 "manufacturer": "Invertek Drives",
 "manufacturer_slug": "invertek-drives",
 "model": "Optidrive E3 IP20 (built-in Modbus RTU)",
 "model_slug": "optidrive-e3",
 "short_model": "Optidrive E3",
 "aliases": [
  "ODE-3",
  "Optidrive E3",
  "ODE-3 IP20",
  "Optidrive ODE-3"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Invertek Optidrive E3 (ODE-3) IP20 drives on the RJ45 Modbus RTU port, per user guide 82-E3I20-IN V1.05.",
 "summary": "Invertek's compact general purpose variable frequency drive with Modbus RTU on the front RJ45 port. Registers 1-4 take the control word, frequency setpoint, PI setpoint and ramp time; registers 7-24 and 2001-2016 report status, output values, I/O and the trip code. Parameters P-04 to P-60 sit at register 128 + parameter number. This map covers the control and monitoring block plus the command-source parameter.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 115200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The guide numbers registers from 1 and tells zero-based masters to subtract 1, so register 1 (control word) is wire address 0 and register 2001 is address 2000. Parameter registers are 128 + parameter number (P-12 = register 140 = address 139)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Optidrive ODE-3 User Guide",
  "doc_number": "82-E3I20-IN V1.05",
  "revision_date": null,
  "url": "https://admin.invertekdrives.com/assets/A09D2FA5-3BCD-4511-BA4D-A4878F2634AE/82-E3I20-IN_V1.05%20E3%20IP20%20User%20Guide%20V1.04%20ENGLISH.pdf",
  "pages": "Section 8 Modbus RTU pp. 32-35 (specification, RJ45 pins, register map 8.4, status word 2001 and IO word 2005); P-12 p. 22; P-36 and P-63 parameter descriptions; fault codes 10.1 p. 39"
 },
 "notes": [
  "Left out: register 6 (drive status / error code) because the guide contradicts itself on which byte holds the error code (the table says low byte, the bit table puts status in bits 0-7 and the trip code in the high byte). Use register 2001 (status) and 2016 (trip code) instead.",
  "Parameter registers P-04 to P-60 (128 + parameter number) are left out apart from P-12: the guide says some use internal scaling without stating it. P-36 (address, baud, watchdog) has three sub-indexes and no stated register layout.",
  "The guide does not state signedness for most registers. Values with a 0-n range are typed UINT16; torque (+/-200 %) and motor output speed (status bit 13 = negative speed) are typed INT16.",
  "Function code 16 (write multiple) is accepted for registers 1-4 only; 03 and 06 work on all registers.",
  "The E3 IP66 Indoor guide (82-E3MAN-IN V2.00) lists only registers 1-24 with slightly different register-6 wording; this map follows the IP20 guide.",
  "Register 3 scaling is given only as 0-4096 = 0-100.0 %, so it is kept raw."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Control word",
   "description": "Run enable, decel ramp select, fault reset, coast stop, relay/DO control.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "1 = run enable, 0 = stop",
    "1": "0 = decel ramp 1 (P-04), 1 = decel ramp 2 (P-24)",
    "2": "1 = fault reset",
    "3": "1 = coast stop request",
    "8": "Relay control: 0 = open, 1 = close",
    "9": "DO control: 1 = off, 0 = on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Frequency setpoint",
   "description": "0-5000 = 0.0-500.0 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "PI setpoint / analog output control",
   "description": "0-4096 = 0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "4",
   "name": "Ramp time",
   "description": "0-60000; used when P-12 = 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7",
   "name": "Output motor frequency",
   "description": "0-20000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "8",
   "name": "Output motor current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "11",
   "name": "Digital input status",
   "description": "Lowest bit = input 1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI1",
    "1": "DI2",
    "2": "DI3",
    "3": "DI4"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "20",
   "name": "Analog input 1 value (P00-01)",
   "description": "Percent of full scale.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "21",
   "name": "Analog input 2 value (P00-02)",
   "description": "Percent of full scale.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "22",
   "name": "Speed reference value (P00-03)",
   "description": "Active setpoint frequency.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "23",
   "name": "DC bus voltage (P00-08)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "24",
   "name": "Drive temperature (P00-09)",
   "description": "Heatsink temperature.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 139,
   "documented": "140 (P-12)",
   "name": "P-12 Primary command source",
   "description": "Set 3 or 4 for Modbus control; register = 128 + 12.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Terminal control",
    "1": "Keypad, forward only",
    "2": "Keypad, forward/reverse",
    "3": "Modbus, internal ramps",
    "4": "Modbus, ramps written over Modbus (register 4)",
    "5": "PI control",
    "6": "PI control + AI1 summation",
    "7": "CAN, internal ramps",
    "8": "CAN, ramps over CAN",
    "9": "Slave mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2000,
   "documented": "2001",
   "name": "Status word 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Ready (no trip, no mains loss, hardware enabled)",
    "1": "Running",
    "2": "Tripped",
    "3": "Standby",
    "4": "Fire mode active",
    "6": "At speed (setpoint reached)",
    "7": "Below minimum speed (P-02)",
    "8": "Overload (current > P-08)",
    "9": "Mains loss",
    "10": "Heatsink > 85 °C",
    "11": "Control board > 80 °C",
    "12": "Switching frequency foldback active",
    "13": "Reverse rotation (negative speed)",
    "15": "Toggles on every read"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2001,
   "documented": "2002",
   "name": "Motor output speed",
   "description": "Hz with one decimal; negative in reverse (see 2001 bit 13).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2002,
   "documented": "2003",
   "name": "Motor output current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "2004",
   "name": "Motor output power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2004,
   "documented": "2005",
   "name": "IO status word",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI1 closed",
    "1": "DI2 closed",
    "2": "DI3 (AI-2) closed",
    "3": "DI4 (AI-1) closed",
    "6": "IP66 FWD switch closed",
    "7": "IP66 REV switch closed",
    "8": "Digital output active / analog output > 0",
    "9": "Relay closed",
    "12": "AI1 4-20 mA signal lost",
    "13": "AI2 4-20 mA signal lost",
    "15": "IP66 pot input > 50 %"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2005,
   "documented": "2006",
   "name": "Motor output torque",
   "description": "0.0 to +/-200.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2006,
   "documented": "2007",
   "name": "DC bus voltage (P00-08)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2007,
   "documented": "2008",
   "name": "Heatsink temperature (P00-09)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2008,
   "documented": "2009",
   "name": "Analog input 1 (P00-01)",
   "description": "Raw 0-4096 (12 bit).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2009,
   "documented": "2010",
   "name": "Analog input 2 (P00-02)",
   "description": "Raw 0-4096 (12 bit).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2010,
   "documented": "2011",
   "name": "Analog output",
   "description": "0.0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2011,
   "documented": "2012",
   "name": "PI output (P00-05)",
   "description": "0.0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2012,
   "documented": "2013",
   "name": "Internal temperature (P00-20)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2013,
   "documented": "2014",
   "name": "Motor output voltage (P00-07)",
   "description": "0-500 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2014,
   "documented": "2015",
   "name": "IP66 pot input value",
   "description": "Raw 0-4096 (12 bit).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2015,
   "documented": "2016",
   "name": "Trip code",
   "description": "Fault code per the guide's fault table; 0 = no fault.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Brake channel over current",
    "2": "Brake resistor overload",
    "3": "Output over current",
    "4": "Motor thermal overload (I2t)",
    "6": "DC bus over voltage",
    "7": "DC bus under voltage",
    "8": "Heatsink over temperature",
    "9": "Under temperature",
    "10": "Factory default parameters loaded",
    "11": "External trip",
    "12": "Optibus comms loss",
    "13": "DC bus ripple too high",
    "14": "Input phase loss",
    "15": "Output over current (short circuit)",
    "16": "Faulty heatsink thermistor",
    "17": "Internal memory fault (IO)",
    "18": "4-20 mA signal lost",
    "19": "Internal memory fault (DSP)",
    "21": "Motor PTC thermistor trip",
    "22": "Cooling fan fault (IP66 only)",
    "23": "Drive internal temperature too high",
    "26": "Output fault",
    "41": "Autotune fault",
    "50": "Modbus comms loss",
    "51": "CAN comms loss"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set P-12 = 3 (or 4 to write ramp times in register 4), keep digital input 1 closed as the hardware enable, then write register 1 = 1 to run and register 2 with the frequency x10. Poll 2001 for status, 2002-2004 for speed, current and power, and 2016 for the trip code.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Control word: run, reset, coast stop"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Frequency setpoint, 0.1 Hz"
   },
   {
    "table": "holding_register",
    "address": 2000,
    "why": "Status word 2"
   },
   {
    "table": "holding_register",
    "address": 2001,
    "why": "Motor output speed, 0.1 Hz"
   },
   {
    "table": "holding_register",
    "address": 2002,
    "why": "Motor output current, 0.1 A"
   },
   {
    "table": "holding_register",
    "address": 2003,
    "why": "Motor output power, 0.1 kW"
   },
   {
    "table": "holding_register",
    "address": 2015,
    "why": "Trip code"
   },
   {
    "table": "holding_register",
    "address": 139,
    "why": "P-12 command source"
   }
  ],
  "enable": "Set P-12 = 3 (Modbus with internal ramps) or 4 (ramps from register 4). Set the drive address, baud rate and watchdog in P-36 indexes 1-3 (factory address 1, 115.2 kbps). An enable signal on digital input 1 is still required in Modbus mode. P-14 must hold the access code (P-37, factory 101) to reach parameters above P-14.",
  "watchdog": "P-36 index 3 sets the communication-loss time: 0 disables it, or 30, 100, 1000 or 3000 ms (factory 3000 ms with trip). A 't' suffix trips the drive (fault 50, Modbus comms loss); the other suffix coast-stops without tripping. P-63 decides whether any valid telegram (0, standard) or only telegrams for this node (1, advanced) reset the timer.",
  "quirks": [
   "Register numbers are 1-based: subtract 1 for the wire address.",
   "Only 8-N-1 framing is listed; the factory baud rate is 115200.",
   "Parameter registers are 128 + parameter number, not the parameter number itself."
  ],
  "setup": [
   "Wire RS485- to RJ45 pin 7, RS485+ to pin 8 and 0 V common to pin 3; pins 4/5 are the PC/keypad port.",
   "Use twisted pair for RS485+/-, connect 0 V common across all devices, and terminate the shield at the controller only.",
   "The RJ45 port is not Ethernet: do not plug it into a network switch."
  ],
  "gotchas": [
   "With the factory P-63 = 0, telegrams for other nodes also keep the watchdog alive.",
   "After an over current or overload trip (codes 3, 4, 15) a reset is refused until the built-in delay has elapsed."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/invertek-drives/optidrive-e3",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}