 "manufacturer": "INVT",
 "manufacturer_slug": "invt",
 "model": "Goodrive270 (GD270) fan and pump VFD",
 "model_slug": "goodrive270-gd270",
 "short_model": "GD270",
 "aliases": [
  "GD270",
  "Goodrive270",
  "GD270 fan and pump drive",
  "GD270 HVAC drive"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).",
 "summary": "INVT's variable frequency drive built for fans, pumps and HVAC duty, with sleep/wake, frost and dry-pump protection. The built-in RS-485 port speaks Modbus RTU (Modbus TCP and BACnet MS/TP need option cards). Commands and setpoints go to the 2000H block, status and fault words sit at 2100H-2103H, monitors at 3000H onwards, and every function parameter has its own hex address. This map covers that block plus the run-source, P14 serial and fault parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Addresses are printed in hex and go on the wire unchanged. Parameter P00.00 sits at 0000H and the manual's example frames carry the address bytes directly (setting P01.20 is sent as 01 06 01 14 00 32, and the multi-register write example starts at 20 00)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Goodrive270 Series VFD for Fan and Pump Operation Manual",
  "doc_number": "V1.4",
  "revision_date": "2025-07",
  "url": "https://www.invt.com/uploads/file1/20250804/GD270%20Manual_V1.4.pdf",
  "pages": "pp. 178 (P00.06), pp. 226-228 (P07.27 fault list), pp. 267-269 (P14 group), pp. 361-366 (9.4.4-9.4.7)"
 },
 "notes": [
  "Every register is a single 16-bit word; there are no 32-bit values in this map.",
  "Any function parameter can be read or written at (group << 8) | index; only the parameters an integrator needs most are listed here.",
  "3016H (identification code) and 5000H (fault code) are printed without range or unit, so they are left out; 2102H and 2103H carry the same information.",
  "The fault list prints codes 77 and 78 twice (AI2/AI3 disconnection and water pipe breaking / power underload), so those two codes are left out of the value lists.",
  "3011H, 300FH and 3010H (pulse input) are reserved or printed with a mixed kHz/0.01 Hz unit and are left out.",
  "300DH/300EH (AI2/AI3) are left out: the address table prints AI2 as 0.00-10.00 V and AI3 as -10.00-10.00 V, but P17.20 prints AI2 as -10.00-10.00 V and AI3 is a 0-10 V option-card input, so signedness is unclear."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "P00.01 (0001H)",
   "name": "P00.01 Run command channel",
   "description": "Set 2 so run/stop comes from 2000H.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Keypad",
    "1": "Terminal",
    "2": "Communication"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "P00.02 (0002H)",
   "name": "P00.02 Communication run command channel",
   "description": "Which bus carries run commands when P00.01 = 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Modbus/Modbus TCP",
    "1": "PROFIBUS/CANopen/BACnet MSTP",
    "2": "Ethernet",
    "3": "PROFINET/EtherNet IP",
    "4": "Programmable card",
    "5": "Wireless communication card"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "P00.03 (0003H)",
   "name": "P00.03 Max. output frequency",
   "description": "Fmax; ceiling for 2001H.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "P00.06 (0006H)",
   "name": "P00.06 A frequency command channel",
   "description": "Set to the Modbus option so 2001H sets the speed; other values pick local sources.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "8": "Modbus/Modbus TCP communication"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1819,
   "documented": "P07.27 (071BH)",
   "name": "P07.27 Present fault type",
   "description": "Same codes as 2102H.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Inverter unit U-phase protection (OUt1)",
    "2": "Inverter unit V-phase protection (OUt2)",
    "3": "Inverter unit W-phase protection (OUt3)",
    "4": "Overcurrent during acceleration (OC1)",
    "5": "Overcurrent during deceleration (OC2)",
    "6": "Overcurrent during constant speed running (OC3)",
    "7": "Overvoltage during acceleration (OV1)",
    "8": "Overvoltage during deceleration (OV2)",
    "9": "Overvoltage during constant speed running (OV3)",
    "10": "Bus undervoltage fault (UV)",
    "11": "Motor overload (OL1)",
    "12": "VFD overload (OL2)",
    "13": "Phase loss on input side (SPI)",
    "14": "Phase loss on output side (SPO)",
    "15": "Rectifier module overheat (OH1)",
    "16": "Inverter module overheat (OH2)",
    "17": "External fault (EF)",
    "18": "Modbus/Modbus TCP communication fault (CE)",
    "19": "Current detection fault (ItE)",
    "20": "Motor autotuning fault (tE)",
    "21": "EEPROM operation error (EEP)",
    "22": "PID feedback offline fault (PIDE)",
    "23": "Braking unit fault (bCE)",
    "24": "Running time reached (END)",
    "25": "Electronic overload (OL3)",
    "26": "Keypad communication error (PCE)",
    "27": "Parameter upload error (UPE)",
    "28": "Parameter download error (DNE)",
    "29": "PROFIBUS communication fault (E-DP)",
    "30": "Ethernet communication fault (E-NET)",
    "31": "CANopen communication fault (E-CAN)",
    "32": "To-ground short-circuit fault 1 (ETH1)",
    "33": "To-ground short-circuit fault 2 (ETH2)",
    "34": "Speed deviation fault (dEu)",
    "35": "Mal-adjustment fault (STo)",
    "36": "Underload fault (LL)",
    "40": "Safe torque off (STO)",
    "41": "Exception to safety circuit of channel 1 (STL1)",
    "42": "Exception to safety circuit of channel 2 (STL2)",
    "43": "Exception to both channels 1 and 2 (STL3)",
    "55": "Duplicate expansion card type (E-Err)",
    "57": "PROFINET communication fault (E_PN)",
    "58": "CAN communication timeout (ESCAN)",
    "59": "Motor overtemperature fault (OT)",
    "60": "Failure to identify the card in slot 1 (F1-Er)",
    "61": "Failure to identify the card in slot 2 (F2-Er)",
    "63": "Communication timeout of the card in slot 1 (C1-Er)",
    "64": "Communication timeout of the card in slot 2 (C2-Er)",
    "67": "BACnet MSTP communication timeout fault (E-BAC)",
    "68": "DeviceNet communication timeout fault (E-DEV)",
    "69": "CAN slave fault in master/slave synchronization (S-Err)",
    "70": "EtherNet IP communication timeout fault (E-EIP)",
    "71": "Braking pipe overcurrent fault (bOC)",
    "72": "Brake pipe overload (boL)",
    "73": "Frost fault (FrOSt)",
    "74": "Stalling fault (Block)",
    "75": "Dry pumping fault (Dry)",
    "76": "AI1 disconnection (E-AI1)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3584,
   "documented": "P14.00 (0E00H)",
   "name": "P14.00 Local communication address",
   "description": "1-247; 0 is broadcast.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3585,
   "documented": "P14.01 (0E01H)",
   "name": "P14.01 Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1200 bps",
    "1": "2400 bps",
    "2": "4800 bps",
    "3": "9600 bps",
    "4": "19200 bps",
    "5": "38400 bps",
    "6": "57600 bps",
    "7": "115200 bps"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3586,
   "documented": "P14.02 (0E02H)",
   "name": "P14.02 Data bit check",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "N,8,1 RTU",
    "1": "E,8,1 RTU",
    "2": "O,8,1 RTU",
    "3": "N,8,2 RTU",
    "4": "E,8,2 RTU",
    "5": "O,8,2 RTU"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3587,
   "documented": "P14.03 (0E03H)",
   "name": "P14.03 Communication response delay",
   "description": "0-200 ms extra delay before replying.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3588,
   "documented": "P14.04 (0E04H)",
   "name": "P14.04 Communication timeout",
   "description": "0.0 = off; otherwise CE fault after this much bus silence.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3589,
   "documented": "P14.05 (0E05H)",
   "name": "P14.05 Transmission fault processing",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Alarm and coast to stop",
    "1": "Keep running, no alarm",
    "2": "Stop by stop mode, no alarm (communication mode only)",
    "3": "Stop by stop mode, no alarm (any mode)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "2000H",
   "name": "Communication control command",
   "description": "Needs P00.01 = 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Forward running",
    "2": "Reverse running",
    "3": "Forward jogging",
    "4": "Reverse jogging",
    "5": "Stop",
    "6": "Coast to stop",
    "7": "Fault reset",
    "8": "Jogging stop"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "2001H",
   "name": "Communication frequency setting",
   "description": "0 to Fmax.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "2002H",
   "name": "PID reference",
   "description": "0-1000 = 0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8195,
   "documented": "2003H",
   "name": "PID feedback",
   "description": "0-1000 = 0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8196,
   "documented": "2004H",
   "name": "Torque setting",
   "description": "-3000 to 3000; 1000 = 100.0 % of motor rated current.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8197,
   "documented": "2005H",
   "name": "Forward upper frequency limit",
   "description": "0 to Fmax.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8198,
   "documented": "2006H",
   "name": "Reverse upper frequency limit",
   "description": "0 to Fmax.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8199,
   "documented": "2007H",
   "name": "Motoring torque upper limit",
   "description": "0-3000; 1000 = 100.0 % of motor rated current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8200,
   "documented": "2008H",
   "name": "Braking torque upper limit",
   "description": "0-3000; 1000 = 100.0 % of motor rated current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8201,
   "documented": "2009H",
   "name": "Special control command word",
   "description": "Bits 0-1 select the motor (00 = motor 1, 01 = motor 2).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "2": "1 = enable speed/torque control switchover",
    "3": "1 = clear electricity consumption data",
    "4": "1 = enable pre-excitation",
    "5": "1 = enable DC braking"
   }
  },
  {
   "table": "holding_register",
   "address": 8202,
   "documented": "200AH",
   "name": "Virtual input terminal command",
   "description": "Range 0x000-0x3FF; S8/S7/S6/S5/Reserved/HDIA/S4/S3/S2/S1 in the manual's order.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8203,
   "documented": "200BH",
   "name": "Virtual output terminal command",
   "description": "Range 0x00-0x0F; RO2/RO1/Reserved/Y1 in the manual's order.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8204,
   "documented": "200CH",
   "name": "Voltage setting (V/F separation)",
   "description": "0-1000 = 0-100.0 % of motor rated voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8205,
   "documented": "200DH",
   "name": "AO output setting 1",
   "description": "-1000 to 1000 = -100.0 to 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8206,
   "documented": "200EH",
   "name": "AO output setting 2",
   "description": "-1000 to 1000 = -100.0 to 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8448,
   "documented": "2100H",
   "name": "VFD status word 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Forward running",
    "2": "Reverse running",
    "3": "Stopped",
    "4": "VFD in fault",
    "5": "POFF",
    "6": "Pre-exciting"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8449,
   "documented": "2101H",
   "name": "VFD status word 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "1 = ready to run",
    "1": "Motor select bit 0 (00 motor 1, 01 motor 2)",
    "2": "Motor select bit 1",
    "3": "1 = synchronous motor",
    "4": "1 = overload pre-alarm",
    "5": "Control source bit 0 (bits 5-6: 0 keypad, 1 terminal, 2 communication)",
    "6": "Control source bit 1",
    "8": "1 = torque control, 0 = speed control",
    "9": "1 = position control",
    "10": "Control mode bit 0 (bits 10-11: 00 vector 0, 01 vector 1, 10 closed-loop vector, 11 space voltage vector)",
    "11": "Control mode bit 1"
   }
  },
  {
   "table": "holding_register",
   "address": 8450,
   "documented": "2102H",
   "name": "VFD fault code",
   "description": "Codes match P07.27.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Inverter unit U-phase protection (OUt1)",
    "2": "Inverter unit V-phase protection (OUt2)",
    "3": "Inverter unit W-phase protection (OUt3)",
    "4": "Overcurrent during acceleration (OC1)",
    "5": "Overcurrent during deceleration (OC2)",
    "6": "Overcurrent during constant speed running (OC3)",
    "7": "Overvoltage during acceleration (OV1)",
    "8": "Overvoltage during deceleration (OV2)",
    "9": "Overvoltage during constant speed running (OV3)",
    "10": "Bus undervoltage fault (UV)",
    "11": "Motor overload (OL1)",
    "12": "VFD overload (OL2)",
    "13": "Phase loss on input side (SPI)",
    "14": "Phase loss on output side (SPO)",
    "15": "Rectifier module overheat (OH1)",
    "16": "Inverter module overheat (OH2)",
    "17": "External fault (EF)",
    "18": "Modbus/Modbus TCP communication fault (CE)",
    "19": "Current detection fault (ItE)",
    "20": "Motor autotuning fault (tE)",
    "21": "EEPROM operation error (EEP)",
    "22": "PID feedback offline fault (PIDE)",
    "23": "Braking unit fault (bCE)",
    "24": "Running time reached (END)",
    "25": "Electronic overload (OL3)",
    "26": "Keypad communication error (PCE)",
    "27": "Parameter upload error (UPE)",
    "28": "Parameter download error (DNE)",
    "29": "PROFIBUS communication fault (E-DP)",
    "30": "Ethernet communication fault (E-NET)",
    "31": "CANopen communication fault (E-CAN)",
    "32": "To-ground short-circuit fault 1 (ETH1)",
    "33": "To-ground short-circuit fault 2 (ETH2)",
    "34": "Speed deviation fault (dEu)",
    "35": "Mal-adjustment fault (STo)",
    "36": "Underload fault (LL)",
    "40": "Safe torque off (STO)",
    "41": "Exception to safety circuit of channel 1 (STL1)",
    "42": "Exception to safety circuit of channel 2 (STL2)",
    "43": "Exception to both channels 1 and 2 (STL3)",
    "55": "Duplicate expansion card type (E-Err)",
    "57": "PROFINET communication fault (E_PN)",
    "58": "CAN communication timeout (ESCAN)",
    "59": "Motor overtemperature fault (OT)",
    "60": "Failure to identify the card in slot 1 (F1-Er)",
    "61": "Failure to identify the card in slot 2 (F2-Er)",
    "63": "Communication timeout of the card in slot 1 (C1-Er)",
    "64": "Communication timeout of the card in slot 2 (C2-Er)",
    "67": "BACnet MSTP communication timeout fault (E-BAC)",
    "68": "DeviceNet communication timeout fault (E-DEV)",
    "69": "CAN slave fault in master/slave synchronization (S-Err)",
    "70": "EtherNet IP communication timeout fault (E-EIP)",
    "71": "Braking pipe overcurrent fault (bOC)",
    "72": "Brake pipe overload (boL)",
    "73": "Frost fault (FrOSt)",
    "74": "Stalling fault (Block)",
    "75": "Dry pumping fault (Dry)",
    "76": "AI1 disconnection (E-AI1)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8451,
   "documented": "2103H",
   "name": "VFD identification code",
   "description": "0x01C0 = GD270 (high byte 0x01 Goodrive series).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12288,
   "documented": "3000H",
   "name": "Running frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12289,
   "documented": "3001H",
   "name": "Set frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12290,
   "documented": "3002H",
   "name": "Bus voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12291,
   "documented": "3003H",
   "name": "Output voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12292,
   "documented": "3004H",
   "name": "Output current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12293,
   "documented": "3005H",
   "name": "Rotating speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12294,
   "documented": "3006H",
   "name": "Output power",
   "description": "-300.0 to 300.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12295,
   "documented": "3007H",
   "name": "Output torque",
   "description": "-250.0 to 250.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12296,
   "documented": "3008H",
   "name": "Closed-loop setting",
   "description": "-100.0 to 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12297,
   "documented": "3009H",
   "name": "Closed-loop feedback",
   "description": "-100.0 to 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12298,
   "documented": "300AH",
   "name": "Input terminal state",
   "description": "Range 00-3F; terminals Reserved/HDIA/S4/S3/S2/S1 in the manual's order.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12299,
   "documented": "300BH",
   "name": "Output terminal state",
   "description": "Range 00-0F; RO2/RO1/Reserved/Y1 in the manual's order.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12300,
   "documented": "300CH",
   "name": "Analog input 1",
   "description": "0.00-10.00 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12306,
   "documented": "3012H",
   "name": "Current step of multi-step speed",
   "description": "0-15.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12307,
   "documented": "3013H",
   "name": "External length value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12308,
   "documented": "3014H",
   "name": "External count value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12309,
   "documented": "3015H",
   "name": "Torque setting",
   "description": "-300.0 to 300.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Set P00.01 = 2 and P00.02 = 0 so run commands come from Modbus, and P00.06 = 8 so the speed reference does too. Write the frequency to 2001H in 0.01 Hz and a run/stop code to 2000H, then poll 2100H, 2102H and 3000H-3004H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8192,
    "why": "Run / stop / fault reset command"
   },
   {
    "table": "holding_register",
    "address": 8193,
    "why": "Speed reference in 0.01 Hz"
   },
   {
    "table": "holding_register",
    "address": 8448,
    "why": "Running / stopped / fault state"
   },
   {
    "table": "holding_register",
    "address": 8450,
    "why": "Active fault code"
   },
   {
    "table": "holding_register",
    "address": 12288,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 12292,
    "why": "Output current"
   },
   {
    "table": "holding_register",
    "address": 12290,
    "why": "DC bus voltage"
   }
  ],
  "enable": "P00.01 = 2 gives the run command to communication; P00.02 = 0 picks Modbus as that channel. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.",
  "watchdog": "P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.",
  "quirks": [
   "Parameter Pxx.yy sits at hex register (xx << 8) | yy: P14.01 = 0E01H, P07.27 = 071BH.",
   "Setting the top bit of a parameter address (for example 8007H for P00.07) writes RAM only and spares the EEPROM; those aliases cannot be read.",
   "Scaled values follow the decimals printed in the parameter list or address table (one decimal = x10, two decimals = x100), per the manual's fieldbus-scale section. Registers with a negative printed range are typed INT16 here."
  ],
  "setup": [
   "P14.00 slave address (default 1), P14.01 baud (default 4 = 19200 bps), P14.02 format (default 1 = E,8,1 RTU).",
   "Read with function 03H; write with 06H or 10H."
  ],
  "gotchas": [
   "Frequent parameter writes wear the EEPROM; use the RAM alias (address + 8000H) for values that change often.",
   "Some parameters cannot be changed while the drive runs; the drive answers with exception 08H."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/invt/goodrive270-gd270",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}