 "manufacturer": "Johnson Controls",
 "manufacturer_slug": "johnson-controls",
 "model": "GS3000 indoor Modbus carbon monoxide transmitter",
 "model_slug": "gs3000",
 "short_model": "GS3000 CO",
 "aliases": [
  "GS3000",
  "GS3001",
  "24-11484-00021"
 ],
 "equipment_type": "Sensor",
 "applies_to": "Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).",
 "summary": "Wall-mounted electrochemical carbon monoxide transmitter (0-500 ppm) for garages and plant rooms. It is a Modbus RTU subordinate with fixed 9600 8N1 serial settings and a DIP-switch address, and it exposes just two holding registers: sensor status and the CO reading in ppm.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Table 4 lists Modbus address 40001 with offset +0 and 40002 with offset +1, and the example query frames (Figure 11) send start address 0x0000 for status and 0x0001 for CO, so the wire addresses are 0 and 1."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "GS3000 Indoor Modbus Carbon Monoxide Transmitter Installation Guide",
  "doc_number": "24-11484-00021 Rev. --",
  "revision_date": "2020-10-01",
  "url": "https://docs.johnsoncontrols.com/bas/r/Johnson-Controls/en-US/GS3000-Indoor-Modbus-Carbon-Monoxide-Transmitter-Installation-Guide",
  "pages": "p. 3 (network communication, Table 1 DIP address), p. 4 (Tables 2-4 RTU format and register addressing), p. 6 (specifications)"
 },
 "notes": [
  "Source is Johnson Controls' documentation portal; the guide's PDF attachment is 241148400021.pdf.",
  "Both registers are unsigned 16-bit words and read-only. Figure 11 shows both being read with function 03 (Read Holding Registers), one register per request; exception codes 01, 02 and 03 are returned for bad requests.",
  "Serial settings other than the address are fixed at the factory (the guide notes they may be factory-customised)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "CO Sensor Status",
   "description": "0x0000 normal, 0x0001 abnormal status.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Abnormal"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "CO Concentration",
   "description": "Measured carbon monoxide, 0-500 ppm range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set a unique address on the 8-way DIP switch, wire A-/B+/shield, and poll holding registers 0-1 at 9600 8N1: status then CO in ppm.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1,
    "why": "CO level in ppm"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Sensor status (abnormal = fault)"
   }
  ],
  "enable": "Modbus is always on; set the address (1-255) with the DIP switch before connecting to the network.",
  "watchdog": null,
  "quirks": [
   "Address is binary on DIP switches weighted 128-64-32-16-8-4-2-1.",
   "Baud, parity and stop bits are fixed (9600, none, 1)."
  ],
  "setup": [
   "Fit the PCB EOL jumper (121 ohm) only on the devices at each end of the segment.",
   "Use 22 AWG shielded twisted pair; ground the shield at one end; max 4000 ft per segment."
  ],
  "gotchas": [
   "Half-wave power supply: keep the same circuit ground on all devices and the controller.",
   "Allow 30 min warm-up before calibrating."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/johnson-controls/gs3000",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}