KATHREIN KATHREIN Wallbox (Modbus TCP server) Modbus register map

Updated 19 November 2026

Short answer

KATHREIN wallboxes include a Modbus TCP server, disabled at the factory, that lets an energy manager read the charger state and set the charging current. This map covers the identity strings, device info and phase mapping, the UTC timestamp, the EVSE, error, PP and CP states, relay state, granted current and power, session duration and energy, and the EMS control block with its timeout fallback.

This page lists 22 Modbus registers for the KATHREIN KATHREIN Wallbox (Modbus TCP server) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KATHREIN’s own free documentation (linked below) and checked against it.

Manufacturer
KATHREIN
Model
KATHREIN Wallbox (Modbus TCP server)
Equipment type
EV charger
Registers
22 (6 writable)
Transport
Modbus TCP
Default unit ID
0
TCP port
502
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Source document
KATHREIN-Wallbox - ModBus-Server - Register-Mapping · Release Version 1.1 · rev. 2024-09-09 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: KATHREIN KATHREIN Wallbox (Modbus TCP server)

Integration in brief

Enable the Modbus server in easyOperate, write 0x8000 to 0x00A0 to take EMS control, then write the charging current in mA to 0x00A2 (0 pauses). Read 0x0060 for state, 0x0066 for granted power and 0x0069 for session energy.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 160EMS-Control: Control-RegisterUINT16Enable EMS controlRead/write
HR 162EMS-Control: Setpoint Charging CurrentUINT16Charging current setpoint (mA)Read/write
HR 163EMS-Control: Timeout PeriodUINT16Setpoint timeoutRead/write
HR 165EMS-Control: Timeout Fallback CurrentUINT16Fallback current after timeoutRead/write
HR 96EVSE: StatusUINT16EVSE statusRead
HR 97EVSE: Error-StateBITMAP16Error flagsRead
HR 102EVSE: Granted PowerUINT16Granted powerRead
HR 105Charging: EnergyUINT32 ABCDSession energyRead

Enable Modbus control & writes

The Modbus server is switched on or off in the easyOperate configuration panel; it is disabled by factory default. EMS control itself is enabled by writing 0x8000 to 0x00A0.

Communication loss & watchdog

If 0x00A3 is set above 0, each setpoint write restarts a timer of that many seconds; when it runs out the wallbox charges with the fallback current in 0x00A5 (default 6000 mA) on the lines in 0x00A4. The default 0 disables the timeout.

Byte order & addressing

Network setup

Watch out for

KATHREIN KATHREIN Wallbox (Modbus TCP server) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

22 of 22 shown
KATHREIN KATHREIN Wallbox (Modbus TCP server) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0x0000Header: Mapping-VersionVersion of this register mapping (currently 0x0001).UINT16Read
HR1doc 0x0001Device: NumberArticle number text, format 620xxxxx(-yyyy).STRING[16]Read
HR9doc 0x0009Device: TypeType text, format ACxx(E).STRING[16]Read
HR17doc 0x0011Device: SerialSerial number text, format G0Rxxxxxxx.STRING[16]Read
HR25doc 0x0019Device: InfoPower class, cable or socket, calibration-law version and relay capability.BITMAP16Readbit 0 = Power class bit 0 (0x0001 = 11 kW, 3 x 16 A); bit 1 = Power class bit 1 (0x0002 = 22 kW, 3 x 32 A); bit 4 = 0 = cable, 1 = socket (plug); bit 7 = 0 = standard, 1 = Eichrecht; bit 8 = Relay capability: L1 only; bit 9 = Relay capability: L2 only; bit 10 = Relay capability: L3 only; bit 12 = Relay capability: L1 and L2; bit 13 = Relay capability: L1 and L3; bit 14 = Relay capability: L2 and L3; bit 15 = Relay capability: L1, L2 and L3
HR26doc 0x001ADevice: Line-MappingPhase rotation the wallbox is wired with.UINT16Read0 = L1-L2-L3 (default); 1 = L1-L3-L2 (invalid phase rotation); 2 = L2-L3-L1; 3 = L2-L1-L3 (invalid phase rotation); 4 = L3-L1-L2; 5 = L3-L2-L1 (invalid phase rotation)
HR27doc 0x001BDevice: Timestamp (UTC)Unix time: seconds since 1970-01-01 00:00:00 UTC.UINT64ABCDsRead
HR96doc 0x0060EVSE: StatusCharging session state.UINT16Read0 = Idle; 1 = EV Connected; 2 = Authentication Waiting; 3 = Authentication Confirmed; 4 = Charging Active; 5 = Charging Paused; 6 = Charging Completed; 7 = RFID-Pairing; 65535 = Error
HR97doc 0x0061EVSE: Error-StateActive fault flags; 0 = no error.BITMAP16Readbit 0 = Relay welded; bit 1 = Residual DC current detected (RCD); bit 2 = Socket lock detection; bit 3 = Charging overcurrent; bit 4 = CP-D: ventilation not available; bit 5 = CP-E: short circuit CP-PE; bit 6 = CP-F: loop broken CP-PE; bit 7 = PP error (short circuit); bit 15 = Internal error
HR98doc 0x0062EVSE: PP-StatePlug version: cable rating from the PP resistor in amps; fixed-cable version reads 0.UINT16Read0 = Cable not connected (socket version) / fixed cable mounted (cable version); 13 = 13 A (1500 ohm); 20 = 20 A (680 ohm); 32 = 32 A (220 ohm); 63 = 63 A (100 ohm); 65535 = Error (invalid PP resistor)
HR99doc 0x0063EVSE: CP-StateControl pilot state; other values mean undefined or error.UINT16Read0 = A (EV not detected, standby); 1 = B (EV detected); 2 = C (EV charging); 3 = D (EV charging with fan); 4 = E (CP short circuit); 5 = F (EVSE not available, CP = -12 VDC)
HR100doc 0x0064EVSE: Relais-StateWhich line relays are closed; 0 = all off.BITMAP16Readbit 0 = Relay L1 activated; bit 1 = Relay L2 activated; bit 2 = Relay L3 activated
HR101doc 0x0065EVSE: Granted CurrentCurrent per line signalled on the CP: 0 or 6000-32000 mA.UINT16mARead
HR102doc 0x0066EVSE: Granted PowerPower allowed over all active lines per the CP signal (1380-22080 W at 230 V).UINT16WRead
HR103doc 0x0067Charging: DurationDuration of the charging session.UINT32ABCDsRead
HR105doc 0x0069Charging: EnergyEnergy delivered in the charging session.UINT32ABCDWhRead
HR160doc 0x00A0EMS-Control: Control-RegisterWrite 0x8000 to hand control to the energy manager; default 0x0000 (off).UINT16Read/write0 = EMS control disabled (default); 32768 = Enable EMS control
HR161doc 0x00A1EMS-Control: Setpoint Relais-MatrixLines used with the current setpoint; L2 and L3 marked reserved for future. Default 0x0007.BITMAP16Read/writebit 0 = Line 1; bit 1 = Line 2 (reserved for future); bit 2 = Line 3 (reserved for future)
HR162doc 0x00A2EMS-Control: Setpoint Charging Current0 pauses, 6000-32000 mA charges, 0xFFFF cancels; default = power-class maximum.UINT16mARead/write0 = Charging paused; 65535 = Charging cancel
HR163doc 0x00A3EMS-Control: Timeout Period0 = timeout off (default); each setpoint write restarts the timer.UINT16sRead/write
HR164doc 0x00A4EMS-Control: Timeout Fallback PatternLines used after a timeout; default 0x0007 (3 lines).BITMAP16Read/writebit 0 = Line 1; bit 1 = Line 2; bit 2 = Line 3
HR165doc 0x00A5EMS-Control: Timeout Fallback CurrentCurrent applied after a timeout: 0 or 6000-32000 mA, default 6000.UINT16mARead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the KATHREIN KATHREIN Wallbox (Modbus TCP server)

What Modbus registers does the KATHREIN KATHREIN Wallbox (Modbus TCP server) have?

This map lists 22 registers: 22 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the KATHREIN KATHREIN Wallbox (Modbus TCP server) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and go on the wire unchanged. The table starts with register 0x0000 (mapping version), which cannot exist in 1-based numbering, so the printed numbers are protocol addresses: 0x00A2 is requested as 162 decimal.

What byte order does the KATHREIN KATHREIN Wallbox (Modbus TCP server) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the KATHREIN KATHREIN Wallbox (Modbus TCP server)?

Start with HR 160 EMS-Control: Control-Register (Enable EMS control); HR 162 EMS-Control: Setpoint Charging Current (Charging current setpoint (mA)); HR 163 EMS-Control: Timeout Period (Setpoint timeout); HR 165 EMS-Control: Timeout Fallback Current (Fallback current after timeout); HR 96 EVSE: Status (EVSE status); HR 97 EVSE: Error-State (Error flags); HR 102 EVSE: Granted Power (Granted power); HR 105 Charging: Energy (Session energy).

How do I enable Modbus control of the KATHREIN KATHREIN Wallbox (Modbus TCP server)?

The Modbus server is switched on or off in the easyOperate configuration panel; it is disabled by factory default. EMS control itself is enabled by writing 0x8000 to 0x00A0.

What happens when the KATHREIN KATHREIN Wallbox (Modbus TCP server) loses Modbus communication?

If 0x00A3 is set above 0, each setpoint write restarts a timer of that many seconds; when it runs out the wallbox charges with the fallback current in 0x00A5 (default 6000 mA) on the lines in 0x00A4. The default 0 disables the timeout.

Where is the official KATHREIN KATHREIN Wallbox (Modbus TCP server) Modbus documentation?

The source is KATHREIN-Wallbox - ModBus-Server - Register-Mapping (Release Version 1.1), revision 2024-09-09. KATHREIN doesn't publish it on its own website, so this map was re-typed from a free copy at https://community.symcon.de/uploads/short-url/cy0QLy5VdPIfO0xxbqwA4czIcnt.pdf. It may be an older revision, so check it against the live unit.

Source: KATHREIN-Wallbox - ModBus-Server - Register-Mapping · Release Version 1.1 · rev. 2024-09-09 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.