{
 "manufacturer": "INVT",
 "manufacturer_slug": "invt",
 "model": "Goodrive350 (GD350) high-performance multifunction VFD",
 "model_slug": "goodrive350-gd350",
 "short_model": "GD350",
 "aliases": [
  "GD350",
  "Goodrive350",
  "GD350 series"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "INVT Goodrive350 drives (not GD350A) using the built-in RS-485 Modbus RTU port, per the GD350 manual V1.1 (communication chapter).",
 "summary": "INVT's high-performance vector drive with option slots for fieldbuses, encoders and I/O. The built-in RS-485 port speaks Modbus RTU. Commands and setpoints go to the 2000H block, status and fault words sit at 2100H-2103H, monitors at 3000H onwards, and each function parameter has its own hex address. This map covers that block plus the run-source, P14 serial and fault parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Addresses are printed in hex and go on the wire unchanged. Parameter P00.00 sits at 0000H and the manual's example frames carry the address bytes directly (reading state word 2100H is sent as 01 03 21 00 00 01, and setting P01.20 as 01 06 01 14 00 32)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Goodrive350 Series High-performance Multifunction VFD Operation Manual",
  "doc_number": "V1.1",
  "revision_date": null,
  "url": "https://www.invt.com/uploads/file1/20210729/GD350%20Series%20VFD%20Manual_V1.1.pdf",
  "pages": "P00 group, P07.27 fault list, pp. 200-202 (P14 group), pp. 275-279 (other function addresses, examples)"
 },
 "notes": [
  "Every register is a single 16-bit word; there are no 32-bit values in this map.",
  "Any function parameter can be read or written at (group << 8) | index; only the parameters an integrator needs most are listed here.",
  "3016H (identification code) and 5000H (fault code) are printed without range or unit, so they are left out; 2102H and 2103H carry the same information.",
  "300FH, 3010H (pulse input printed with a mixed kHz/0.01 Hz unit) and 3011H are left out.",
  "P00.02 values other than 0 select option cards; only 0 (Modbus) is listed.",
  "GD350A has its own map in this library; check the drive label.",
  "300DH/300EH (AI2/AI3) are left out: the address table prints AI2 as 0.00-10.00 V and AI3 as -10.00-10.00 V, but P17.20 prints AI2 as -10.00-10.00 V and AI3 is a 0-10 V option-card input, so signedness is unclear."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "P00.01 (0001H)",
   "name": "P00.01 Run command channel",
   "description": "Set 2 so run/stop comes from 2000H.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Keypad",
    "1": "Terminal",
    "2": "Communication"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "P00.02 (0002H)",
   "name": "P00.02 Communication run command channel",
   "description": "Which bus carries run commands when P00.01 = 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Modbus"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "P00.03 (0003H)",
   "name": "P00.03 Max. output frequency",
   "description": "Fmax; ceiling for 2001H.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "P00.06 (0006H)",
   "name": "P00.06 A frequency command channel",
   "description": "Set to the Modbus option so 2001H sets the speed; other values pick local sources.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "8": "Modbus communication"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1819,
   "documented": "P07.27 (071BH)",
   "name": "P07.27 Present fault type",
   "description": "Same codes as 2102H.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Inverter unit U phase protection (OUt1)",
    "2": "Inverter unit V phase protection (OUt2)",
    "3": "Inverter unit W phase protection (OUt3)",
    "4": "Overcurrent during acceleration (OC1)",
    "5": "Overcurrent during deceleration (OC2)",
    "6": "Overcurrent during constant speed (OC3)",
    "7": "Overvoltage during acceleration (OV1)",
    "8": "Overvoltage during deceleration (OV2)",
    "9": "Overvoltage during constant speed (OV3)",
    "10": "Bus undervoltage fault (UV)",
    "11": "Motor overload (OL1)",
    "12": "VFD overload (OL2)",
    "13": "Phase loss on input side (SPI)",
    "14": "Phase loss on output side (SPO)",
    "15": "Rectifier module overheat (OH1)",
    "16": "Inverter module overheat (OH2)",
    "17": "External fault (EF)",
    "18": "485 communication fault (CE)",
    "19": "Current detection fault (ItE)",
    "20": "Motor autotuning fault (tE)",
    "21": "EEPROM operation fault (EEP)",
    "22": "PID feedback offline fault (PIDE)",
    "23": "Braking unit fault (bCE)",
    "24": "Running time reached (END)",
    "25": "Electronic overload (OL3)",
    "26": "Keypad communication error (PCE)",
    "27": "Parameter upload error (UPE)",
    "28": "Parameter download error (DNE)",
    "29": "Profibus DP communication fault (E-DP)",
    "30": "Ethernet communication fault (E-NET)",
    "31": "CANopen communication fault (E-CAN)",
    "32": "To-ground short-circuit fault 1 (ETH1)",
    "33": "To-ground short-circuit fault 2 (ETH2)",
    "34": "Speed deviation fault (dEu)",
    "35": "Mal-adjustment fault (STo)",
    "36": "Underload fault (LL)",
    "37": "Encoder offline fault (ENC1O)",
    "38": "Encoder reversal fault (ENC1D)",
    "39": "Encoder Z pulse offline fault (ENC1Z)",
    "40": "Safe torque off (STO)",
    "41": "Channel H1 safety circuit exception (STL1)",
    "42": "Channel H2 safety circuit exception (STL2)",
    "43": "Channel H1 and H2 exception (STL3)",
    "44": "Safety code FLASH CRC check fault (CrCE)",
    "55": "Repetitive extension card type fault (E-Err)",
    "56": "Encoder UVW loss fault (ENCUV)",
    "57": "PROFINET communication timeout fault (E-PN)",
    "58": "CAN communication fault (SECAN)",
    "59": "Motor over-temperature fault (OT)",
    "60": "Card slot 1 card identification failure (F1-Er)",
    "61": "Card slot 2 card identification failure (F2-Er)",
    "62": "Card slot 3 card identification failure (F3-Er)",
    "63": "Card slot 1 card communication timeout fault (C1-Er)",
    "64": "Card slot 2 card communication timeout fault (C2-Er)",
    "65": "Card slot 3 card communication timeout fault (C3-Er)",
    "66": "EtherCAT communication fault (E-CAT)",
    "67": "Bacnet communication fault (E-BAC)",
    "68": "DeviceNet communication fault (E-DEV)",
    "69": "Master-slave synchronous CAN slave fault (S-Err)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3584,
   "documented": "P14.00 (0E00H)",
   "name": "P14.00 Local communication address",
   "description": "1-247; 0 is broadcast.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3585,
   "documented": "P14.01 (0E01H)",
   "name": "P14.01 Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1200 bps",
    "1": "2400 bps",
    "2": "4800 bps",
    "3": "9600 bps",
    "4": "19200 bps",
    "5": "38400 bps",
    "6": "57600 bps",
    "7": "115200 bps"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3586,
   "documented": "P14.02 (0E02H)",
   "name": "P14.02 Data bit check",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "N,8,1 RTU",
    "1": "E,8,1 RTU",
    "2": "O,8,1 RTU",
    "3": "N,8,2 RTU",
    "4": "E,8,2 RTU",
    "5": "O,8,2 RTU"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3587,
   "documented": "P14.03 (0E03H)",
   "name": "P14.03 Communication response delay",
   "description": "0-200 ms extra delay before replying.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3588,
   "documented": "P14.04 (0E04H)",
   "name": "P14.04 Communication timeout",
   "description": "0.0 = off; otherwise CE fault after this much bus silence.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3589,
   "documented": "P14.05 (0E05H)",
   "name": "P14.05 Transmission fault processing",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Alarm and coast to stop",
    "1": "Keep running, no alarm",
    "2": "Stop by stop mode, no alarm (communication mode only)",
    "3": "Stop by stop mode, no alarm (any mode)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "2000H",
   "name": "Communication control command",
   "description": "Needs P00.01 = 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Forward running",
    "2": "Reverse running",
    "3": "Forward jogging",
    "4": "Reverse jogging",
    "5": "Stop",
    "6": "Coast to stop",
    "7": "Fault reset",
    "8": "Jogging stop"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "2001H",
   "name": "Communication frequency setting",
   "description": "0 to Fmax.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "2002H",
   "name": "PID reference",
   "description": "0-1000 = 0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8195,
   "documented": "2003H",
   "name": "PID feedback",
   "description": "0-1000 = 0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8196,
   "documented": "2004H",
   "name": "Torque setting",
   "description": "-3000 to 3000; 1000 = 100.0 % of motor rated current.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8197,
   "documented": "2005H",
   "name": "Forward upper frequency limit",
   "description": "0 to Fmax.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8198,
   "documented": "2006H",
   "name": "Reverse upper frequency limit",
   "description": "0 to Fmax.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8199,
   "documented": "2007H",
   "name": "Motoring torque upper limit",
   "description": "0-3000; 1000 = 100.0 % of the VFD rated current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8200,
   "documented": "2008H",
   "name": "Braking torque upper limit",
   "description": "0-3000; 1000 = 100.0 % of motor rated current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8201,
   "documented": "2009H",
   "name": "Special control command word",
   "description": "Bits 0-1 select the motor (00 = motor 1, 01 = motor 2, 10 = motor 3, 11 = motor 4).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "2": "1 = torque control disabled",
    "3": "1 = reset power consumption to 0",
    "4": "1 = pre-excitation",
    "5": "1 = DC brake"
   }
  },
  {
   "table": "holding_register",
   "address": 8202,
   "documented": "200AH",
   "name": "Virtual input terminal command",
   "description": "Range 0x000-0x3FF; S8/S7/S6/S5/HDIB/HDIA/S4/S3/S2/S1 in the manual's order.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8203,
   "documented": "200BH",
   "name": "Virtual output terminal command",
   "description": "Range 0x00-0x0F; RO2/RO1/HDO/Y1 in the manual's order.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8204,
   "documented": "200CH",
   "name": "Voltage setting (V/F separation)",
   "description": "0-1000 = 0-100.0 % of motor rated voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8205,
   "documented": "200DH",
   "name": "AO output setting 1",
   "description": "-1000 to 1000 = -100.0 to 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8206,
   "documented": "200EH",
   "name": "AO output setting 2",
   "description": "-1000 to 1000 = -100.0 to 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8448,
   "documented": "2100H",
   "name": "VFD status word 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "Forward running",
    "2": "Reverse running",
    "3": "Stopped",
    "4": "Faulty",
    "5": "POFF",
    "6": "Pre-excited"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8449,
   "documented": "2101H",
   "name": "VFD status word 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "1 = ready to run",
    "1": "Motor select bit 0 (bits 1-2: 00 motor 1 .. 11 motor 4)",
    "2": "Motor select bit 1",
    "3": "1 = synchronous motor, 0 = asynchronous",
    "4": "1 = overload pre-alarm",
    "5": "Control source bit 0 (bits 5-6: 00 keypad, 01 terminal, 10 communication)",
    "6": "Control source bit 1",
    "8": "1 = torque control, 0 = speed control",
    "9": "1 = position control",
    "10": "Control mode bit 0 (bits 10-11: 0 vector 0, 1 vector 1, 2 closed-loop vector, 3 space voltage vector)",
    "11": "Control mode bit 1"
   }
  },
  {
   "table": "holding_register",
   "address": 8450,
   "documented": "2102H",
   "name": "VFD fault code",
   "description": "Codes match P07.27.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Inverter unit U phase protection (OUt1)",
    "2": "Inverter unit V phase protection (OUt2)",
    "3": "Inverter unit W phase protection (OUt3)",
    "4": "Overcurrent during acceleration (OC1)",
    "5": "Overcurrent during deceleration (OC2)",
    "6": "Overcurrent during constant speed (OC3)",
    "7": "Overvoltage during acceleration (OV1)",
    "8": "Overvoltage during deceleration (OV2)",
    "9": "Overvoltage during constant speed (OV3)",
    "10": "Bus undervoltage fault (UV)",
    "11": "Motor overload (OL1)",
    "12": "VFD overload (OL2)",
    "13": "Phase loss on input side (SPI)",
    "14": "Phase loss on output side (SPO)",
    "15": "Rectifier module overheat (OH1)",
    "16": "Inverter module overheat (OH2)",
    "17": "External fault (EF)",
    "18": "485 communication fault (CE)",
    "19": "Current detection fault (ItE)",
    "20": "Motor autotuning fault (tE)",
    "21": "EEPROM operation fault (EEP)",
    "22": "PID feedback offline fault (PIDE)",
    "23": "Braking unit fault (bCE)",
    "24": "Running time reached (END)",
    "25": "Electronic overload (OL3)",
    "26": "Keypad communication error (PCE)",
    "27": "Parameter upload error (UPE)",
    "28": "Parameter download error (DNE)",
    "29": "Profibus DP communication fault (E-DP)",
    "30": "Ethernet communication fault (E-NET)",
    "31": "CANopen communication fault (E-CAN)",
    "32": "To-ground short-circuit fault 1 (ETH1)",
    "33": "To-ground short-circuit fault 2 (ETH2)",
    "34": "Speed deviation fault (dEu)",
    "35": "Mal-adjustment fault (STo)",
    "36": "Underload fault (LL)",
    "37": "Encoder offline fault (ENC1O)",
    "38": "Encoder reversal fault (ENC1D)",
    "39": "Encoder Z pulse offline fault (ENC1Z)",
    "40": "Safe torque off (STO)",
    "41": "Channel H1 safety circuit exception (STL1)",
    "42": "Channel H2 safety circuit exception (STL2)",
    "43": "Channel H1 and H2 exception (STL3)",
    "44": "Safety code FLASH CRC check fault (CrCE)",
    "55": "Repetitive extension card type fault (E-Err)",
    "56": "Encoder UVW loss fault (ENCUV)",
    "57": "PROFINET communication timeout fault (E-PN)",
    "58": "CAN communication fault (SECAN)",
    "59": "Motor over-temperature fault (OT)",
    "60": "Card slot 1 card identification failure (F1-Er)",
    "61": "Card slot 2 card identification failure (F2-Er)",
    "62": "Card slot 3 card identification failure (F3-Er)",
    "63": "Card slot 1 card communication timeout fault (C1-Er)",
    "64": "Card slot 2 card communication timeout fault (C2-Er)",
    "65": "Card slot 3 card communication timeout fault (C3-Er)",
    "66": "EtherCAT communication fault (E-CAT)",
    "67": "Bacnet communication fault (E-BAC)",
    "68": "DeviceNet communication fault (E-DEV)",
    "69": "Master-slave synchronous CAN slave fault (S-Err)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8451,
   "documented": "2103H",
   "name": "VFD identification code",
   "description": "0x01A0 = GD350 (high byte 0x01 Goodrive series).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12288,
   "documented": "3000H",
   "name": "Running frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12289,
   "documented": "3001H",
   "name": "Set frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12290,
   "documented": "3002H",
   "name": "Bus voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12291,
   "documented": "3003H",
   "name": "Output voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12292,
   "documented": "3004H",
   "name": "Output current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12293,
   "documented": "3005H",
   "name": "Rotating speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12294,
   "documented": "3006H",
   "name": "Output power",
   "description": "-300.0 to 300.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12295,
   "documented": "3007H",
   "name": "Output torque",
   "description": "-250.0 to 250.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12296,
   "documented": "3008H",
   "name": "Closed-loop setting",
   "description": "-100.0 to 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12297,
   "documented": "3009H",
   "name": "Closed-loop feedback",
   "description": "-100.0 to 100.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12298,
   "documented": "300AH",
   "name": "Input terminal state",
   "description": "Range 000-3F; HDIB/HDIA/S4/S3/S2/S1 in the manual's order.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12299,
   "documented": "300BH",
   "name": "Output terminal state",
   "description": "Range 000-0F; RO2/RO1/HDO/Y1 in the manual's order.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12300,
   "documented": "300CH",
   "name": "Analog input 1",
   "description": "0.00-10.00 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12306,
   "documented": "3012H",
   "name": "Current step of multi-step speed",
   "description": "0-15.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12307,
   "documented": "3013H",
   "name": "External length value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12308,
   "documented": "3014H",
   "name": "External count value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 12309,
   "documented": "3015H",
   "name": "Torque setting",
   "description": "-300.0 to 300.0 %.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Set P00.01 = 2 and P00.02 = 0 so run commands come from Modbus, and P00.06 = 8 so the speed reference does too. Write the frequency to 2001H in 0.01 Hz and a run/stop code to 2000H, then poll 2100H, 2102H and 3000H-3004H.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8192,
    "why": "Run / stop / fault reset command"
   },
   {
    "table": "holding_register",
    "address": 8193,
    "why": "Speed reference in 0.01 Hz"
   },
   {
    "table": "holding_register",
    "address": 8448,
    "why": "Running / stopped / fault state"
   },
   {
    "table": "holding_register",
    "address": 8450,
    "why": "Active fault code"
   },
   {
    "table": "holding_register",
    "address": 12288,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 12292,
    "why": "Output current"
   },
   {
    "table": "holding_register",
    "address": 12290,
    "why": "DC bus voltage"
   }
  ],
  "enable": "P00.01 = 2 gives the run command to communication; P00.02 = 0 picks Modbus as that channel. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.",
  "watchdog": "P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.",
  "quirks": [
   "Parameter Pxx.yy sits at hex register (xx << 8) | yy: P14.01 = 0E01H, P07.27 = 071BH.",
   "Setting the top bit of a parameter address (for example 8007H for P00.07) writes RAM only and spares the EEPROM; those aliases cannot be read.",
   "Scaled values follow the decimals printed in the parameter list or address table (one decimal = x10, two decimals = x100), per the manual's fieldbus-scale section. Registers with a negative printed range are typed INT16 here."
  ],
  "setup": [
   "P14.00 slave address (default 1), P14.01 baud (default 4 = 19200 bps), P14.02 format (default 1 = E,8,1 RTU).",
   "Read with function 03H; write with 06H or 10H."
  ],
  "gotchas": [
   "Frequent parameter writes wear the EEPROM; use the RAM alias (address + 8000H) for values that change often.",
   "Some parameters cannot be changed while the drive runs; the drive answers with exception 08H."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/invt/goodrive350-gd350",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}
