 "manufacturer": "KEBA",
 "manufacturer_slug": "keba",
 "model": "KeContact E10 smart energy meter (Modbus)",
 "model_slug": "kecontact-e10",
 "short_model": "KeContact E10",
 "aliases": [
  "E10",
  "KEBA E10",
  "KeContact E10"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "KEBA KeContact E10 energy meter (companion meter for KeContact wallboxes and PV home systems), register list v1.00 (03.2024).",
 "summary": "The KeContact E10 is KEBA's three-phase smart energy meter for home energy management with its wallboxes. It answers Modbus with holding registers only: instantaneous power, current, voltage, power factor and frequency, 64-bit energy counters per phase, a fast block for current/voltage/power, a plug-and-play identity block, a SunSpec common + meter (203) model, and a few configuration, identify and restart registers.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The list gives start addresses, not register numbers: the first block starts at address 0 and the SunSpec block at 40000. The sheet itself warns that SunSpec register 40001 is read at address 40000."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "KeContact E10 - Modbus Register List",
  "doc_number": "132941/00 v1.00",
  "revision_date": "2024-03",
  "url": "https://www.keba.com/download/x/052f09a75c/e10_modbus_register_list_v100.xlsx",
  "pages": "XLSX sheet 'E10 Modbus Register List' (all blocks) and sheet 'Description' (multi-register order, scaling examples)"
 },
 "notes": [
  "Multi-register values are most significant word first: the description sheet says the lower address holds the most significant bits and gives a uint32 example (0x0023 then 0x0044). 64-bit energy counters follow the same rule.",
  "Engineering values: power in 0.1 W/var/VA steps, current and voltage in 0.001 A/V, power factor in 0.001, frequency in 0.001 Hz, energy in 0.1 Wh/varh/VAh.",
  "SunSpec values use scale-factor registers that KEBA says can change at run time; always read the scale factor with the value.",
  "All data is read with function 03 (read holding registers); configuration registers accept 06 and 16.",
  "Static IP and subnet mask take one octet per register (4 registers each); network changes take effect after a restart (61615).",
  "In the SunSpec block the list shows 0x8000 (SunSpec 'not implemented') for total current 40072 and the average voltages 40077/40081, 0x8000 for the reactive-energy scale factor 40174, and 0 for the var-hour quadrant counters; use the per-phase values and the native energy counters instead.",
  "Reading an address that is not in the list returns exception 02. Reserved gaps are not listed.",
  "Bus settings other than the baud-rate code (register 258) are not given in the list, so defaults are left empty."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Active power+",
   "description": "OBIS 1-0:1.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Active power-",
   "description": "OBIS 1-0:2.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Reactive power+",
   "description": "OBIS 1-0:3.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Reactive power-",
   "description": "OBIS 1-0:4.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "16",
   "name": "Apparent power+",
   "description": "OBIS 1-0:9.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "18",
   "name": "Apparent power-",
   "description": "OBIS 1-0:10.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "24",
   "name": "Power factor",
   "description": "OBIS 1-0:13.4.0*255.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "26",
   "name": "Supply frequency",
   "description": "OBIS 1-0:14.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40",
   "name": "Active power+ (L1)",
   "description": "OBIS 1-0:21.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "42",
   "name": "Active power- (L1)",
   "description": "OBIS 1-0:22.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "44",
   "name": "Reactive power+ (L1)",
   "description": "OBIS 1-0:23.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "46",
   "name": "Reactive power- (L1)",
   "description": "OBIS 1-0:24.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "56",
   "name": "Apparent power+ (L1)",
   "description": "OBIS 1-0:29.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "58",
   "name": "Apparent power- (L1)",
   "description": "OBIS 1-0:30.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "60",
   "name": "Current (L1)",
   "description": "OBIS 1-0:31.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "62",
   "name": "Voltage (L1)",
   "description": "OBIS 1-0:32.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "64",
   "name": "Power factor (L1)",
   "description": "OBIS 1-0:33.4.0*255.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "80",
   "name": "Active power+ (L2)",
   "description": "OBIS 1-0:41.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "82",
   "name": "Active power- (L2)",
   "description": "OBIS 1-0:42.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "84",
   "name": "Reactive power+ (L2)",
   "description": "OBIS 1-0:43.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "86",
   "name": "Reactive power- (L2)",
   "description": "OBIS 1-0:44.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "96",
   "name": "Apparent power+ (L2)",
   "description": "OBIS 1-0:49.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "98",
   "name": "Apparent power- (L2)",
   "description": "OBIS 1-0:50.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "100",
   "name": "Current (L2)",
   "description": "OBIS 1-0:51.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "102",
   "name": "Voltage (L2)",
   "description": "OBIS 1-0:52.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "104",
   "name": "Power factor (L2)",
   "description": "OBIS 1-0:53.4.0*255.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "120",
   "name": "Active power+ (L3)",
   "description": "OBIS 1-0:61.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "122",
   "name": "Active power- (L3)",
   "description": "OBIS 1-0:62.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "124",
   "name": "Reactive power+ (L3)",
   "description": "OBIS 1-0:63.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "126",
   "name": "Reactive power- (L3)",
   "description": "OBIS 1-0:64.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "136",
   "name": "Apparent power+ (L3)",
   "description": "OBIS 1-0:69.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 138,
   "documented": "138",
   "name": "Apparent power- (L3)",
   "description": "OBIS 1-0:70.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "140",
   "name": "Current (L3)",
   "description": "OBIS 1-0:71.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "142",
   "name": "Voltage (L3)",
   "description": "OBIS 1-0:72.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 144,
   "documented": "144",
   "name": "Power factor (L3)",
   "description": "OBIS 1-0:73.4.0*255.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 146,
   "documented": "146",
   "name": "Minimum active power+ * 3",
   "description": "Three times the minimum active power+ (as named in the list).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "256",
   "name": "Measuring Interval",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "20 ms",
    "1": "100 ms",
    "2": "200 ms",
    "3": "500 ms",
    "4": "1000 ms"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 257,
   "documented": "257",
   "name": "Current transformer type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "XH-SCT-10",
    "1": "XH-SCT-16",
    "2": "XH-SCT-24",
    "3": "EB103"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 258,
   "documented": "258",
   "name": "Modbus RTU baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600 Bd",
    "1": "14400 Bd",
    "2": "19200 Bd",
    "3": "38400 Bd",
    "4": "57600 Bd",
    "5": "115200 Bd"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 259,
   "documented": "259",
   "name": "Static IP Address octet 1",
   "description": "One octet per register; active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "260",
   "name": "Static IP Address octet 2",
   "description": "One octet per register; active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 261,
   "documented": "261",
   "name": "Static IP Address octet 3",
   "description": "One octet per register; active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 262,
   "documented": "262",
   "name": "Static IP Address octet 4",
   "description": "One octet per register; active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 263,
   "documented": "263",
   "name": "Subnet Mask octet 1",
   "description": "One octet per register; active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 264,
   "documented": "264",
   "name": "Subnet Mask octet 2",
   "description": "One octet per register; active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 265,
   "documented": "265",
   "name": "Subnet Mask octet 3",
   "description": "One octet per register; active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 266,
   "documented": "266",
   "name": "Subnet Mask octet 4",
   "description": "One octet per register; active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 267,
   "documented": "267",
   "name": "DHCP on/off",
   "description": "Active after restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable DHCP",
    "1": "Enable DHCP"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 268,
   "documented": "268",
   "name": "Activate Read Only",
   "description": "Write 1 to lock all configuration and restart registers.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "512",
   "name": "Active energy+",
   "description": "OBIS 1-0:1.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 516,
   "documented": "516",
   "name": "Active energy-",
   "description": "OBIS 1-0:2.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 520,
   "documented": "520",
   "name": "Reactive energy+",
   "description": "OBIS 1-0:3.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 524,
   "documented": "524",
   "name": "Reactive energy-",
   "description": "OBIS 1-0:4.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 544,
   "documented": "544",
   "name": "Apparent energy+",
   "description": "OBIS 1-0:9.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 548,
   "documented": "548",
   "name": "Apparent energy-",
   "description": "OBIS 1-0:10.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 592,
   "documented": "592",
   "name": "Active energy+ (L1)",
   "description": "OBIS 1-0:21.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 596,
   "documented": "596",
   "name": "Active energy- (L1)",
   "description": "OBIS 1-0:22.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 600,
   "documented": "600",
   "name": "Reactive energy+ (L1)",
   "description": "OBIS 1-0:23.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 604,
   "documented": "604",
   "name": "Reactive energy- (L1)",
   "description": "OBIS 1-0:24.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 624,
   "documented": "624",
   "name": "Apparent energy+ (L1)",
   "description": "OBIS 1-0:29.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 628,
   "documented": "628",
   "name": "Apparent energy- (L1)",
   "description": "OBIS 1-0:30.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 672,
   "documented": "672",
   "name": "Active energy+ (L2)",
   "description": "OBIS 1-0:41.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 676,
   "documented": "676",
   "name": "Active energy- (L2)",
   "description": "OBIS 1-0:42.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 680,
   "documented": "680",
   "name": "Reactive energy+ (L2)",
   "description": "OBIS 1-0:43.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 684,
   "documented": "684",
   "name": "Reactive energy- (L2)",
   "description": "OBIS 1-0:44.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 704,
   "documented": "704",
   "name": "Apparent energy+ (L2)",
   "description": "OBIS 1-0:49.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 708,
   "documented": "708",
   "name": "Apparent energy- (L2)",
   "description": "OBIS 1-0:50.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 752,
   "documented": "752",
   "name": "Active energy+ (L3)",
   "description": "OBIS 1-0:61.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 756,
   "documented": "756",
   "name": "Active energy- (L3)",
   "description": "OBIS 1-0:62.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 760,
   "documented": "760",
   "name": "Reactive energy+ (L3)",
   "description": "OBIS 1-0:63.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 764,
   "documented": "764",
   "name": "Reactive energy- (L3)",
   "description": "OBIS 1-0:64.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 784,
   "documented": "784",
   "name": "Apparent energy+ (L3)",
   "description": "OBIS 1-0:69.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 788,
   "documented": "788",
   "name": "Apparent energy- (L3)",
   "description": "OBIS 1-0:70.8.0*255.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "8192",
   "name": "ManufacturerID",
   "description": "Fixed value 0x5233.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "8193",
   "name": "ProductID",
   "description": "Hardware type code (SU103/SU106 variants).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "1": "SU103 R",
    "2": "SU103 L",
    "3": "SU103 LR",
    "17": "SU106 R",
    "18": "SU106 L",
    "19": "SU106 LR"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "8194",
   "name": "ProductVersion",
   "description": "Hardware revision, e.g. 0x0103 = 1.3.x.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8195,
   "documented": "8195",
   "name": "FirmwareVersion",
   "description": "Firmware revision, e.g. 0x0103 = 1.3.x.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8196,
   "documented": "8196",
   "name": "VendorName",
   "description": "32 characters, NUL padded.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8212,
   "documented": "8212",
   "name": "ProductName",
   "description": "32 characters, NUL padded.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8228,
   "documented": "8228",
   "name": "SerialNumber",
   "description": "32 characters, NUL padded.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8244,
   "documented": "8244",
   "name": "MeasuringInterval",
   "description": "Measuring interval in ms.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 8245,
   "documented": "8245",
   "name": "SubSwVersion",
   "description": "Patch level and release-candidate number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40000,
   "documented": "40000",
   "name": "C_SunSpec_ID",
   "description": "0x53756E53 ('SunS') marks a SunSpec map.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40002,
   "documented": "40002",
   "name": "C_SunSpec_DID",
   "description": "Common model: ID 1, length 66.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40003,
   "documented": "40003",
   "name": "C_SunSpec_Length",
   "description": "Common model: ID 1, length 66.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40004,
   "documented": "40004",
   "name": "C_Manufacturer",
   "description": "SunSpec common model text; 16 registers.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40020,
   "documented": "40020",
   "name": "C_Model",
   "description": "SunSpec common model text; 16 registers.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40036,
   "documented": "40036",
   "name": "C_Options",
   "description": "SunSpec common model text; 8 registers.",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40044,
   "documented": "40044",
   "name": "C_Version",
   "description": "SunSpec common model text; 8 registers.",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40052,
   "documented": "40052",
   "name": "C_SerialNumber",
   "description": "SunSpec common model text; 16 registers.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40068,
   "documented": "40068",
   "name": "C_DeviceAddress",
   "description": "Modbus unit ID.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40070,
   "documented": "40070",
   "name": "C_SunSpec_DID",
   "description": "Meter model ID 203.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40071,
   "documented": "40071",
   "name": "C_SunSpec_Length",
   "description": "Meter model length 105.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40072,
   "documented": "40072",
   "name": "M_AC_Current",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40076
   },
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40073,
   "documented": "40073",
   "name": "M_AC_Current_A",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40076
   },
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40074,
   "documented": "40074",
   "name": "M_AC_Current_B",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40076
   },
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40075,
   "documented": "40075",
   "name": "M_AC_Current_C",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40076
   },
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40076,
   "documented": "40076",
   "name": "M_AC_Current_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40077,
   "documented": "40077",
   "name": "M_AC_Voltage_LN",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40085
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40078,
   "documented": "40078",
   "name": "M_AC_Voltage_AN",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40085
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40079,
   "documented": "40079",
   "name": "M_AC_Voltage_BN",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40085
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40080,
   "documented": "40080",
   "name": "M_AC_Voltage_CN",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40085
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40081,
   "documented": "40081",
   "name": "M_AC_Voltage_LL",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40085
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40082,
   "documented": "40082",
   "name": "M_AC_Voltage_AB",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40085
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40083,
   "documented": "40083",
   "name": "M_AC_Voltage_BC",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40085
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40084,
   "documented": "40084",
   "name": "M_AC_Voltage_CA",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40085
   },
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40085,
   "documented": "40085",
   "name": "M_AC_Voltage_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40086,
   "documented": "40086",
   "name": "M_AC_Freq",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40087
   },
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40087,
   "documented": "40087",
   "name": "M_AC_Freq_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40088,
   "documented": "40088",
   "name": "M_AC_Power",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40092
   },
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40089,
   "documented": "40089",
   "name": "M_AC_Power_A",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40092
   },
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40090,
   "documented": "40090",
   "name": "M_AC_Power_B",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40092
   },
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40091,
   "documented": "40091",
   "name": "M_AC_Power_C",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40092
   },
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40092,
   "documented": "40092",
   "name": "M_AC_Power_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40093,
   "documented": "40093",
   "name": "M_AC_VA",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40097
   },
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40094,
   "documented": "40094",
   "name": "M_AC_VA_A",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40097
   },
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40095,
   "documented": "40095",
   "name": "M_AC_VA_B",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40097
   },
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40096,
   "documented": "40096",
   "name": "M_AC_VA_C",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40097
   },
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40097,
   "documented": "40097",
   "name": "M_AC_VA_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40098,
   "documented": "40098",
   "name": "M_AC_VAR",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40102
   },
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40099,
   "documented": "40099",
   "name": "M_AC_VAR_A",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40102
   },
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40100,
   "documented": "40100",
   "name": "M_AC_VAR_B",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40102
   },
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40101,
   "documented": "40101",
   "name": "M_AC_VAR_C",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40102
   },
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40102,
   "documented": "40102",
   "name": "M_AC_VAR_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40103,
   "documented": "40103",
   "name": "M_AC_PF",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40107
   },
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40104,
   "documented": "40104",
   "name": "M_AC_PF_A",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40107
   },
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40105,
   "documented": "40105",
   "name": "M_AC_PF_B",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40107
   },
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40106,
   "documented": "40106",
   "name": "M_AC_PF_C",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40107
   },
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40107,
   "documented": "40107",
   "name": "M_AC_PF_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40108,
   "documented": "40108",
   "name": "M_Exported",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40124
   },
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40110,
   "documented": "40110",
   "name": "M_Exported_A",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40124
   },
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40112,
   "documented": "40112",
   "name": "M_Exported_B",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40124
   },
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40114,
   "documented": "40114",
   "name": "M_Exported_C",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40124
   },
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40116,
   "documented": "40116",
   "name": "M_Imported",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40124
   },
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40118,
   "documented": "40118",
   "name": "M_Imported_A",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40124
   },
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40120,
   "documented": "40120",
   "name": "M_Imported_B",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40124
   },
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40122,
   "documented": "40122",
   "name": "M_Imported_C",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40124
   },
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40124,
   "documented": "40124",
   "name": "M_Energy_W_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40125,
   "documented": "40125",
   "name": "M_Exported_VA",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40141
   },
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40127,
   "documented": "40127",
   "name": "M_Exported_VA_A",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40141
   },
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40129,
   "documented": "40129",
   "name": "M_Exported_VA_B",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40141
   },
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40131,
   "documented": "40131",
   "name": "M_Exported_VA_C",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40141
   },
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40133,
   "documented": "40133",
   "name": "M_Imported_VA",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40141
   },
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40135,
   "documented": "40135",
   "name": "M_Imported_VA_A",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40141
   },
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40137,
   "documented": "40137",
   "name": "M_Imported_VA_B",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40141
   },
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40139,
   "documented": "40139",
   "name": "M_Imported_VA_C",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40141
   },
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40141,
   "documented": "40141",
   "name": "M_Energy_VA_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40142,
   "documented": "40142",
   "name": "M_Import_VARh_Q1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40144,
   "documented": "40144",
   "name": "M_Import_VARh_Q1A",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40146,
   "documented": "40146",
   "name": "M_Import_VARh_Q1B",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40148,
   "documented": "40148",
   "name": "M_Import_VARh_Q1C",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40150,
   "documented": "40150",
   "name": "M_Import_VARh_Q2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40152,
   "documented": "40152",
   "name": "M_Import_VARh_Q2A",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40154,
   "documented": "40154",
   "name": "M_Import_VARh_Q2B",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40156,
   "documented": "40156",
   "name": "M_Import_VARh_Q2C",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40158,
   "documented": "40158",
   "name": "M_Export_VARh_Q3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40160,
   "documented": "40160",
   "name": "M_Export_VARh_Q3A",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40162,
   "documented": "40162",
   "name": "M_Export_VARh_Q3B",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40164,
   "documented": "40164",
   "name": "M_Export_VARh_Q3C",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40166,
   "documented": "40166",
   "name": "M_Export_VARh_Q4",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40168,
   "documented": "40168",
   "name": "M_Export_VARh_Q4A",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40170,
   "documented": "40170",
   "name": "M_Export_VARh_Q4B",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40172,
   "documented": "40172",
   "name": "M_Export_VARh_Q4C",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": {
    "table": "holding_register",
    "address": 40174
   },
   "units": "VARh",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40174,
   "documented": "40174",
   "name": "M_Energy_VAR_SF",
   "description": "Power-of-ten scale factor for the related values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40175,
   "documented": "40175",
   "name": "M_Events",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40177,
   "documented": "40177",
   "name": "C_SunSpec_DID",
   "description": "End model marker (0xFFFF, length 0).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 40178,
   "documented": "40178",
   "name": "C_SunSpec_Length",
   "description": "End model marker (0xFFFF, length 0).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61440,
   "documented": "61440",
   "name": "Active power+ (L1) (fast block)",
   "description": "OBIS 1-0:21.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61442,
   "documented": "61442",
   "name": "Active power- (L1) (fast block)",
   "description": "OBIS 1-0:22.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61444,
   "documented": "61444",
   "name": "Current (L1) (fast block)",
   "description": "OBIS 1-0:31.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61446,
   "documented": "61446",
   "name": "Voltage (L1) (fast block)",
   "description": "OBIS 1-0:32.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61448,
   "documented": "61448",
   "name": "Active power+ (L2) (fast block)",
   "description": "OBIS 1-0:41.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61450,
   "documented": "61450",
   "name": "Active power- (L2) (fast block)",
   "description": "OBIS 1-0:42.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61452,
   "documented": "61452",
   "name": "Current (L2) (fast block)",
   "description": "OBIS 1-0:51.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61454,
   "documented": "61454",
   "name": "Voltage (L2) (fast block)",
   "description": "OBIS 1-0:52.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61456,
   "documented": "61456",
   "name": "Active power+ (L3) (fast block)",
   "description": "OBIS 1-0:61.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61458,
   "documented": "61458",
   "name": "Active power- (L3) (fast block)",
   "description": "OBIS 1-0:62.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61460,
   "documented": "61460",
   "name": "Current (L3) (fast block)",
   "description": "OBIS 1-0:71.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61462,
   "documented": "61462",
   "name": "Voltage (L3) (fast block)",
   "description": "OBIS 1-0:72.4.0*255.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61464,
   "documented": "61464",
   "name": "Number of measurements (fast block)",
   "description": "Count of measurements taken.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61613,
   "documented": "61613",
   "name": "Identify: blink frequency",
   "description": "100-10000 mHz, default 1000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "mHz",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61614,
   "documented": "61614",
   "name": "Identify: blink duration",
   "description": "Non-zero starts the identify blink, 0 stops it (0-600 s).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61615,
   "documented": "61615",
   "name": "Restart",
   "description": "Write 0x1 to restart the meter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 61616,
   "documented": "61616",
   "name": "Start bootloader",
   "description": "Write 0xA0B1 to start the bootloader.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read the 64-bit energy counters at 512 (import) and 516 (export) and the per-phase power/current/voltage block 0-147, or use the SunSpec meter model at 40070 if your system speaks SunSpec. All values are big-endian, high word first.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Active power import (total)"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Active power export (total)"
   },
   {
    "table": "holding_register",
    "address": 60,
    "why": "Current L1"
   },
   {
    "table": "holding_register",
    "address": 62,
    "why": "Voltage L1"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 512,
    "why": "Active energy import"
   },
   {
    "table": "holding_register",
    "address": 516,
    "why": "Active energy export"
   }
  ],
  "enable": "Modbus RTU baud rate is set in register 258 (0 = 9600 ... 5 = 115200). IP address, subnet mask and DHCP are in registers 259-267 and take effect after a restart.",
  "watchdog": null,
  "quirks": [
   "Read all registers of a multi-register value in one request.",
   "Writing 1 to register 268 locks all configuration and the restart register; plan the configuration first."
  ],
  "setup": [
   "Registers 61613/61614 make the meter blink for identification on site."
  ],
  "gotchas": [
   "Power values are split into + (import) and - (export) registers, both unsigned, rather than one signed value."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/keba/kecontact-e10",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}