 "manufacturer": "Legrand",
 "manufacturer_slug": "legrand",
 "model": "Energy meter 4 120 68 (RS-485 Modbus)",
 "model_slug": "energy-meter-412068",
 "short_model": "4 120 68",
 "aliases": [
  "412068",
  "4 120 68",
  "Legrand 412068"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "Legrand energy meter cat. no. 4 120 68 with RS-485 Modbus RTU, per Modbus table F02230EN-01.",
 "summary": "Legrand's 4 120 68 is a meter with an RS-485 Modbus RTU port. Its short Modbus table gives voltage, current, frequency, active/reactive/apparent power and power factor as 16-bit words, two 32-bit energy counters, the internal temperature, a date/time block and the baud-rate and address settings. The energy counters are left out of this map because the table does not say which word comes first.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The table gives a 1-based register number and the 0-based register address in decimal and hex (voltage: number 1, address 0). The address is sent on the wire: the date/time example reads register number 34 with the frame ADDR 03 0021 0004."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Modbus table F02230EN-01 (4 120 68)",
  "doc_number": "F02230EN-01",
  "revision_date": null,
  "url": "https://assets.legrand.com/pim/NP-FT-GT/F02230EN-01%20(4%20120%2068).pdf",
  "pages": "Table organisation, protocol and serial details p. 1; input registers p. 4; date/time and settings with example frames p. 5"
 },
 "notes": [
  "Left out: positive active energy (address 7, 2 words, x10 Wh) and positive reactive energy (address 17, 2 words, x10 varh). The table only says data are 'Big Endian' (most significant byte first), which fixes the byte order inside a word but not which of the two words is sent first.",
  "Supported functions: 03 (read) and 16 (write). Exception codes 1, 2 and 3.",
  "Serial details: RS-485 two-wire, RTU, address 1-247, programmable baud rate, 8 data bits, no parity, 1 stop bit.",
  "Timing: inter-character time-out 25 ms, response delay 25-100 ms, wait more than 25 ms between master requests.",
  "Left out: the 4-register date/day-of-week/time block at 33 (packed BCD-style digits per the example).",
  "The table heads the measurement page 'Input registers' but gives read function code 3, so they are listed here as holding registers (function 03)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3",
   "name": "Active power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Reactive power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "5",
   "name": "Apparent power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Power factor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "37",
   "name": "Internal temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "42",
   "name": "Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1200",
    "2": "2400",
    "3": "4800",
    "4": "9600"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "43",
   "name": "Modbus address",
   "description": "1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers with function 03 from address 0: 7 words give voltage, current, frequency, active/reactive/apparent power and power factor. Address 37 is the internal temperature.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Voltage"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Current"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Active power"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Power factor"
   }
  ],
  "enable": "Modbus RTU is active on the RS-485 port; baud rate (register 42) and address (register 43) can be written with function 16, e.g. ADDR 10 002A 0001 02 0002 sets 2400 baud.",
  "watchdog": null,
  "quirks": [
   "Register numbers in the table are address + 1; send the address.",
   "Power values are unsigned 16-bit."
  ],
  "setup": [
   "Baud codes: 1 = 1200, 2 = 2400, 3 = 4800, 4 = 9600."
  ],
  "gotchas": [
   "Active power is 16-bit whole watts, so it tops out at 65535 W."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/legrand/energy-meter-412068",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}