 "manufacturer": "Intesis (HMS Networks)",
 "manufacturer_slug": "intesis",
 "model": "INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server",
 "model_slug": "inmbsdal0640000",
 "short_model": "Intesis DALI-2 Modbus",
 "aliases": [
  "INMBSDAL0640000",
  "INMBSDAL1280000",
  "Intesis Modbus Server - DALI",
  "Intesis DALI-2 Modbus gateway"
 ],
 "equipment_type": "Lighting gateway (DALI-2 to Modbus)",
 "applies_to": "Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).",
 "summary": "Gateway that exposes DALI / DALI-2 control gear on one or two DALI lines as Modbus holding registers. Addresses follow fixed formulas: per ballast short address (100 registers each), per DALI group (from 6400) and broadcast (from 6800), plus a 7000 offset for the second line. Signals cover levels, on/off, step, scenes, fade and limit settings, status and failure bits.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "parameter-derived",
  "note": "Address = 7000 x channel + 100 x short address + signal (ballasts), 7000 x line + 20 x group + 6400..6415 (groups), 7000 x line + 6800..6815 (broadcast). The manual states the result is in link-layer format with the first register at 0, so it is the wire address. Only short address 0, group 0 and two broadcast signals of channel 0 are listed."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Intesis Modbus Server - DALI (DALI-2) User Manual",
  "doc_number": "User Manual r1.2 EN (page headers read r1.1)",
  "revision_date": "2021-09",
  "url": "https://cdn.chipkin.com/assets/uploads/2022/Feb/user-manual-inmbsdalxxx0000_17-21-45-17.pdf",
  "unofficial": true,
  "pages": "p. 10 (Modbus interface), pp. 11-18 (single device map), pp. 19-20 (groups), pp. 21-22 (broadcast)"
 },
 "notes": [
  "HMS does not appear to host this manual revision publicly any more (newer IN703DAL / INMBSDAL0640200 products have their own manuals); this copy is an unaltered HMS document on an integrator's site (Chipkin).",
  "The manual says every register is a 16-bit signed integer, big endian; levels are whole percent.",
  "The map applies only when the 'Modbus Addresses' parameter in Intesis MAPS is set to Fixed.",
  "For other gear add 100 per short address (sa 0..63), 20 per group (0..15) and 7000 for DALI channel 2 (two-channel model only).",
  "Device-type-specific registers for emergency lighting (type 1, from +42) and LED gear (type 6) exist but are not listed; see the manual.",
  "Addresses 0..20000 that are not in the map are read-only and return 0; an invalid address returns a Modbus exception."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "7000 x channel + (100 x sa) + 0",
   "name": "Ballast / lamp failure bit field (ECG15-ECG0)",
   "description": "Bit set = that short address reports ballast or lamp failure.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "7000 x channel + (100 x sa) + 1",
   "name": "Ballast / lamp failure bit field (ECG31-ECG16)",
   "description": "Bit set = that short address reports ballast or lamp failure.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "7000 x channel + (100 x sa) + 2",
   "name": "Ballast / lamp failure bit field (ECG47-ECG32)",
   "description": "Bit set = that short address reports ballast or lamp failure.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "7000 x channel + (100 x sa) + 3",
   "name": "Ballast / lamp failure bit field (ECG63-ECG48)",
   "description": "Bit set = that short address reports ballast or lamp failure.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "7000 x channel + (100 x sa) + 4",
   "name": "Update all ECG status",
   "description": "Write 1 to trigger a status refresh of all gear.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Update finished",
    "1": "Trigger update"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "7000 x channel + (100 x sa) + 5",
   "name": "Ballast status (sa 0)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "BallFail",
    "1": "LampFail",
    "2": "LampPwrOn",
    "3": "BallLimErr",
    "4": "FadeRun",
    "5": "ResetSt",
    "6": "MissShAdd",
    "7": "PwrCycle"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7000 x channel + (100 x sa) + 6",
   "name": "Actual level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7000 x channel + (100 x sa) + 7",
   "name": "Device type (sa 0)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fluorescent",
    "1": "Emergency",
    "2": "Discharge",
    "3": "Halogen",
    "4": "Incandescent",
    "5": "Digital signal",
    "6": "LED",
    "7": "Switching",
    "8": "Colour control"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "7000 x channel + (100 x sa) + 8",
   "name": "Physical minimum level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "7000 x channel + (100 x sa) + 9",
   "name": "Min level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "7000 x channel + (100 x sa) + 10",
   "name": "Max level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "7000 x channel + (100 x sa) + 11",
   "name": "Power on level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "7000 x channel + (100 x sa) + 12",
   "name": "System failure level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "7000 x channel + (100 x sa) + 13",
   "name": "Fade time (sa 0)",
   "description": "DALI fade time code 0..15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "7000 x channel + (100 x sa) + 14",
   "name": "Fade rate (sa 0)",
   "description": "DALI fade rate code 1..15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "7000 x channel + (100 x sa) + 15",
   "name": "Arc power level (sa 0)",
   "description": "Dim level 0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "7000 x channel + (100 x sa) + 16",
   "name": "Arc power off / on (sa 0)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "100 %"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "7000 x channel + (100 x sa) + 17",
   "name": "Step down / up (sa 0)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Step down",
    "1": "Step up"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "7000 x channel + (100 x sa) + 18",
   "name": "Recall min level (sa 0)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Recall min level"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "7000 x channel + (100 x sa) + 19",
   "name": "Recall max level (sa 0)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Recall max level"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "7000 x channel + (100 x sa) + 20",
   "name": "Go to scene (sa 0)",
   "description": "Scene 0..15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "7000 x channel + (100 x sa) + 21",
   "name": "Store current level as scene (sa 0)",
   "description": "Scene 0..15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "7000 x channel + (100 x sa) + 22",
   "name": "Clear / remove scene (sa 0)",
   "description": "Scene 0..15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "7000 x channel + (100 x sa) + 23",
   "name": "Set fade time (sa 0)",
   "description": "0..15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "7000 x channel + (100 x sa) + 24",
   "name": "Set fade rate (sa 0)",
   "description": "1..15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "7000 x channel + (100 x sa) + 25",
   "name": "Set min level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "7000 x channel + (100 x sa) + 26",
   "name": "Set max level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "7000 x channel + (100 x sa) + 27",
   "name": "Set power-on level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "7000 x channel + (100 x sa) + 28",
   "name": "Set system-failure level (sa 0)",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "7000 x channel + (100 x sa) + 31",
   "name": "Multicontrol (sa 0)",
   "description": "Coded command: 0 off, 1 100%, 2 up, 3 down, 1XX scene, 2XX store, 3XX remove, 1XXX-6XXX settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6400,
   "documented": "7000 * line + (20 * gr) + 6400",
   "name": "Group 0: Arc power level",
   "description": "0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6401,
   "documented": "7000 * line + (20 * gr) + 6401",
   "name": "Group 0: Arc power off / on",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "100 %"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6402,
   "documented": "7000 * line + (20 * gr) + 6402",
   "name": "Group 0: Step down / up",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Step down",
    "1": "Step up"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6403,
   "documented": "7000 * line + (20 * gr) + 6403",
   "name": "Group 0: Recall min level",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Recall min level"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6404,
   "documented": "7000 * line + (20 * gr) + 6404",
   "name": "Group 0: Recall max level",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Recall max level"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6405,
   "documented": "7000 * line + (20 * gr) + 6405",
   "name": "Group 0: Go to scene",
   "description": "Scene 0..15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6800,
   "documented": "7000 * line + 6800",
   "name": "Broadcast: arc power level",
   "description": "All gear on the line, 0..100 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6801,
   "documented": "7000 * line + 6801",
   "name": "Broadcast: arc power off / on",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "100 %"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Configure the gateway in Intesis MAPS with fixed Modbus addresses, then write arc power level (sa x 100 + 15) or the group/broadcast level registers and read actual level (sa x 100 + 6) and ballast status (+5).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 15,
    "why": "Set level of short address 0"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Actual level of short address 0"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Ballast status"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Failure bits for sa 0-15"
   },
   {
    "table": "holding_register",
    "address": 6400,
    "why": "Group 0 level"
   },
   {
    "table": "holding_register",
    "address": 6800,
    "why": "Broadcast level"
   }
  ],
  "enable": "All settings (Modbus RTU/TCP parameters, slave number, IP, Fixed address mode) are made in the Intesis MAPS configuration tool.",
  "watchdog": null,
  "quirks": [
   "The two-channel model (1280000) is Modbus TCP only.",
   "Writes use FC06 or FC16; reads FC03 or FC04."
  ],
  "setup": [
   "RTU: 1200..115200 baud, parity and stop bits selectable, EIA-485 or EIA-232.",
   "TCP: port 502 by default, plus keep-alive and IP settings in MAPS."
  ],
  "gotchas": [
   "Status registers only refresh after an update; write 1 to register 4 to trigger a full ECG status update."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/intesis/inmbsdal0640000",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}