 "manufacturer": "Janitza",
 "manufacturer_slug": "janitza",
 "model": "UMG 96-S2 energy analyser (serial Modbus)",
 "model_slug": "umg-96-s2",
 "short_model": "UMG 96-S2",
 "aliases": [
  "UMG96-S2",
  "UMG 96 S2",
  "UMG96S2",
  "Janitza UMG96-S2"
 ],
 "equipment_type": "Power meter (energy analyser)",
 "applies_to": "UMG 96-S2 energy analyser, per address list 2.062.026.1.b (10/2019).",
 "summary": "The UMG 96-S2 is an energy analyser with a serial Modbus slave port (baud and framing set by parameters 1 and 2). Values are big-endian 32-bit floats that include the CT/VT ratios. This map covers the 19000-19120 'frequently required readings' block (volts, amps, power, PF, frequency, energy, THD), total power factor, the bus and transformer parameters, the digital output source and the reset commands.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Addresses are printed as the protocol address and sent unchanged: 19000 is requested as 19000. The parameter list starts at address 0 (device address), which only fits 0-based numbering. In a 1-based or Modicon tool enter 19001 / 419001."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Energy Analyser UMG 96-S2 - Modbus-address list and Formulary",
  "doc_number": "2.062.026.1.b",
  "revision_date": "2019-10",
  "url": "https://www.janitza.com/files/download/manuals/current/UMG96-S2/janitza-mal-umg96s2-en.pdf",
  "pages": "Functions p. 4; transfer parameters, byte order, number formats p. 5; frequently required readings pp. 12-13; parameters p. 14; measured values p. 15"
 },
 "notes": [
  "Byte order: the list says its addresses return data big-endian (high byte first, high word in the lower register = ABCD). Adding 32768 to an address returns the same value little-endian; that mirror block is not listed.",
  "Unlike other Janitza lists, 19044-19048 are printed as 'power factor' (not CosPhi), 19068 is the consumed L1-L3 total, and the rotation field 19052 is an int (signed 32-bit) rather than a float.",
  "Transfer parameters (p. 5): 9600, 19200 or 38400 baud, 8 data bits; the page names odd/even parity and 1 or 2 stop bits, while parameter 2 also offers stop-bit-only framing. The list gives no defaults, so defaults are left blank.",
  "Parameter 0 is printed with a range of 0-255 and a footnote mark whose text is not on the page; use 1-247 for a normal Modbus slave address.",
  "Left out: display, averaging-time and threshold parameters, the pulse valence at 102 (range given but no unit beyond 'e.g. imp/kWh'), tariff assignment bits, mean/min/max blocks, tariff energy and the double-type energy copies.",
  "The address list names no physical interface (RS-485) or framing mode (RTU); RTU is assumed from the serial baud/parity parameters. Confirm in the device user manual."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Device address",
   "description": "Modbus device address (printed range 0-255).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Baud rate",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600",
    "1": "19200",
    "2": "38400"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Framing",
   "description": "Stop bits / parity.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1 stop bit",
    "1": "2 stop bits",
    "2": "Even parity",
    "3": "Odd parity"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "CT primary",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "12",
   "name": "CT secondary",
   "description": "1 or 5 A.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "14",
   "name": "VT primary",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "16",
   "name": "VT secondary",
   "description": "100 or 400 V.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "100",
   "name": "Digital output 1 function",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "P (active power)",
    "1": "Q (reactive power)",
    "2": "S (apparent power)",
    "3": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 506,
   "documented": "506",
   "name": "Delete min/max values",
   "description": "Write 1 to clear stored minimum and maximum values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 507,
   "documented": "507",
   "name": "Delete energy",
   "description": "Write 1 to clear the energy counters.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1018,
   "documented": "1018",
   "name": "Power factor total",
   "description": "Psum3 / Ssum3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1038,
   "documented": "1038",
   "name": "CosPhi total",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19000,
   "documented": "19000",
   "name": "Voltage L1-N",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19002,
   "documented": "19002",
   "name": "Voltage L2-N",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19004,
   "documented": "19004",
   "name": "Voltage L3-N",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19006,
   "documented": "19006",
   "name": "Voltage L1-L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19008,
   "documented": "19008",
   "name": "Voltage L2-L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19010,
   "documented": "19010",
   "name": "Voltage L3-L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19012,
   "documented": "19012",
   "name": "Current L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19014,
   "documented": "19014",
   "name": "Current L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19016,
   "documented": "19016",
   "name": "Current L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19018,
   "documented": "19018",
   "name": "Neutral current (vector sum)",
   "description": "Calculated vector sum of the three phase currents.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19020,
   "documented": "19020",
   "name": "Real power L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19022,
   "documented": "19022",
   "name": "Real power L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19024,
   "documented": "19024",
   "name": "Real power L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19026,
   "documented": "19026",
   "name": "Real power total",
   "description": "Sum of L1-L3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19028,
   "documented": "19028",
   "name": "Apparent power L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19030,
   "documented": "19030",
   "name": "Apparent power L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19032,
   "documented": "19032",
   "name": "Apparent power L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19034,
   "documented": "19034",
   "name": "Apparent power total",
   "description": "Sum of L1-L3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19036,
   "documented": "19036",
   "name": "Reactive power L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19038,
   "documented": "19038",
   "name": "Reactive power L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19040,
   "documented": "19040",
   "name": "Reactive power L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19042,
   "documented": "19042",
   "name": "Reactive power total",
   "description": "Sum of L1-L3.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19044,
   "documented": "19044",
   "name": "Power factor L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19046,
   "documented": "19046",
   "name": "Power factor L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19048,
   "documented": "19048",
   "name": "Power factor L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19050,
   "documented": "19050",
   "name": "Frequency",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19052,
   "documented": "19052",
   "name": "Rotation field",
   "description": "Integer here, not float.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Clockwise",
    "0": "None",
    "-1": "Anticlockwise"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19054,
   "documented": "19054",
   "name": "Active energy L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19056,
   "documented": "19056",
   "name": "Active energy L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19058,
   "documented": "19058",
   "name": "Active energy L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19060,
   "documented": "19060",
   "name": "Active energy L1-L3",
   "description": "Three-phase total, not split into consumed and delivered.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19062,
   "documented": "19062",
   "name": "Active energy L1, consumed",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19064,
   "documented": "19064",
   "name": "Active energy L2, consumed",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19066,
   "documented": "19066",
   "name": "Active energy L3, consumed",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19068,
   "documented": "19068",
   "name": "Active energy L1-L3, consumed",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19070,
   "documented": "19070",
   "name": "Active energy L1, delivered",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19072,
   "documented": "19072",
   "name": "Active energy L2, delivered",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19074,
   "documented": "19074",
   "name": "Active energy L3, delivered",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19076,
   "documented": "19076",
   "name": "Active energy L1-L3, delivered",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19084,
   "documented": "19084",
   "name": "Apparent energy L1-L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19092,
   "documented": "19092",
   "name": "Reactive energy L1-L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19100,
   "documented": "19100",
   "name": "Reactive energy inductive L1-L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19108,
   "documented": "19108",
   "name": "Reactive energy capacitive L1-L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19110,
   "documented": "19110",
   "name": "THD voltage L1-N",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19112,
   "documented": "19112",
   "name": "THD voltage L2-N",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19114,
   "documented": "19114",
   "name": "THD voltage L3-N",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19116,
   "documented": "19116",
   "name": "THD current L1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19118,
   "documented": "19118",
   "name": "THD current L2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19120,
   "documented": "19120",
   "name": "THD current L3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers (function 03) from 19000: the block gives volts, amps, power, power factor, frequency, energy and THD as big-endian floats. Set the bus address, baud rate and framing with parameters 0-2.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 19000,
    "why": "Voltage L1-N"
   },
   {
    "table": "holding_register",
    "address": 19012,
    "why": "Current L1"
   },
   {
    "table": "holding_register",
    "address": 19026,
    "why": "Total active power"
   },
   {
    "table": "holding_register",
    "address": 1018,
    "why": "Total power factor"
   },
   {
    "table": "holding_register",
    "address": 19050,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 19068,
    "why": "Consumed active energy total"
   },
   {
    "table": "holding_register",
    "address": 19076,
    "why": "Delivered active energy total"
   }
  ],
  "enable": "Device address, baud rate and framing are parameters 0, 1 and 2, readable and writable over Modbus. The list gives no other enable step.",
  "watchdog": null,
  "quirks": [
   "Addresses are used as printed (0-based).",
   "Floats are ABCD; add 32768 to an address to get the same value little-endian.",
   "Energy is in Wh and varh, not kWh.",
   "19052 rotation field is an INT32, not a float."
  ],
  "setup": [
   "Baud options: 9600, 19200, 38400 (parameter 1).",
   "Set CT and VT ratios (parameters 10-16) so the floats read in primary units.",
   "Write 1 to 507 to clear energy, or to 506 to clear min/max values."
  ],
  "gotchas": [
   "Framing parameter 2 mixes stop-bit and parity choices in one value; match the master to it exactly."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/janitza/umg-96-s2",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}