 "manufacturer": "Johnson Controls",
 "manufacturer_slug": "johnson-controls",
 "model": "VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)",
 "model_slug": "vfd68",
 "short_model": "VFD68",
 "aliases": [
  "VFD68Bxx",
  "VFD68Cxx",
  "VFD68BDC-2C",
  "VFD68CDF-2C",
  "PENN VFD68"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.",
 "summary": "Compact HVAC drive with a Modbus RTU subordinate on its RJ45 PU port. All data are holding registers: reset and parameter-clear commands, a control/status word, the running-frequency command (0.01 Hz), a real-time monitor block (output frequency, current, voltage, power, load factors, PID values, energy), eight fault-history slots with fault codes, and every parameter P.n at register 41000 + n.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 0,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Registers are listed as 4xxxx. The bulletin states the address in the frame is the register number minus 40001 and shows it in examples (41004 is sent as H03EB = 1003)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "VFD68 Variable Frequency Drives Technical Bulletin",
  "doc_number": "24-7664-3051",
  "revision_date": "2019-08-09",
  "url": "https://docs.johnsoncontrols.com/bas/r/PENN-Controls/en-US/VFD68-Variable-Frequency-Drives-Technical-Bulletin/C",
  "pages": "Appendix 4, printed pp. 93-110 (Table 88 communication parameters, Tables 93-104 frame examples, Tables 124-130 register maps and fault codes)"
 },
 "notes": [
  "Source is Johnson Controls' documentation portal; the bulletin's PDF attachment is 24-7664-3051.pdf.",
  "Scaling comes from the unit column of Table 126 and the worked examples (H1770 = 60.00 Hz written to 40014; P.4-P.6 read as 6000/3000/1000 = 60/30/10 Hz; 0.5 s written to P.7 as 5).",
  "Parameters: register = 41000 + parameter number for P.0-P.999 (C2-C7 calibration values also have 42xxx/43xxx analog-value registers). Only the parameters whose scaling the bulletin shows or that set up communication are listed; see the drive parameter lists for the rest.",
  "Communication defaults from Table 88: P.117 station number 0 (no reply - must be set 1-247), P.118 = 96 (9600 bps), P.120 = 2 (even parity, 1 stop bit), P.549 = 0 (computer link). The VFD68 parameter table (Table 34) instead lists P.549 = 1 (Modbus RTU) as the VFD68 default, so check P.549 on the drive. Communication parameters can only be set when P.160 = 0.",
  "Operation-mode values for 40010 and the control/status bit assignments can change with P.180-P.182 and P.190-P.192; the bits listed are the initial settings.",
  "PID Deviation (40254, 0.1 %) is left out: a deviation can be negative but the bulletin does not say whether the register is signed."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "VFD Reset",
   "description": "Write any value to reset the drive.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Parameter Clear",
   "description": "Write H965A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "All Parameters Clear",
   "description": "Write H965A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Parameter Clear (keeps communication settings)",
   "description": "Write H965A. Communication parameters are not cleared.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "All Parameters Clear (keeps communication settings)",
   "description": "Write H965A. Communication parameters are not cleared.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "40009",
   "name": "VFD Status / Control Input Instruction",
   "description": "Write control bits (Table 125: 1 FWD, 2 REV, 10 MRS ...); read returns status bits.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "RUN (drive running)",
    "1": "Forward rotation",
    "2": "Reverse rotation",
    "3": "SU up to frequency",
    "4": "OL overload",
    "6": "FU frequency detection",
    "7": "ABC fault",
    "15": "Fault occurrence"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "40010",
   "name": "Operation Mode / VFD Setting",
   "description": "Write sets the operation mode; read returns the mode status.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "40014",
   "name": "Running Frequency (RAM)",
   "description": "Frequency command, not stored. 6000 = 60.00 Hz (P.37 can change it to speed).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40015",
   "name": "Running Frequency (EEPROM)",
   "description": "Frequency command stored in EEPROM.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "40201",
   "name": "Output Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 201,
   "documented": "40202",
   "name": "Output Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 202,
   "documented": "40203",
   "name": "Output Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 204,
   "documented": "40205",
   "name": "Frequency Setting",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 207,
   "documented": "40208",
   "name": "Converter Output Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 208,
   "documented": "40209",
   "name": "Regenerative Brake Duty",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 209,
   "documented": "40210",
   "name": "Electronic Thermal Relay Load Factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 210,
   "documented": "40211",
   "name": "Output Current Peak",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 211,
   "documented": "40212",
   "name": "Converter Output Voltage Peak",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 213,
   "documented": "40214",
   "name": "Output Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 214,
   "documented": "40215",
   "name": "Input Terminal Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "STF",
    "1": "STR",
    "4": "RL",
    "5": "RM",
    "6": "RH"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 215,
   "documented": "40216",
   "name": "Output Terminal Status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "RUN",
    "5": "ABC"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 219,
   "documented": "40220",
   "name": "Cumulative Energization Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 222,
   "documented": "40223",
   "name": "Actual Operation Time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 223,
   "documented": "40224",
   "name": "Motor Load Factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 224,
   "documented": "40225",
   "name": "Cumulative Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 251,
   "documented": "40252",
   "name": "PID Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "40253",
   "name": "PID Measured Value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "40261",
   "name": "Motor Thermal Load Factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 261,
   "documented": "40262",
   "name": "VFD Thermal Load Factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 262,
   "documented": "40263",
   "name": "Cumulative Power 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 263,
   "documented": "40264",
   "name": "PTC Thermistor Resistance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kΩ",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "40501",
   "name": "Fault History 1",
   "description": "Fault code in the low byte. Writing any value clears the history.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No fault",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "192": "E.CPU",
    "196": "E.CDO",
    "197": "E.IOH",
    "199": "E.AIE",
    "201": "E.SAF",
    "245": "E.5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 501,
   "documented": "40502",
   "name": "Fault History 2",
   "description": "Fault code in the low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "192": "E.CPU",
    "196": "E.CDO",
    "197": "E.IOH",
    "199": "E.AIE",
    "201": "E.SAF",
    "245": "E.5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 502,
   "documented": "40503",
   "name": "Fault History 3",
   "description": "Fault code in the low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "192": "E.CPU",
    "196": "E.CDO",
    "197": "E.IOH",
    "199": "E.AIE",
    "201": "E.SAF",
    "245": "E.5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 503,
   "documented": "40504",
   "name": "Fault History 4",
   "description": "Fault code in the low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "192": "E.CPU",
    "196": "E.CDO",
    "197": "E.IOH",
    "199": "E.AIE",
    "201": "E.SAF",
    "245": "E.5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 504,
   "documented": "40505",
   "name": "Fault History 5",
   "description": "Fault code in the low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "192": "E.CPU",
    "196": "E.CDO",
    "197": "E.IOH",
    "199": "E.AIE",
    "201": "E.SAF",
    "245": "E.5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 505,
   "documented": "40506",
   "name": "Fault History 6",
   "description": "Fault code in the low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "192": "E.CPU",
    "196": "E.CDO",
    "197": "E.IOH",
    "199": "E.AIE",
    "201": "E.SAF",
    "245": "E.5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 506,
   "documented": "40507",
   "name": "Fault History 7",
   "description": "Fault code in the low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "192": "E.CPU",
    "196": "E.CDO",
    "197": "E.IOH",
    "199": "E.AIE",
    "201": "E.SAF",
    "245": "E.5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 507,
   "documented": "40508",
   "name": "Fault History 8",
   "description": "Fault code in the low byte.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "16": "E.OC1",
    "17": "E.OC2",
    "18": "E.OC3",
    "32": "E.OV1",
    "33": "E.OV2",
    "34": "E.OV3",
    "48": "E.THT",
    "49": "E.THM",
    "64": "E.FIN",
    "82": "E.ILF",
    "96": "E.OLT",
    "112": "E.BE",
    "128": "E.GF",
    "129": "E.LF",
    "144": "E.OHT",
    "145": "E.PTC",
    "176": "E.PE",
    "177": "E.PUE",
    "178": "E.RET",
    "192": "E.CPU",
    "196": "E.CDO",
    "197": "E.IOH",
    "199": "E.AIE",
    "201": "E.SAF",
    "245": "E.5"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1003,
   "documented": "41004",
   "name": "P.4 High speed",
   "description": "Multi-speed RH setting; manual example reads 6000 = 60.00 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "41005",
   "name": "P.5 Middle speed",
   "description": "Multi-speed RM setting; example 3000 = 30.00 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1005,
   "documented": "41006",
   "name": "P.6 Low speed",
   "description": "Multi-speed RL setting; example 1000 = 10.00 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1006,
   "documented": "41007",
   "name": "P.7 Acceleration time",
   "description": "Parameter P.7; example writes 5 = 0.5 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1007,
   "documented": "41008",
   "name": "P.8 Deceleration time",
   "description": "Parameter P.8; example writes 10 = 1 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1116,
   "documented": "41117",
   "name": "P.117 PU communication station number",
   "description": "0 = no reply; 1-247 station number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1117,
   "documented": "41118",
   "name": "P.118 PU communication speed",
   "description": "Value x 100 = bit/s (48, 96, 192, 384).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1119,
   "documented": "41120",
   "name": "P.120 PU communication parity check",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity, 2 stop bits",
    "1": "Odd parity, 1 stop bit",
    "2": "Even parity, 1 stop bit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1342,
   "documented": "41343",
   "name": "P.343 Communication error count",
   "description": "Communication errors since power-up (read only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1501,
   "documented": "41502",
   "name": "P.502 Stop mode selection at communication error",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Coast to stop (E.PUE)",
    "1": "Decelerate to stop, then E.PUE",
    "2": "Decelerate to stop, E.PUE shown, no fault output"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1548,
   "documented": "41549",
   "name": "P.549 Protocol selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "VFD computer link protocol",
    "1": "Modbus RTU"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set P.549 = 1 (Modbus RTU), a station number in P.117 and the speed/parity in P.118/P.120, then use function 03/06/16 on 4xxxx holding registers: command the drive with 40009 (bit 1 forward, bit 2 reverse) and 40014 (0.01 Hz), and monitor 40201-40214 and 40501.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8,
    "why": "Run command (write) / drive status (read)"
   },
   {
    "table": "holding_register",
    "address": 13,
    "why": "Frequency command in 0.01 Hz"
   },
   {
    "table": "holding_register",
    "address": 200,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 201,
    "why": "Output current"
   },
   {
    "table": "holding_register",
    "address": 213,
    "why": "Output power"
   },
   {
    "table": "holding_register",
    "address": 500,
    "why": "Latest fault code"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Fault reset"
   }
  ],
  "enable": "On the operation panel set P.549 = 1 (Modbus RTU) and P.117 = 1-247 (0 means the drive never replies), then P.118/P.120 for speed and parity; these parameters can only be set when P.160 = 0.",
  "watchdog": "P.122 (PU communication check time interval: 0, 0.1-999.8 s or 9999, default 9999; the bulletin does not explain the 0 and 9999 settings) and P.502 (stop mode at communication error: coast with E.PUE, decelerate then E.PUE, or decelerate with E.PUE shown but no fault output).",
  "quirks": [
   "Register numbers are 4xxxx; subtract 40001 for the PDU address.",
   "Default station number 0 means broadcast-only: the drive will not answer until P.117 is set.",
   "Parity and stop bits are linked: no parity forces 2 stop bits, odd/even use 1.",
   "Writing to 40014 changes the RAM value only; 40015 writes the frequency to EEPROM."
  ],
  "setup": [
   "RJ45 PU port pins (Table 87): 1 and 7 SG (ground), 3 RDA, 4 SDB, 5 SDA, 6 RDB. Do not connect pins 2 and 8 (drive power supply).",
   "Speeds 4800/9600/19200/38400 bps, 8 data bits, up to 32 drives per segment."
  ],
  "gotchas": [
   "Supported function codes are 03, 06, 08, 16 and 70 (H46 access log).",
   "Reading a non-existent register in a block returns 0 instead of an error unless every register in the block is invalid."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/johnson-controls/vfd68",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}