 "manufacturer": "KROHNE",
 "manufacturer_slug": "krohne",
 "model": "MFC 300 Coriolis mass flow converter (Modbus RTU)",
 "model_slug": "mfc-300",
 "short_model": "MFC 300",
 "aliases": [
  "MFC300",
  "KROHNE MFC 300"
 ],
 "equipment_type": "Sensor (Coriolis mass flowmeter)",
 "applies_to": "MFC 300 converter with the Modbus option, supplementary instructions 4000744801 R01 (11/2009).",
 "summary": "The MFC 300 is a KROHNE signal converter for Coriolis mass flowmeters. With the Modbus option it is an RS-485 Modbus RTU slave. This map covers mass and volume flow, density, temperature, concentration and diagnosis floats, the double-float counters, counter and calibration parameters, serial settings and the control coils.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual lists protocol addresses that go into the request unchanged: input register 30006 is requested as start address 30006 (0x7536)."
 },
 "default_word_order": "ABCD",
 "firmware": "Electronic revision ER 3.3.xx (SW.REV. 3.3x), Modbus version 1.0.x",
 "source": {
  "title": "MFC 300 Supplementary instructions - Description of Modbus interface",
  "doc_number": "4000744801 R01",
  "revision_date": "2009-11",
  "url": "https://cdn.krohne.com/archive/AD_MFC300_Modbus_en_091124_4000744801_R01.pdf",
  "pages": "Serial settings p. 6; protocol and addressing pp. 8-9; coils pp. 10-11; input registers p. 12; holding registers pp. 13-16; calibration pp. 17-22"
 },
 "notes": [
  "Data format is selectable in converter menu C6.8; the default is Big Endian, which section 6.2 defines as MSB first, so floats and doubles are listed ABCD. The register table for 50004 pairs the labels the other way round (see below), so check one known value (for example 30000 at zero flow, or the baud rate at 50000) before trusting a new installation.",
  "Left out: the data-format register 50004, because its printed coding contradicts itself (0 = Little Endian 'MSB first', 1 = Big Endian 'LSB first'); set data format at the converter menu instead.",
  "Left out: long status sensor/device (30062 / 30064, byte[4]) because their bits are not defined here.",
  "Counter 3 and its parameters exist only on converters with the IO2 option; writing to a missing counter returns an error.",
  "Factory serial settings: address 1, 19200 baud, even parity, 1 stop bit."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 1000,
   "documented": "1000",
   "name": "Cold start",
   "description": "Write 1 to cold-start the converter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1001,
   "documented": "1001",
   "name": "Warm start",
   "description": "Write 1 to warm-start; activates new calibration values.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1002,
   "documented": "1002",
   "name": "Error reset",
   "description": "Write 1 to reset errors.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2000,
   "documented": "2000",
   "name": "Zero calibration",
   "description": "Write 1 to start; reads 1 while running.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2001,
   "documented": "2001",
   "name": "Single-point density calibration",
   "description": "Write 1 to start.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2002,
   "documented": "2002",
   "name": "Two-point density calibration, point 1",
   "description": "Write 1 to start.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2003,
   "documented": "2003",
   "name": "Two-point density calibration, point 2",
   "description": "Write 1 to start.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3000,
   "documented": "3000",
   "name": "Counter 1 start/stop",
   "description": "Write 1 start, 0 stop.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3001,
   "documented": "3001",
   "name": "Counter 2 start/stop",
   "description": "Write 1 start, 0 stop.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3002,
   "documented": "3002",
   "name": "Counter 3 start/stop",
   "description": "IO2 only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3003,
   "documented": "3003",
   "name": "Counter 1 reset",
   "description": "Write 1 to reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3004,
   "documented": "3004",
   "name": "Counter 2 reset",
   "description": "Write 1 to reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3005,
   "documented": "3005",
   "name": "Counter 3 reset",
   "description": "IO2 only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20000,
   "documented": "20000",
   "name": "Calibration result",
   "description": "Result of the last calibration function (first float).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30000,
   "documented": "30000",
   "name": "Flow velocity",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30002,
   "documented": "30002",
   "name": "Volume flow",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "m3/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30004,
   "documented": "30004",
   "name": "Mass flow",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30006,
   "documented": "30006",
   "name": "Temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "K",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30008,
   "documented": "30008",
   "name": "Density",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/m3",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30010,
   "documented": "30010",
   "name": "Concentration 1",
   "description": "Type chosen in 42000.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30012,
   "documented": "30012",
   "name": "Concentration 2 or diagnosis 3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30014,
   "documented": "30014",
   "name": "Concentration flow 1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30016,
   "documented": "30016",
   "name": "Concentration flow 2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30018,
   "documented": "30018",
   "name": "Diagnosis 1",
   "description": "Type chosen in 42002.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30020,
   "documented": "30020",
   "name": "Diagnosis 2",
   "description": "Type chosen in 42003.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30022,
   "documented": "30022",
   "name": "Display channel 1",
   "description": "First line of the first measurement screen, SI units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30024,
   "documented": "30024",
   "name": "Display channel 2",
   "description": "First line of the second measurement screen, SI units.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30026,
   "documented": "30026",
   "name": "Operating time",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30050,
   "documented": "30050",
   "name": "Counter 1",
   "description": "m3 or kg.",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30054,
   "documented": "30054",
   "name": "Counter 2",
   "description": "m3 or kg.",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30058,
   "documented": "30058",
   "name": "Counter 3",
   "description": "m3 or kg; only with IO2.",
   "data_type": "FLOAT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40000,
   "documented": "40000",
   "name": "Counter 1 function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Sum counter",
    "2": "+ counter",
    "3": "- counter",
    "0": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40001,
   "documented": "40001",
   "name": "Counter 1 measurement",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "21": "Volume flow",
    "22": "Mass flow",
    "27": "Concentration flow 1",
    "28": "Concentration flow 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40002,
   "documented": "40002",
   "name": "Counter 2 function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Sum counter",
    "2": "+ counter",
    "3": "- counter",
    "0": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40003,
   "documented": "40003",
   "name": "Counter 2 measurement",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "21": "Volume flow",
    "22": "Mass flow",
    "27": "Concentration flow 1",
    "28": "Concentration flow 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40004,
   "documented": "40004",
   "name": "Counter 3 function",
   "description": "Only with IO2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Sum counter",
    "2": "+ counter",
    "3": "- counter",
    "0": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40005,
   "documented": "40005",
   "name": "Counter 3 measurement",
   "description": "Only with IO2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "21": "Volume flow",
    "22": "Mass flow",
    "27": "Concentration flow 1",
    "28": "Concentration flow 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41000,
   "documented": "41000",
   "name": "Counter 1 low flow cutoff",
   "description": "m3/s or kg/s.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41002,
   "documented": "41002",
   "name": "Counter 1 time constant",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41004,
   "documented": "41004",
   "name": "Counter 1 value (set/read)",
   "description": "m3 or kg.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41006,
   "documented": "41006",
   "name": "Counter 2 low flow cutoff",
   "description": "m3/s or kg/s.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41008,
   "documented": "41008",
   "name": "Counter 2 time constant",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41010,
   "documented": "41010",
   "name": "Counter 2 value (set/read)",
   "description": "m3 or kg.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41012,
   "documented": "41012",
   "name": "Counter 3 low flow cutoff",
   "description": "m3/s or kg/s; IO2 only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41014,
   "documented": "41014",
   "name": "Counter 3 time constant",
   "description": "IO2 only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41016,
   "documented": "41016",
   "name": "Counter 3 value (set/read)",
   "description": "m3 or kg; IO2 only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41018,
   "documented": "41018",
   "name": "Counter 1 preset",
   "description": "m3 or kg.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41020,
   "documented": "41020",
   "name": "Counter 2 preset",
   "description": "m3 or kg.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41022,
   "documented": "41022",
   "name": "Counter 3 preset",
   "description": "m3 or kg; IO2 only.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42000,
   "documented": "42000",
   "name": "Concentration 1 selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Brix",
    "3": "% mass",
    "4": "Baume 144",
    "5": "Baume 145",
    "6": "% NaOH",
    "7": "Plato",
    "8": "API",
    "9": "% volume"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42001,
   "documented": "42001",
   "name": "Concentration 2 selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Off",
    "2": "Brix",
    "3": "% mass",
    "4": "Baume 144",
    "5": "Baume 145",
    "6": "% NaOH",
    "7": "Plato",
    "8": "API",
    "9": "% volume"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42002,
   "documented": "42002",
   "name": "Diagnosis 1 selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "9": "Tube frequency [Hz]",
    "10": "Measuring tube strain [Ohm]",
    "11": "Inner cylinder strain [Ohm]",
    "14": "Drive energy [%]",
    "31": "Sensor average [%]",
    "32": "Sensor deviation [%]",
    "255": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42003,
   "documented": "42003",
   "name": "Diagnosis 2 selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "9": "Tube frequency [Hz]",
    "10": "Measuring tube strain [Ohm]",
    "11": "Inner cylinder strain [Ohm]",
    "14": "Drive energy [%]",
    "31": "Sensor average [%]",
    "32": "Sensor deviation [%]",
    "255": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42004,
   "documented": "42004",
   "name": "Diagnosis 3 selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "9": "Tube frequency [Hz]",
    "10": "Measuring tube strain [Ohm]",
    "11": "Inner cylinder strain [Ohm]",
    "14": "Drive energy [%]",
    "31": "Sensor average [%]",
    "32": "Sensor deviation [%]",
    "255": "Off"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43000,
   "documented": "43000",
   "name": "Zero calibration value",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43002,
   "documented": "43002",
   "name": "Zero calibration temperature",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43004,
   "documented": "43004",
   "name": "DCF2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43006,
   "documented": "43006",
   "name": "DCF3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43008,
   "documented": "43008",
   "name": "DCF4",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43010,
   "documented": "43010",
   "name": "DCF6",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43012,
   "documented": "43012",
   "name": "DCF7",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43014,
   "documented": "43014",
   "name": "DCF8",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44000,
   "documented": "44000",
   "name": "Density calibration state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "First point not done",
    "1": "First point done"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44001,
   "documented": "44001",
   "name": "DCF1 medium",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Empty",
    "1": "Pure water",
    "2": "Town water",
    "3": "Other"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44002,
   "documented": "44002",
   "name": "DCF5 medium",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Empty",
    "1": "Pure water",
    "2": "Town water",
    "3": "Other"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50000,
   "documented": "50000",
   "name": "Baud rate",
   "description": "1200-115200; default 19200.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "baud",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50002,
   "documented": "50002",
   "name": "Slave address",
   "description": "1-247, default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50003,
   "documented": "50003",
   "name": "Parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even (default)",
    "1": "Odd",
    "3": "None"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read input registers 30000-30027 (function 04) for flow, density and temperature floats and 30050-30061 for the double-float counters. Use coils 3000-3005 to start, stop and reset counters.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 30004,
    "why": "Mass flow"
   },
   {
    "table": "input_register",
    "address": 30002,
    "why": "Volume flow"
   },
   {
    "table": "input_register",
    "address": 30008,
    "why": "Density"
   },
   {
    "table": "input_register",
    "address": 30006,
    "why": "Temperature"
   },
   {
    "table": "input_register",
    "address": 30050,
    "why": "Counter 1"
   }
  ],
  "enable": "Set address, baud rate, parity, data format and stop bits in converter menu C6.8.",
  "watchdog": null,
  "quirks": [
   "Protocol addresses are sent as printed.",
   "Temperature is in kelvin.",
   "Counters are 64-bit doubles."
  ],
  "setup": [
   "Defaults 19200 baud, even parity, 1 stop bit, address 1.",
   "Bus termination and biasing are off by default; set jumpers X5/X6 on the Modbus board to enable them."
  ],
  "gotchas": [
   "New calibration values take effect after a warm start (coil 1001)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/krohne/mfc-300",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}