 "manufacturer": "Invertek Drives",
 "manufacturer_slug": "invertek-drives",
 "model": "Optidrive Elevator Core (built-in Modbus RTU)",
 "model_slug": "optidrive-elevator-core",
 "short_model": "Elevator Core",
 "aliases": [
  "Elevator Core",
  "Optidrive Elevator Core"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Invertek Elevator Core lift drives on the RJ45 Modbus RTU port, per the online Elevator Core user guide (support.invertekdrives.com).",
 "summary": "The Elevator Core is Invertek's drive for lift (elevator) motors, geared or gearless, open or closed loop. Modbus RTU is built in on the RJ45 port. Register 1 runs the drive forward or reverse and resets faults, register 2 sets the speed in the drive's active unit, and registers 5-48 report status, speed, current, torque, power, faults and run time. Parameters sit at their group-and-number register, and group 0 monitor values at 10000 + number.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 115200,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Registers are numbered from 1. The guide's worked telegrams settle it: the control-word write is broken down as physical address 0x0000 = logical register 1, and the status-word read uses physical 0x0005 for register 6. Parameters use group and number (P1-01 = register 101 = wire address 100); group 0 is read at 10000 + parameter number."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Elevator Core User Guide (online) - Modbus RTU Individual Register Details",
  "doc_number": null,
  "revision_date": null,
  "url": "https://support.invertekdrives.com/elevator-core/en/modbus-rtu-individual-register-details.html",
  "pages": "Topics: Modbus RTU Individual Register Details (control word, speed reference, status word, control and monitoring registers); Modbus RTU Specification (modbus-rtu-specification.html); Modbus RTU Connecting to the Drive (modbus-rtu-connecting-to-the-drive.html); Group 2 parameters (group-2-parameter-descriptions.html)"
 },
 "notes": [
  "Source is Invertek's official online user guide (HTML), spread over the topics named in the source pages field.",
  "Fault reset: the bit tables put reset on control-word bit 2, while one troubleshooting line says bit 3; this map follows the bit tables (bit 2, also shown in P2-50). The reset only acts on a 0 to 1 change.",
  "A troubleshooting line says the fault code is in the upper byte of register 6, but the status-word topic defines all 16 bits of register 6 and puts the fault code in P2-56 (register 256) and register 18. This map follows the status-word topic.",
  "P2-56 low-byte status bits are left as a plain value: the register-details topic and the group 2 topic give different bit layouts.",
  "Speed registers (2, 5, 7, 22) use the drive's active unit, set by P4-06 and P3-08: Hz (0.1), rpm (1), ft/s (0.01) or m/s (0.01). They are kept raw. Signedness is not printed; speeds are typed INT16 because the drive runs in both directions.",
  "Registers 3, 4, 12, 32, 33 and 40-47 are reserved. The CANopen interface and the full parameter list are not covered here.",
  "Supported functions: 03, 06 and 16."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Command control word",
   "description": "Run forward, run reverse and fault reset; needs P1-01 = 1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run forward (0 = stop)",
    "1": "Run reverse (0 = stop)",
    "2": "Fault reset request"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Commanded speed reference",
   "description": "Units follow the drive setting: 0.1 Hz, 1 rpm, 0.01 ft/s or 0.01 m/s.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "Internal speed reference",
   "description": "Pre-ramp speed reference (as P0-13), 0.01 resolution in the active unit.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "6",
   "name": "Status word",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Ready (no fault, mains present, safety chain closed)",
    "1": "Running",
    "2": "Tripped",
    "6": "At speed set-point",
    "7": "Below minimum speed (P8-02) while enabled",
    "8": "Overload (current above P4-03)",
    "9": "Mains loss",
    "10": "Heatsink above 85 °C",
    "11": "Control board above 80 °C",
    "12": "Switching frequency reduction active",
    "13": "Reverse rotation",
    "14": "Auto-tune active",
    "15": "Live toggle bit"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7",
   "name": "Output speed",
   "description": "In the active speed unit, two decimal places.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "8",
   "name": "Output current",
   "description": "105 = 10.5 A.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "9",
   "name": "Output torque",
   "description": "474 = 47.4 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "10",
   "name": "Output power",
   "description": "1100 = 11.00 kW.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "11",
   "name": "Digital input status",
   "description": "One bit per drive input.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "13",
   "name": "Drive power rating",
   "description": "Power rating in kW; resolution not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "14",
   "name": "Drive voltage rating",
   "description": "Voltage rating; resolution not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "15",
   "name": "I/O firmware",
   "description": "Major x 100 + minor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "16",
   "name": "Power firmware",
   "description": "Major x 100 + minor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "17",
   "name": "Drive type code",
   "description": "Always 0x0330.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "18",
   "name": "Active fault code",
   "description": "Low byte = active fault code, high byte = fault sub-index (0 if none).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "19",
   "name": "Alarm code",
   "description": "One bit per active alarm (see the Alarm Codes topic).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "20",
   "name": "Analog 1 level",
   "description": "1000 = 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "21",
   "name": "Analog 2 level",
   "description": "1000 = 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "22",
   "name": "Pre-ramp speed reference",
   "description": "Internal speed set-point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "23",
   "name": "DC bus voltage",
   "description": "Measured, in volts.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "24",
   "name": "Drive temperature",
   "description": "Heatsink temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "25",
   "name": "Serial number part 1",
   "description": "Registers 25-28 together form the serial number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "26",
   "name": "Serial number part 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "27",
   "name": "Serial number part 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "28",
   "name": "Serial number part 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "29",
   "name": "Digital output status",
   "description": "Bit = 1 when that output is closed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "30",
   "name": "Energy consumption kWh",
   "description": "kWh part of the energy total.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "31",
   "name": "Energy consumption MWh",
   "description": "MWh part of the energy total.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "34",
   "name": "Drive total run time (h)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "35",
   "name": "Drive total run time (m)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "36",
   "name": "Run time since last enable (h)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "37",
   "name": "Run time since last enable (m)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "38",
   "name": "Service time remaining",
   "description": "Time until the next service is due; unit not stated.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "39",
   "name": "Control board temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "48",
   "name": "STO status",
   "description": "1 when both STO1 and STO2 are closed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "101",
   "name": "P1-01 Primary command source",
   "description": "Set 1 for Modbus RTU control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Terminal",
    "1": "Modbus RTU",
    "2": "CANopen"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "201",
   "name": "P2-01 Modbus slave address",
   "description": "0-247, default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "202",
   "name": "P2-02 Modbus RTU baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600 bps",
    "1": "19200 bps",
    "2": "38400 bps",
    "3": "57600 bps",
    "4": "115200 bps (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "203",
   "name": "P2-03 Modbus RTU data format",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity, 1 stop bit (default)",
    "1": "No parity, 2 stop bits",
    "2": "Odd parity, 1 stop bit",
    "3": "Even parity, 1 stop bit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 203,
   "documented": "204",
   "name": "P2-04 Modbus communications loss timeout",
   "description": "0.0-5.0 s, default 1.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "205",
   "name": "P2-05 Communications loss action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Trip (default)",
    "1": "Ramp to stop then trip",
    "2": "Ramp to stop only (no trip)",
    "3": "Run at inspection speed (P8-08)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 205,
   "documented": "206",
   "name": "P2-06 Modbus RTU response delay",
   "description": "Extra characters of delay, 0-16.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 255,
   "documented": "256",
   "name": "P2-56 Modbus status word (byte pair)",
   "description": "High byte = active error code; low byte = extra status bits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "258",
   "name": "P2-58 Modbus motor current",
   "description": "Only active while P1-01 = 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "259",
   "name": "P2-59 Modbus output torque",
   "description": "Only active while P1-01 = 1.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10002,
   "documented": "10003",
   "name": "P0-03 STO status (group 0 read)",
   "description": "Group 0 parameters read at 10000 + parameter number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set P1-01 = 1, close both STO inputs, write the speed to register 2 and then write register 1 = 1 (up/forward) or 2 (reverse). Poll register 6 for status, 7-10 for speed, current, torque and power, and 18 for the fault code.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Control word: run forward/reverse, reset"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Speed reference"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Status word"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Output speed"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Output current, 0.1 A"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Active fault code"
   },
   {
    "table": "holding_register",
    "address": 100,
    "why": "P1-01 command source"
   }
  ],
  "enable": "Set P1-01 = 1 (Modbus RTU). Set the address in P2-01, baud in P2-02 and data format in P2-03. STO1 and STO2 must both be closed (24 V present); no digital input is needed to run.",
  "watchdog": "P2-04 sets the Modbus loss timeout (0.0-5.0 s, default 1.0 s) and P2-05 the reaction: 0 trip (default), 1 ramp to stop then trip, 2 ramp to stop only, 3 run at inspection speed P8-08.",
  "quirks": [
   "Register numbers are 1-based; subtract 1 for the wire address.",
   "Setting both run bits (value 3) stops the drive or keeps it from starting.",
   "Group 0 monitor parameters are read at 10000 + number, and their sub-indexes at 11000 + number x 10 + index."
  ],
  "setup": [
   "RS-485 on the RJ45 port; always connect the 0 V pin.",
   "Factory settings: address 1, 115200 bps, no parity, 1 stop bit. Up to 247 drives per network.",
   "A 120 ohm terminating resistor at the end of the line helps with dropped telegrams."
  ],
  "gotchas": [
   "The drive rejects a speed reference outside the range of P8-01, and ramps still follow the group 8 and 9 S-ramp parameters under Modbus control.",
   "Leaving out the 0 V connection can damage the port."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/invertek-drives/optidrive-elevator-core",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}