }
  ],
  "enable": "The units must be set up in Intesis MAPS; the unit index used in the formulas is the one shown on the Signals tab.",
  "watchdog": null,
  "quirks": [
   "Writes accept FC06 (single register) only.",
   "All-unit (T) registers are trigger-only commands."
  ],
  "setup": [
   "All Modbus settings (RTU or TCP, slave address, baud, parity) are made with the Intesis MAPS tool; the manual gives no factory serial settings.",
   "On first power-up DHCP is tried for 30 seconds, then the gateway falls back to 192.168.100.246.",
   "Modbus RTU uses the EIA-485 port (A+, B-); bias and 120 ohm termination are on DIP switch block SW A."
  ],
  "gotchas": [
   "The unit index n is the one shown in the Unit column of the MAPS Signals tab."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/intesis/in770air-bosch-vrf",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}