 "manufacturer": "KROHNE",
 "manufacturer_slug": "krohne",
 "model": "IFC 070 signal converter (Modbus)",
 "model_slug": "ifc-070",
 "short_model": "IFC 070",
 "aliases": [
  "WATERFLUX 3070",
  "IFC070",
  "IFC 070 FlexPower"
 ],
 "equipment_type": "Sensor (battery-powered electromagnetic water flowmeter)",
 "applies_to": "IFC 070 electronic revision 5.1.0, Modbus version 1.1.1 (battery) and 1.1.0 (FlexPower), per AD IFC 070 Modbus R02.",
 "summary": "The IFC 070 is KROHNE's battery-powered electromagnetic water meter converter, with an optional mains (FlexPower) supply and an RS-485 Modbus RTU add-on. Flow, totalizers, pressure and temperature are offered three times: as doubles, floats and integers. This map covers the double and float banks, the integer litre counters, alarms, coil commands and the Modbus settings.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The tables list the Modbus protocol (data) address, which goes on the wire unchanged: flow speed at 3000 is requested as 3000. In a 1-based or Modicon tool add 1 (3001 / 43001)."
 },
 "default_word_order": "ABCD",
 "firmware": "Electronic revision 5.1.0; Modbus 1.1.1 (battery) / 1.1.0 (FlexPower)",
 "source": {
  "title": "IFC 070 Supplementary Instructions - Battery powered electromagnetic water meter with optional FlexPower",
  "doc_number": "4005415902 - AD IFC 070 Modbus R02 en",
  "revision_date": "2022-05",
  "url": "https://core.instrumart.com/assets/krohne-ifc-070-v3-signal-converter-supplementary-instructions.pdf",
  "unofficial": true,
  "pages": "technical data p. 4; local configuration p. 6; addressing and functions p. 9; coils pp. 10-12; registers pp. 13-19; Modbus settings p. 25; system information p. 26; diagnostics p. 27; data encoding p. 31"
 },
 "notes": [
  "This copy is hosted by the distributor Instrumart; it is KROHNE document 4005415902 (AD IFC 070 Modbus R02).",
  "Word order: the data-format setting (8004) offers little endian, big endian (default) and two mixed-endian modes, and the data encoding page says the most significant byte of any multi-byte quantity is sent first. In the default big-endian mode, 32- and 64-bit values are therefore ABCD (highest word first). If the data format is changed, the order changes too.",
  "The register banks can be read with function 03 or 04 and written with 16; coils with 01/02 and 05. The register section says every address can be read with any function code, so the coil addresses also read as unsigned integers.",
  "Left out: integer-format flow speed (5000), pressure (5014), temperature (5016, 5032) and battery capacity (5026/5028), because the manual gives no scaling for these integer values; the measurement-settings block 6000-6027, whose printed layout is too jumbled to tie each code to its address; and the string/array identity registers other than the serial numbers.",
  "Settings registers marked R/W* only accept writes after unlocking with the access-control register 9998 and with the special write option enabled; changes are held until 'Apply changes' (coil 1002).",
  "To save battery the Modbus interface can be switched off when mains power is lost (default off) and can be set to listen only at a reception interval."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 1000,
   "documented": "1000",
   "name": "Restart device",
   "description": "Write 1 to restart.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1001,
   "documented": "1001",
   "name": "Reset errors",
   "description": "Write 1 to clear errors.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1002,
   "documented": "1002",
   "name": "Apply changes",
   "description": "Write 1 to commit pending setting changes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1003,
   "documented": "1003",
   "name": "Discard changes",
   "description": "Write 1 to drop pending setting changes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1004,
   "documented": "1004",
   "name": "Load factory defaults",
   "description": "Write 1; needs Supervisor login.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2000,
   "documented": "2000",
   "name": "Flow measurement warning/error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2001,
   "documented": "2001",
   "name": "Battery low (<10 % left)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2002,
   "documented": "2002",
   "name": "Pressure measurement warning/error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2003,
   "documented": "2003",
   "name": "Temperature measurement warning/error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2004,
   "documented": "2004",
   "name": "EEPROM error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2005,
   "documented": "2005",
   "name": "Empty pipe",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2006,
   "documented": "2006",
   "name": "Add-on to main board communication error",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2007,
   "documented": "2007",
   "name": "Pressure above maximum alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2008,
   "documented": "2008",
   "name": "Pressure below minimum alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2009,
   "documented": "2009",
   "name": "Temperature above maximum alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2010,
   "documented": "2010",
   "name": "Temperature below minimum alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2011,
   "documented": "2011",
   "name": "Flow direction",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Forward flow",
    "1": "Reverse flow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2500,
   "documented": "2500",
   "name": "Counter 1 run",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Running"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2501,
   "documented": "2501",
   "name": "Counter 2 run",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stopped",
    "1": "Running"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2502,
   "documented": "2502",
   "name": "Reset counter 1",
   "description": "Write 1 to reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2503,
   "documented": "2503",
   "name": "Reset counter 2",
   "description": "Write 1 to reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3000,
   "documented": "3000",
   "name": "Flow speed",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3004,
   "documented": "3004",
   "name": "Volume flow",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3008,
   "documented": "3008",
   "name": "Counter 1",
   "description": "Can be read or preset.",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3012,
   "documented": "3012",
   "name": "Counter 2",
   "description": "Can be read or preset.",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3016,
   "documented": "3016",
   "name": "Total volume counter",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3020,
   "documented": "3020",
   "name": "Forward volume counter",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3024,
   "documented": "3024",
   "name": "Reverse volume counter",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3028,
   "documented": "3028",
   "name": "Pressure",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "mbar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3032,
   "documented": "3032",
   "name": "Temperature",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3036,
   "documented": "3036",
   "name": "Pressure alarm state",
   "description": "Reading acknowledges the alarm.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Minimum alarm active",
    "1": "Maximum alarm active",
    "2": "Unread old minimum alarm",
    "3": "Unread old maximum alarm",
    "4": "Sensor measurement error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3040,
   "documented": "3040",
   "name": "Temperature alarm state",
   "description": "Reading acknowledges the alarm.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Minimum alarm active",
    "1": "Maximum alarm active",
    "2": "Unread old minimum alarm",
    "3": "Unread old maximum alarm",
    "4": "Sensor measurement error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3044,
   "documented": "3044",
   "name": "Error/warning states",
   "description": "",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Flow measurement warning",
    "1": "Battery below 10 %",
    "2": "EEPROM error",
    "3": "Communication error",
    "4": "Empty pipe",
    "5": "Mains power failure"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3048,
   "documented": "3048",
   "name": "Battery type",
   "description": "",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None (mains supply)",
    "1": "Internal 1 battery",
    "2": "Internal 2 battery",
    "3": "External battery pack"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3052,
   "documented": "3052",
   "name": "Battery capacity",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3056,
   "documented": "3056",
   "name": "Battery remaining",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3060,
   "documented": "3060",
   "name": "Flow direction",
   "description": "",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Forward flow",
    "1": "Reverse flow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3064,
   "documented": "3064",
   "name": "Pressure",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3068,
   "documented": "3068",
   "name": "Temperature",
   "description": "",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4000,
   "documented": "4000",
   "name": "Flow speed (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4002,
   "documented": "4002",
   "name": "Volume flow (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4004,
   "documented": "4004",
   "name": "Counter 1 (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4006,
   "documented": "4006",
   "name": "Counter 2 (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4008,
   "documented": "4008",
   "name": "Total volume counter (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4010,
   "documented": "4010",
   "name": "Forward volume counter (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4012,
   "documented": "4012",
   "name": "Reverse volume counter (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4014,
   "documented": "4014",
   "name": "Pressure (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "mbar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4016,
   "documented": "4016",
   "name": "Temperature (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4018,
   "documented": "4018",
   "name": "Pressure alarm state (32-bit)",
   "description": "Reading acknowledges the alarm.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Minimum alarm active",
    "1": "Maximum alarm active",
    "2": "Unread old minimum alarm",
    "3": "Unread old maximum alarm",
    "4": "Sensor measurement error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4020,
   "documented": "4020",
   "name": "Temperature alarm state (32-bit)",
   "description": "Reading acknowledges the alarm.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Minimum alarm active",
    "1": "Maximum alarm active",
    "2": "Unread old minimum alarm",
    "3": "Unread old maximum alarm",
    "4": "Sensor measurement error"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4022,
   "documented": "4022",
   "name": "Error/warning states (32-bit)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Flow measurement warning",
    "1": "Battery below 10 %",
    "2": "EEPROM error",
    "3": "Communication error",
    "4": "Empty pipe",
    "5": "Mains power failure"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4024,
   "documented": "4024",
   "name": "Battery type (32-bit)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None (mains supply)",
    "1": "Internal 1 battery",
    "2": "Internal 2 battery",
    "3": "External battery pack"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4026,
   "documented": "4026",
   "name": "Battery capacity (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4028,
   "documented": "4028",
   "name": "Battery remaining (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4030,
   "documented": "4030",
   "name": "Flow direction (32-bit)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Forward flow",
    "1": "Reverse flow"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4032,
   "documented": "4032",
   "name": "Pressure (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4034,
   "documented": "4034",
   "name": "Temperature (float)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5002,
   "documented": "5002",
   "name": "Volume flow (integer)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "l/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5004,
   "documented": "5004",
   "name": "Counter 1 (integer)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "l",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5006,
   "documented": "5006",
   "name": "Counter 2 (integer)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "l",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5008,
   "documented": "5008",
   "name": "Total volume counter (integer)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "l",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5010,
   "documented": "5010",
   "name": "Forward volume counter (integer)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "l",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5012,
   "documented": "5012",
   "name": "Reverse volume counter (integer)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "l",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8000,
   "documented": "8000",
   "name": "Baud rate",
   "description": "1200 to 115200; default 9600. Write needs unlocked access.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "baud",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8002,
   "documented": "8002",
   "name": "Slave address",
   "description": "Write needs unlocked access.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8003,
   "documented": "8003",
   "name": "Parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even (default)",
    "1": "Odd",
    "2": "None"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8004,
   "documented": "8004",
   "name": "Data format",
   "description": "Byte/word order of multi-register values.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Little endian",
    "1": "Big endian (default)",
    "2": "Mixed, little-endian words",
    "3": "Mixed, big-endian words"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8005,
   "documented": "8005",
   "name": "Transmission delay",
   "description": "Allowed: 0, 5, 10, 20, 30, 40, 50.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8006,
   "documented": "8006",
   "name": "Stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1 stop bit",
    "2": "2 stop bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8007,
   "documented": "8007",
   "name": "Modbus when mains power lost",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Modbus off (default)",
    "1": "Modbus on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8008,
   "documented": "8008",
   "name": "Reception interval",
   "description": "0-3600; listen window period for battery saving.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8499,
   "documented": "8499",
   "name": "Uncommitted setting changes",
   "description": "Count of changes waiting for Apply.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8512,
   "documented": "8512",
   "name": "Converter serial number",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8524,
   "documented": "8524",
   "name": "System serial number",
   "description": "",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8532,
   "documented": "8532",
   "name": "Sensor serial number",
   "description": "",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8548,
   "documented": "8548",
   "name": "Converter software version",
   "description": "",
   "data_type": "STRING",
   "length": 2,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9902,
   "documented": "9902",
   "name": "Bus message count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9903,
   "documented": "9903",
   "name": "Bus communication error count",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read the double bank 3000-3071 or the float bank 4000-4035 in one request each. Keep the data format at big endian so multi-register values decode high word first.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 4002,
    "why": "Volume flow (float)"
   },
   {
    "table": "holding_register",
    "address": 4008,
    "why": "Total volume counter (float)"
   },
   {
    "table": "holding_register",
    "address": 3016,
    "why": "Total volume counter (double precision)"
   },
   {
    "table": "holding_register",
    "address": 4022,
    "why": "Error and warning bits"
   },
   {
    "table": "holding_register",
    "address": 4028,
    "why": "Battery remaining"
   },
   {
    "table": "holding_register",
    "address": 4030,
    "why": "Flow direction"
   }
  ],
  "enable": "The Modbus add-on is configured in the local menu: slave address (default 1), baud rate (default 9600), parity (default even), stop bits, data format (default big endian), transmission delay and reception interval.",
  "watchdog": null,
  "quirks": [
   "Addresses are protocol addresses (0-based).",
   "Changing the data format register flips byte and/or word order for every multi-register value.",
   "Reading an alarm-state register acknowledges the alarm."
  ],
  "setup": [
   "Default RTU settings: address 1, 9600 baud, even parity, 1 stop bit.",
   "On battery-powered units the bus is not isolated and is limited to about 100 m without termination."
  ],
  "gotchas": [
   "On battery units Modbus may be off after a mains loss (8007 default off) or listening only at the reception interval: a master that polls at random times gets no answer.",
   "Setting writes stay pending until coil 1002 (Apply changes) is set."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/krohne/ifc-070",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}