 "manufacturer": "Intesis (HMS Networks)",
 "manufacturer_slug": "intesis",
 "model": "INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway",
 "model_slug": "inmbsmhi128o000",
 "short_model": "INMBSMHI128O000 MHI Superlink",
 "aliases": [
  "INMBSMHI128O000",
  "INMBSMHI048O000",
  "MH-AC-MBS-128",
  "MH-AC-MBS-48",
  "Intesis Modbus Server MHI Superlink"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).",
 "summary": "Gateway that sits on the Mitsubishi Heavy Industries Superlink bus and exposes up to 128 (or 48) indoor units as a fixed Modbus map: 20 registers per unit address with on/off, mode, setpoint, fan, louver, room temperature, error and lock, plus a few all-unit commands. Modbus RTU (RS-485 or RS-232) and Modbus TCP.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "The tables say 'base addr is 1': printed register 1 is wire address 0. Indoor unit with Superlink address n (0..127) uses printed n x 20 + 1 .. n x 20 + 14, so wire n x 20 + 0..13. This file lists unit address 0 (printed 1..14, wire 0..13) and the all-unit block (printed 2995..3000)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Intesis Modbus Server - Mitsubishi Heavy Industries AC User's Manual",
  "doc_number": "User's Manual r1.0 eng",
  "revision_date": "2012-05",
  "url": "https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsmhixxxo000.pdf",
  "pages": "pp. 8-10 (Modbus interface and address map), p. 26 (error codes)"
 },
 "notes": [
  "Only indoor unit address 0 is listed. For unit address n add n x 20 to each wire address (unit 127 on/off: printed 2542, wire 2541).",
  "The manual says registers are 2-byte big-endian values but does not say signed or unsigned; all listed values are non-negative, so UINT16 is used.",
  "Temperatures are whole °C (no x10).",
  "Writes must use function 06 (single register). Reads use 03 or 04. A poll range containing an invalid address returns an exception.",
  "Error code numbers match MHI remote-controller E codes (value 40 = E40 high pressure); full table on p. 26 of the manual.",
  "INMBSMHI048O000 serves unit addresses 00..47 only."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "IU communication status",
   "description": "Indoor unit address 0 shown; see notes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Communication OK",
    "1": "Communication error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "IU on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "IU operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cool",
    "1": "Heat",
    "2": "Fan",
    "3": "Auto",
    "4": "Dry"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "4",
   "name": "IU setpoint temperature",
   "description": "Whole °C, 16..30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "IU fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Low",
    "1": "Medium",
    "2": "High",
    "3": "Powerful"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "6",
   "name": "IU remote controller lock",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Remote controller locked",
    "1": "Remote controller unlocked"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7",
   "name": "IU louver control",
   "description": "Reads Swing while the louver moves between positions.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Swing",
    "1": "Pos 1",
    "2": "Pos 2",
    "3": "Pos 3",
    "4": "Pos 4"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "8",
   "name": "IU room temperature",
   "description": "Whole °C, 0..30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "9",
   "name": "IU filter sign",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "10",
   "name": "IU error code",
   "description": "0 = no error; 1..99 = MHI E-code number (e.g. 9 = E9 drain trouble).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "11",
   "name": "IU compressor status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "12",
   "name": "IU filter sign reset",
   "description": "Reads back 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Clear filter alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "13",
   "name": "IU remote controller error reset",
   "description": "Reads back 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Clear remote controller error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "14",
   "name": "IU thermo on/off status",
   "description": "Inverter units only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2994,
   "documented": "2995",
   "name": "Hardware communication status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No hardware communication error",
    "1": "Hardware communication error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2995,
   "documented": "2996",
   "name": "All units on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2996,
   "documented": "2997",
   "name": "All units operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Cool",
    "1": "Heat",
    "2": "Fan",
    "3": "Auto",
    "4": "Dry"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2997,
   "documented": "2998",
   "name": "All units setpoint",
   "description": "Whole °C, 16..30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2998,
   "documented": "2999",
   "name": "All units fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Low",
    "1": "Medium",
    "2": "High",
    "3": "Powerful"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2999,
   "documented": "3000",
   "name": "All units remote controller lock",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Remote controller locked",
    "1": "Remote controller unlocked"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Enable the indoor units in LinkBoxMB, set the SLK selector (New = Superlink-II, Old = Superlink-I), then poll each unit's 20-register block. Write single registers (FC06) for on/off, mode, setpoint and fan.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Unit communication status"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Setpoint (°C)"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Room temperature (°C)"
   },
   {
    "table": "holding_register",
    "address": 9,
    "why": "Error code"
   },
   {
    "table": "holding_register",
    "address": 2994,
    "why": "Gateway hardware communication status"
   }
  ],
  "enable": "Each indoor unit must be enabled in the LinkBoxMB Devices list and the configuration file sent to the gateway.",
  "watchdog": "A per-unit communication-error signal is raised when a unit stops answering within the 'Timeout response' set in LinkBoxMB (2000..10000 ms).",
  "quirks": [
   "Printed addresses are 1-based: subtract 1 for the wire address.",
   "Only FC06 is supported for writes (no FC16).",
   "Mode codes differ from most other Intesis maps: 0 = Cool, 1 = Heat, 2 = Fan, 3 = Auto, 4 = Dry."
  ],
  "setup": [
   "Configure Modbus (TCP and/or RTU, RS-485 on C1 or RS-232 on C2, baud 1200..38400, parity, slave number) in LinkBoxMB over the console port.",
   "Superlink connects to the A-B terminals (no polarity), max 1000 m, no loop wiring.",
   "Set the SLK selector to NEW for Superlink-II systems or OLD for Superlink-I."
  ],
  "gotchas": [
   "With SC-SL2NA / SC-SL3NA central controllers present, unconnected indoor units must be deregistered and the remote lock rights adjusted (see manual section 1)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/intesis/inmbsmhi128o000",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}