 "manufacturer": "KOSTAL",
 "manufacturer_slug": "kostal",
 "model": "KOSTAL Smart Energy Meter (KSEM G1 / G2)",
 "model_slug": "smart-energy-meter-ksem",
 "short_model": "KSEM",
 "aliases": [
  "KSEM",
  "KSEM G1",
  "KSEM G2",
  "KOSTAL Smart Energy Meter"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "KOSTAL Smart Energy Meter generation 1 and 2, firmware 2.6.0 (interface description dated 13.03.2025); OBIS-coded internal registers only.",
 "summary": "The KSEM is a three-phase energy meter and energy manager. As a Modbus RTU slave (RS485 A/B) or Modbus TCP slave (port 502, TLS on 802) it exposes OBIS-coded power and energy registers, a plug-and-play identification block and a SunSpec meter block. This map covers the internal instantaneous values (0-145), the 64-bit energy counters (512-791) and the identification block (8192-8249).",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "0-based",
  "note": "The register tables give decimal and hex addresses that are used directly on the wire: the manual's own example reads active power+ from holding registers 0 and 1 and energy from registers 512-515."
 },
 "default_word_order": "ABCD",
 "firmware": "KSEM software 2.6.0",
 "source": {
  "title": "KSEM G1/G2 KOSTAL Smart Energy Meter - Interface Description MODBUS",
  "doc_number": "DOC02348405-0007",
  "revision_date": "2025-03-13",
  "url": "https://www.kostal-solar-electric.com/fileadmin/downloadcenter/kse/BA_KOSTAL_Interface_KSEM_EN.pdf",
  "pages": "PDF pp. 9-10 (register layout and word order example), pp. 13-16 (sections 3.1-3.4 tables)"
 },
 "notes": [
  "Word order is stated in section 2.2: in a multi-register value the lower address holds the most significant bits, and the worked examples combine register 0 x 2^16 + register 1 and registers 512-515 most significant first.",
  "Each import/export quantity is split into a '+' and a '-' register, both unsigned; net power = (+) minus (-).",
  "The SunSpec block at 40000-40177, the static/dynamic E-mobility and energy-flow areas, group registers and sensor registers are not included in this file.",
  "Register 146 ('Minimum active power+ * 3', no OBIS code) and the MAC address at 8250-8252 (outside the stated PnP range) are left out.",
  "Reading an address not listed in the tables returns exception 0x02 (illegal data address); request each multi-register value in a single read."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Active power+",
   "description": "OBIS 1-0:1.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Active power-",
   "description": "OBIS 1-0:2.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Reactive power+",
   "description": "OBIS 1-0:3.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Reactive power-",
   "description": "OBIS 1-0:4.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "16",
   "name": "Apparent power+",
   "description": "OBIS 1-0:9.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "18",
   "name": "Apparent power-",
   "description": "OBIS 1-0:10.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "24",
   "name": "Power factor",
   "description": "OBIS 1-0:13.4.0*255",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "26",
   "name": "Supply frequency",
   "description": "OBIS 1-0:14.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40",
   "name": "Active power+ (L1)",
   "description": "OBIS 1-0:21.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "42",
   "name": "Active power- (L1)",
   "description": "OBIS 1-0:22.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "44",
   "name": "Reactive power+ (L1)",
   "description": "OBIS 1-0:23.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "46",
   "name": "Reactive power- (L1)",
   "description": "OBIS 1-0:24.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "56",
   "name": "Apparent power+ (L1)",
   "description": "OBIS 1-0:29.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "58",
   "name": "Apparent power- (L1)",
   "description": "OBIS 1-0:30.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "60",
   "name": "Current (L1)",
   "description": "OBIS 1-0:31.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "62",
   "name": "Voltage (L1)",
   "description": "OBIS 1-0:32.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "64",
   "name": "Power factor (L1)",
   "description": "OBIS 1-0:33.4.0*255",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "80",
   "name": "Active power+ (L2)",
   "description": "OBIS 1-0:41.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "82",
   "name": "Active power- (L2)",
   "description": "OBIS 1-0:42.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "84",
   "name": "Reactive power+ (L2)",
   "description": "OBIS 1-0:43.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 86,
   "documented": "86",
   "name": "Reactive power- (L2)",
   "description": "OBIS 1-0:44.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "96",
   "name": "Apparent power+ (L2)",
   "description": "OBIS 1-0:49.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "98",
   "name": "Apparent power- (L2)",
   "description": "OBIS 1-0:50.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "100",
   "name": "Current (L2)",
   "description": "OBIS 1-0:51.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "102",
   "name": "Voltage (L2)",
   "description": "OBIS 1-0:52.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "104",
   "name": "Power factor (L2)",
   "description": "OBIS 1-0:53.4.0*255",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "120",
   "name": "Active power+ (L3)",
   "description": "OBIS 1-0:61.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 122,
   "documented": "122",
   "name": "Active power- (L3)",
   "description": "OBIS 1-0:62.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 124,
   "documented": "124",
   "name": "Reactive power+ (L3)",
   "description": "OBIS 1-0:63.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 126,
   "documented": "126",
   "name": "Reactive power- (L3)",
   "description": "OBIS 1-0:64.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 136,
   "documented": "136",
   "name": "Apparent power+ (L3)",
   "description": "OBIS 1-0:69.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 138,
   "documented": "138",
   "name": "Apparent power- (L3)",
   "description": "OBIS 1-0:70.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "140",
   "name": "Current (L3)",
   "description": "OBIS 1-0:71.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "142",
   "name": "Voltage (L3)",
   "description": "OBIS 1-0:72.4.0*255",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 144,
   "documented": "144",
   "name": "Power factor (L3)",
   "description": "OBIS 1-0:73.4.0*255",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "512",
   "name": "Active energy+",
   "description": "OBIS 1-0:1.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 516,
   "documented": "516",
   "name": "Active energy-",
   "description": "OBIS 1-0:2.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 520,
   "documented": "520",
   "name": "Reactive energy+",
   "description": "OBIS 1-0:3.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 524,
   "documented": "524",
   "name": "Reactive energy-",
   "description": "OBIS 1-0:4.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 544,
   "documented": "544",
   "name": "Apparent energy+",
   "description": "OBIS 1-0:9.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 548,
   "documented": "548",
   "name": "Apparent energy-",
   "description": "OBIS 1-0:10.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 592,
   "documented": "592",
   "name": "Active energy+ (L1)",
   "description": "OBIS 1-0:21.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 596,
   "documented": "596",
   "name": "Active energy- (L1)",
   "description": "OBIS 1-0:22.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 600,
   "documented": "600",
   "name": "Reactive energy+ (L1)",
   "description": "OBIS 1-0:23.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 604,
   "documented": "604",
   "name": "Reactive energy- (L1)",
   "description": "OBIS 1-0:24.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 624,
   "documented": "624",
   "name": "Apparent energy+ (L1)",
   "description": "OBIS 1-0:29.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 628,
   "documented": "628",
   "name": "Apparent energy- (L1)",
   "description": "OBIS 1-0:30.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 672,
   "documented": "672",
   "name": "Active energy+ (L2)",
   "description": "OBIS 1-0:41.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 676,
   "documented": "676",
   "name": "Active energy- (L2)",
   "description": "OBIS 1-0:42.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 680,
   "documented": "680",
   "name": "Reactive energy+ (L2)",
   "description": "OBIS 1-0:43.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 684,
   "documented": "684",
   "name": "Reactive energy- (L2)",
   "description": "OBIS 1-0:44.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 704,
   "documented": "704",
   "name": "Apparent energy+ (L2)",
   "description": "OBIS 1-0:49.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 708,
   "documented": "708",
   "name": "Apparent energy- (L2)",
   "description": "OBIS 1-0:50.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 752,
   "documented": "752",
   "name": "Active energy+ (L3)",
   "description": "OBIS 1-0:61.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 756,
   "documented": "756",
   "name": "Active energy- (L3)",
   "description": "OBIS 1-0:62.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 760,
   "documented": "760",
   "name": "Reactive energy+ (L3)",
   "description": "OBIS 1-0:63.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 764,
   "documented": "764",
   "name": "Reactive energy- (L3)",
   "description": "OBIS 1-0:64.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 784,
   "documented": "784",
   "name": "Apparent energy+ (L3)",
   "description": "OBIS 1-0:69.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 788,
   "documented": "788",
   "name": "Apparent energy- (L3)",
   "description": "OBIS 1-0:70.8.0*255",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "8192",
   "name": "ManufacturerID",
   "description": "Fixed TQ maker ID, reads 0x5233.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "8193",
   "name": "ProductID",
   "description": "Hardware type of the meter.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "18498": "HW v1 (0x4842)",
    "18514": "HW v2 (0x4852)",
    "18530": "HW v3 (0x4862)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "8194",
   "name": "ProductVersion",
   "description": "Hardware revision of the processor board.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8195,
   "documented": "8195",
   "name": "FirmwareVersion",
   "description": "Firmware revision, e.g. 0x0103 = 1.3.x.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8196,
   "documented": "8196",
   "name": "VendorName",
   "description": "Vendor name, NUL padded.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8212,
   "documented": "8212",
   "name": "ProductName",
   "description": "Product name, NUL padded.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8228,
   "documented": "8228",
   "name": "SerialNumber",
   "description": "Serial number, NUL padded.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8244,
   "documented": "8244",
   "name": "MeasuringInterval",
   "description": "Measuring interval of the metering chip.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8245,
   "documented": "8245",
   "name": "UNIXTimestamp",
   "description": "Current UNIX time in milliseconds.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8249,
   "documented": "8249",
   "name": "ModbusSpecVersion",
   "description": "Version of the Modbus specification in use.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Turn on the Modbus TCP slave in the KSEM web UI and poll the listed blocks of holding registers 0-145 for live values and 512-791 for 64-bit energy counters, high word first, splitting reads at the gaps. Net grid power is Active power+ minus Active power-.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Active power import (0.1 W)"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Active power export (0.1 W)"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Grid frequency"
   },
   {
    "table": "holding_register",
    "address": 62,
    "why": "Voltage L1"
   },
   {
    "table": "holding_register",
    "address": 60,
    "why": "Current L1"
   },
   {
    "table": "holding_register",
    "address": 512,
    "why": "Imported active energy (0.1 Wh)"
   },
   {
    "table": "holding_register",
    "address": 516,
    "why": "Exported active energy (0.1 Wh)"
   },
   {
    "table": "holding_register",
    "address": 8228,
    "why": "Serial number for identification"
   }
  ],
  "enable": "In the KSEM web interface open the Modbus settings and activate the TCP slave (and optionally TLS), or set RS485 A or B to Modbus RTU slave; save the settings before polling.",
  "watchdog": null,
  "quirks": [
   "Values are unsigned with separate + and - registers instead of one signed value, except power factor (int32).",
   "With TLS enabled the slave only answers on port 802, not 502.",
   "64-bit energy counters must be read as all four registers in one request."
  ],
  "setup": [
   "Default TCP port 502; encrypted Modbus on port 802.",
   "A self-signed TLS client certificate must be accepted in the KSEM certificate list before reads are allowed."
  ],
  "gotchas": [
   "Reading across a gap between listed registers returns exception 0x02, so split polls at the gaps (e.g. 0-7, 16-27, 40-47)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/kostal/smart-energy-meter-ksem",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}