 "manufacturer": "Lenze",
 "manufacturer_slug": "lenze",
 "model": "i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)",
 "model_slug": "i510",
 "short_model": "i510",
 "aliases": [
  "i500 series",
  "i510 Cabinet",
  "I51AE"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Lenze i510 cabinet inverters 0.25-2.2 kW with the Modbus/CANopen control unit, selector set to Modbus, firmware 01.01.01.00 as documented in the commissioning manual.",
 "summary": "Lenze's i510 is a compact cabinet frequency inverter whose Modbus/CANopen control unit acts as a Modbus RTU slave. Besides 24 freely mappable registers, it has fixed blocks: status data from 42001 and control data from 42101. This map covers those predefined registers: AC drive control and status words, frequency setpoint and actual frequency, drive status, error code, motor voltage and current, apparent power, temperatures, DC bus and torque.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual states all data are 4X registers numbered from 1 but addressed from 0, so register 40001 is address 0; its example writes register 42101 to address 2100 (0x0834). So 42001 = wire 2000 and 42101 = wire 2100."
 },
 "default_word_order": "ABCD",
 "firmware": "01.01.01.00",
 "source": {
  "title": "Inverter i510 Cabinet 0.25 ... 2.2 kW - Configuration | Commissioning | Service",
  "doc_number": null,
  "revision_date": null,
  "url": "https://www.precision-elec.com/wp-content/uploads/2017/02/Lenze-AC-Tech-i500-i510-VFD-Users-Manual-For-Commissioning.pdf",
  "unofficial": true,
  "pages": "pp. 105-110 (AC drive control/status word, drive status, setpoint and actual frequency), pp. 127-137 (Modbus chapter: settings, function codes and addressing p. 131, predefined registers p. 132, short setup and example frame p. 137), pp. 229-250 (parameter attribute list: data type and factor)"
 },
 "notes": [
  "This copy is hosted by the US distributor Precision Electric and is the unaltered Lenze commissioning manual; Lenze's own copy sits in its download portal and was not found as a direct public link.",
  "Data types and scaling come from the parameter attribute list (data type and network factor: the integer read is divided by the factor, e.g. factor 10 -> scale 0.1).",
  "Apparent power 42008/42009 is a 32-bit signed value; the register table states 42008 = high word and 42009 = low word (ABCD), factor 1000 (kW as printed).",
  "Left out: 42012 digital inputs (0x60FD is a 32-bit parameter but only one register is assigned, so which half is sent is unclear); 42103 and 42104, because the register table gives 42103 as NETWordIN2 with address 0x4008:003 (which the attribute list calls NETWordIN3) and repeats 0x400B:001 for 42104.",
  "The 24 freely mappable registers (0x232B:1-24, internal register numbers from 2500 shown in 0x232C) are not listed; their content depends on configuration.",
  "Only function codes 3, 6, 16 and 23 are supported; all data are holding registers. Data are big-endian (most significant byte first)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 2000,
   "documented": "42001",
   "name": "AC Drive status word (0x400C:001)",
   "description": "EtherNet/IP AC drive profile bits.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Fault/trip",
    "1": "Reserved",
    "2": "Running forward",
    "3": "Running reverse",
    "4": "Ready",
    "5": "Control from network",
    "6": "Reference from network",
    "7": "At reference",
    "8": "Reserved",
    "9": "Reserved",
    "10": "Reserved",
    "11": "Reserved",
    "12": "Process controller active",
    "13": "Torque mode active",
    "14": "Current limit reached",
    "15": "DC braking active"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2001,
   "documented": "42002",
   "name": "Actual frequency (0x400C:006)",
   "description": "Unsigned; direction is in the status word.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2002,
   "documented": "42003",
   "name": "Error code (0x603F)",
   "description": "Active error code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "42004",
   "name": "Drive status (0x400C:005)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Error (non-resettable)",
    "1": "Error",
    "2": "Waiting for start",
    "3": "Identification not executed",
    "4": "Controller inhibit",
    "5": "Stop",
    "7": "Identification",
    "8": "Running",
    "9": "Acceleration",
    "10": "Deceleration",
    "11": "Deceleration override",
    "12": "DC braking",
    "13": "Flying start",
    "14": "Current limit reached",
    "16": "Process controller idle state"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2004,
   "documented": "42005",
   "name": "Actual motor voltage (0x2D89)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2005,
   "documented": "42006",
   "name": "Actual motor current (0x2D88)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2006,
   "documented": "42007",
   "name": "Current actual value (0x6078)",
   "description": "Motor current in percent.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2007,
   "documented": "42008",
   "name": "Apparent power (0x2DA2:002)",
   "description": "42008 = high word, 42009 = low word.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2009,
   "documented": "42010",
   "name": "Heatsink temperature (0x2D84:001)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2010,
   "documented": "42011",
   "name": "DC-bus voltage (0x2D87)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2012,
   "documented": "42013",
   "name": "Torque actual value (0x6077)",
   "description": "Percent of rated motor torque.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2100,
   "documented": "42101",
   "name": "AC Drive control word (0x400B:001)",
   "description": "EtherNet/IP AC drive profile bits.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run forward",
    "1": "Run reverse",
    "2": "Reset error (0-1 edge)",
    "3": "Reserved",
    "4": "Reserved",
    "5": "Control from network",
    "6": "Reference from network",
    "7": "Reserved",
    "8": "Reserved",
    "9": "Reserved",
    "10": "Reserved",
    "11": "Reserved",
    "12": "Controller inhibit",
    "13": "Quick stop",
    "14": "Process controller off",
    "15": "DC braking"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2101,
   "documented": "42102",
   "name": "Network setpoint frequency (0x400B:005)",
   "description": "Unsigned, 0.00-599.00 Hz; direction via control word.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2104,
   "documented": "42105",
   "name": "Network process controller setpoint (0x400B:007)",
   "description": "-300.00 to 300.00 process units.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "PUnit",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2105,
   "documented": "42106",
   "name": "Target torque (0x6071)",
   "description": "100 % = motor rated torque (0x6076).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2106,
   "documented": "42107",
   "name": "NETWordIN1 (0x4008:001)",
   "description": "Freely assignable bit functions (0x400E).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2107,
   "documented": "42108",
   "name": "NETWordIN4 (0x4008:004)",
   "description": "0.0-100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the front selector to Modbus, activate the network (0x2631:037 = TRUE) and make the network the setpoint source (0x2860:001 = 5). Write 0x0061 to 42101 (run forward + control and reference from network) and the frequency to 42102 in 0.01 Hz; read 42001-42011 for status and measurements.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2100,
    "why": "AC Drive control word (start/stop/reset)"
   },
   {
    "table": "holding_register",
    "address": 2101,
    "why": "Frequency setpoint, 0.01 Hz"
   },
   {
    "table": "holding_register",
    "address": 2000,
    "why": "AC Drive status word"
   },
   {
    "table": "holding_register",
    "address": 2001,
    "why": "Actual frequency, 0.01 Hz"
   },
   {
    "table": "holding_register",
    "address": 2002,
    "why": "Error code"
   },
   {
    "table": "holding_register",
    "address": 2005,
    "why": "Motor current, 0.1 A"
   },
   {
    "table": "holding_register",
    "address": 2010,
    "why": "DC-bus voltage"
   }
  ],
  "enable": "Set the Modbus/CANopen selector on the inverter front to Modbus. Set 0x2631:037 (PAR 400/037) Activate network = TRUE and 0x2860:001 (PAR 201/001) = 5 Network. Set node address 0x2321:001 (1-247, default 1), baud 0x2321:002 and data format 0x2321:003 (both default Automatic), then restart Modbus communication (0x2320 = 1) or power-cycle.",
  "watchdog": "0x2858:002 Time-out (0.0-300.0 s, default 2.0 s) with 0x2858:001 Response to time-out (default Error).",
  "quirks": [
   "Register 42101 is sent as address 2100 (0x0834).",
   "The frequency setpoint and actual frequency are unsigned; direction comes from control word bits 0/1 and status bits 2/3.",
   "With automatic baud rate or data format detection the first 5-10 messages after power-up are lost.",
   "Digital input DI1 is 'Start enable' by default and must be high for the drive to start."
  ],
  "setup": [
   "Baud 2400-115200 or automatic; data format 8E1, 8O1, 8N2 or automatic.",
   "A minimum response delay can be set in 0x2321:004 (0-1000 ms)."
  ],
  "gotchas": [
   "The manual's example: writing 0x0061 to 42101 on node 1 starts the drive if DI1 is high.",
   "MOD-ERR LED blinking = communication error; MOD-RUN and MOD-ERR flickering = automatic baud detection still running."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/lenze/i510",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}