 "manufacturer": "Invertek Drives",
 "manufacturer_slug": "invertek-drives",
 "model": "Optidrive Coolvert compressor drive (built-in Modbus RTU)",
 "model_slug": "optidrive-coolvert",
 "short_model": "Optidrive Coolvert",
 "aliases": [
  "Optidrive CoolVert",
  "Coolvert"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Invertek Optidrive Coolvert HVAC compressor drives on the terminal or RJ45 Modbus RTU port, per user guide version 2.01.",
 "summary": "The Optidrive Coolvert is Invertek's variable speed drive for refrigeration and HVAC compressors (BLDC, PM, induction and synchronous reluctance). Modbus RTU is built in on control terminals 1-3 and the RJ45 port. Registers 1-5 take the control word, speed set point in rps and ramp time; registers 7-45 report speed, current, power, trip codes, energy and run time. Every parameter also has its own register (P1-11 = 111).",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 115200,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The guide numbers registers from 1 and tells masters that start at register 0 to subtract 1, so control word register 1 is wire address 0. Parameters use their group and number as the register (P6-04 = register 604 = wire address 603)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Optidrive Coolvert User Guide",
  "doc_number": "Version 2.01",
  "revision_date": null,
  "url": "https://www.invertekdrives.com/downloads/Optidrive%20Coolvert%20User%20Guide%20V2.01.pdf",
  "pages": "5.5 Modbus connections and telegram structure pp. 44-47 (status word, control word); 5.6 register list p. 48; P0 list pp. 49-50; P1-11 and group 6 parameters pp. 52-59; trip codes 6.1 pp. 60-62"
 },
 "notes": [
  "Left out: register 6 (drive status). The guide describes it both as a 16-bit status word with bits 0-15 defined and as a single byte holding the last fault code, so its layout cannot be settled. Use register 9 for the trip code.",
  "Register 3 is not listed. Function 16 (write multiple) is accepted for registers 1-4 only; 03 and 06 work on the others.",
  "The guide states no signedness for most registers. Speed and analogue values that can go negative are typed INT16, counters and ratings UINT16.",
  "Registers 5, 40 and 42 use an 'IDL format' where 3000 = 50 Hz; they are kept raw.",
  "P6-02 (baud rate) is left out because the guide shows it in kbps (default 115) next to a 0-5 option list, so the stored value is unclear.",
  "Only the parameters an integrator needs for Modbus control are listed; every other parameter is reachable at its group-and-number register (for example 107 for P1-07).",
  "Trip codes listed are the A-class table; frame 3-5 drives with EN/UL 60730 certification also have class B trips."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Drive control word",
   "description": "Run, coast stop, fault reset, relay and crankcase heating commands.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run (1) / stop (0)",
    "2": "Coast stop request",
    "3": "Fault reset request (return to 0 after reset)",
    "4": "User relay control (P3-05 = 6)",
    "5": "Activate crankcase heating"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Speed set point",
   "description": "600 = 60.0 rps. Negative values only if enabled by parameter.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "rps",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "4",
   "name": "Modbus user ramp time",
   "description": "3000 = 300.0 s; used only when P6-06 = 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "Speed reference (IDL format)",
   "description": "Printed scaling: 3000 = 50.0 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7",
   "name": "Output frequency (compressor speed)",
   "description": "600 = 60.0 rps (P0-60).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "rps",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "8",
   "name": "Output current",
   "description": "100 = 10.0 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "9",
   "name": "Trip code",
   "description": "Active trip code; 0 when healthy.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No trip",
    "3": "O-I over current",
    "5": "PS-trp power stage trip",
    "6": "O-Volt over voltage",
    "7": "U-Volt under voltage",
    "10": "P-DEF load default parameters",
    "11": "E-Trip external trip (STO opened while running)",
    "12": "SC-OBS Optibus serial comms fault",
    "13": "Flt-DC excessive DC bus ripple",
    "14": "P-Loss input phase loss",
    "15": "h O-I hardware over current",
    "17": "DATA-F I/O processor data error",
    "18": "4-20F 4-20 mA signal out of range",
    "19": "DATA-E motor control processor data error",
    "20": "U-DEF user parameters default",
    "21": "F-PTC motor PTC overheat",
    "22": "FAN-F drive cooling fan fault",
    "23": "O-hEAt ambient temperature too high",
    "26": "Out-F drive output fault",
    "29": "STO-F fault in STO circuit",
    "40": "AtF-01 stator resistance unbalance",
    "41": "AtF-02 stator resistance too large",
    "42": "AtF-03 motor inductance too low",
    "43": "AtF-04 motor inductance too large",
    "44": "AtF-05 parameters not convergent",
    "49": "Out-Ph motor output phase loss",
    "50": "SC-F01 Modbus comms fault",
    "81": "OI-U phase U over current",
    "82": "OI-V phase V over current",
    "83": "OI-W phase W over current",
    "88": "Out-U phase U output fault",
    "89": "Out-V phase V output fault",
    "90": "Out-W phase W output fault",
    "97": "SC-Los IO-PS comms loss",
    "98": "DATA-03 wrong VDo3 checksum",
    "101": "STO-R STO opened at drive running",
    "102": "ML-Run mains loss at running",
    "103": "FW-Err PS firmware is changed",
    "107": "Stall compressor is stalled",
    "253": "HW-ID hardware ID not supported",
    "254": "Type-E drive ID not supported"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "10",
   "name": "Output power",
   "description": "1000 = 10.00 kW.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "11",
   "name": "Digital input status",
   "description": "Bit 0 = digital input 1 (P0-03).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Digital input 1"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "12",
   "name": "Rating ID",
   "description": "Frame size and input voltage code (P0-29).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "13",
   "name": "Power rating",
   "description": "P0-29 entry 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "14",
   "name": "Voltage rating",
   "description": "P0-29 entry 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "15",
   "name": "IO processor software version",
   "description": "100 = 1.00.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "16",
   "name": "Compressor control processor software version",
   "description": "100 = 1.00.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "17",
   "name": "Drive type",
   "description": "P0-29 entry 4 (drive ID).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "20",
   "name": "Analogue input signal level",
   "description": "1000 = 100.0 % (P0-01, range -100.0 to 100.0 %).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "22",
   "name": "Pre-ramp speed reference",
   "description": "600 = 60.0 rps.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "rps",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "23",
   "name": "DC bus voltage",
   "description": "600 = 600 V (P0-20).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "24",
   "name": "Drive temperature",
   "description": "Heatsink temperature, 40 = 40 °C (P0-21).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "25",
   "name": "Drive serial number 4",
   "description": "Serial number part (P0-30).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "26",
   "name": "Drive serial number 3",
   "description": "Serial number part (P0-30).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "27",
   "name": "Drive serial number 2",
   "description": "Serial number part (P0-30).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "28",
   "name": "Drive serial number 1",
   "description": "Serial number part (P0-30).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "29",
   "name": "Relay output status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "30",
   "name": "Last two faults",
   "description": "Two trip codes, one per byte (P0-13).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "31",
   "name": "Previous two faults",
   "description": "Two older trip codes, one per byte (P0-13).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "32",
   "name": "kWh meter",
   "description": "100 = 10.0 kWh; rolls into the MWh meter at 999.9 (P0-26).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "33",
   "name": "MWh meter",
   "description": "100 = 100 MWh (P0-27).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "34",
   "name": "Running time - hours",
   "description": "Hours run since manufacture (P0-31).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "35",
   "name": "Running time - min/sec",
   "description": "Minutes and seconds part of P0-31; packing not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "36",
   "name": "Run time since enable - hours",
   "description": "P0-34.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "37",
   "name": "Run time since enable - min/sec",
   "description": "Minutes and seconds part of P0-34; packing not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "39",
   "name": "Room (control PCB) temperature",
   "description": "40 = 40 °C (P0-05).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "40",
   "name": "Speed reference value",
   "description": "Printed scaling: 3000 = 50 Hz.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "42",
   "name": "Compressor speed (IDL format)",
   "description": "Printed scaling: 3000 = 50 Hz.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "43",
   "name": "Compressor output voltage",
   "description": "100 = 100 V AC (P0-11).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "44",
   "name": "Indirect parameter access index",
   "description": "Parameter to access through register 45.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "45",
   "name": "Indirect parameter access value",
   "description": "Value of the parameter chosen in register 44.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "111",
   "name": "P1-11 Primary command source",
   "description": "Set 0 for Modbus control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Modbus control",
    "1": "Terminal mode",
    "2": "Terminal mode, start when AI1 > 10 %",
    "3": "User PI mode",
    "4": "Slave mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 600,
   "documented": "601",
   "name": "P6-01 Fieldbus drive address",
   "description": "1-63, default 1; Modbus address unless P6-08 is set.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 602,
   "documented": "603",
   "name": "P6-03 Modbus data format",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity, 1 stop bit (default)",
    "1": "No parity, 2 stop bits",
    "2": "Odd parity, 1 stop bit",
    "3": "Even parity, 1 stop bit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 603,
   "documented": "604",
   "name": "P6-04 Communications loss timeout",
   "description": "0-60 s, default 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 604,
   "documented": "605",
   "name": "P6-05 Communications loss action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Trip",
    "1": "Ramp to stop then trip",
    "2": "Ramp to stop (no trip)",
    "3": "Run at signal loss speed P3-11"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 605,
   "documented": "606",
   "name": "P6-06 Fieldbus ramp control enable",
   "description": "1 = ramps come from register 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (internal ramps)",
    "1": "Enabled (ramps from fieldbus)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 606,
   "documented": "607",
   "name": "P6-07 Modbus response delay",
   "description": "Extra characters of delay, 0-16.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 607,
   "documented": "608",
   "name": "P6-08 Modbus address",
   "description": "0-200; 0 = use P6-01 for Modbus too.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set P1-11 = 0, close the STO circuit, then write register 1 = 1 to run and register 2 with the speed in 0.1 rps. Poll registers 7, 8, 10 and 9 for speed, current, power and the trip code.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Control word: run, coast stop, reset"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Speed set point, 0.1 rps"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Compressor speed, 0.1 rps"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Output current, 0.1 A"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Trip code"
   },
   {
    "table": "holding_register",
    "address": 9,
    "why": "Output power, 0.01 kW"
   },
   {
    "table": "holding_register",
    "address": 110,
    "why": "P1-11 command source"
   }
  ],
  "enable": "Set P1-11 = 0 (Modbus mode). The STO inputs (terminals 8 and 9) must be energised for the drive to run. Set the drive address in P6-01 (or a separate Modbus address in P6-08), the baud rate in P6-02 and parity in P6-03. Set P6-06 = 1 to take ramp times from register 4.",
  "watchdog": "P6-04 sets the communication-loss time (0-60 s, default 5 s). P6-05 picks the reaction: 0 trip (default), 1 ramp to stop then trip, 2 ramp to stop without a trip, 3 run at the signal-loss speed P3-11. A comms loss trip shows as code 50 (SC-F01).",
  "quirks": [
   "Register numbers are 1-based: subtract 1 for the wire address.",
   "Speeds are in revolutions per second (rps), not Hz or rpm; the IDL-format registers are the exception.",
   "The fault-reset bit in the control word must be returned to 0 after the reset or the drive will reset again unexpectedly."
  ],
  "setup": [
   "RS-485 on control terminals 1 (0 V), 2 (+) and 3 (-), or RJ45 pins 3 (0 V), 8 (+) and 7 (-).",
   "Factory settings: address 1, 115.2 kbps, no parity, 1 stop bit.",
   "Connect 0 V common to every device; terminate the shield at the controller only, not at the drive."
  ],
  "gotchas": [
   "The RJ45 port is not Ethernet; do not plug it into a network switch.",
   "Class B trips on frame 3-5 drives cannot be reset for two minutes, and ten trips of one kind before a power cycle cause a lockout that only a power cycle clears."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/invertek-drives/optidrive-coolvert",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}