 "manufacturer": "Lenze",
 "manufacturer_slug": "lenze",
 "model": "MC Series drives MC1000 / MC3000 (Modbus RTU)",
 "model_slug": "mc-series",
 "short_model": "MC1000/MC3000",
 "aliases": [
  "MC1000",
  "MC3000",
  "MC Series",
  "Lenze AC Tech MC",
  "RG-MCMOD"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Lenze AC Tech MC1000 and MC3000 Series drives, software 213-083 rev 13 (parameter configurations 188-190); reference guide RG-MCMOD.",
 "summary": "The MC1000/MC3000 are Lenze AC Tech drives with a Modbus RTU slave at a fixed 9600 baud. Registers #1-#50 hold the control word, keypad speed command, status bytes (load, run status, direction, source, fault), motor voltage, run time and PID values; programming parameter n sits at register n + 51.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "parameter-derived",
  "note": "Lenze numbers by AC Tech register #, which is the address sent on the wire (Modbus 4X/3X numbers are one larger). The frame examples confirm it: #24 is read at start address 0x0018. Programming parameter n = register n + 51."
 },
 "default_word_order": null,
 "firmware": "MC software 213-083 revision 13 (register #50 = 188, 189 or 190)",
 "source": {
  "title": "MC Series Drives Modbus Communications Reference Guide",
  "doc_number": "RG-MCMOD",
  "revision_date": null,
  "url": "https://www.precision-elec.com/wp-content/uploads/2014/08/lenze-ac-tech-mc-series-modbus-communications-reference.pdf",
  "unofficial": true,
  "pages": "pp. 3-18 (protocol, setup, control registers and status tables), pp. 20+ (parameter list)"
 },
 "notes": [
  "Host: copy hosted by Precision Electric (a Lenze AC Tech distributor); no copy was found on lenze.com.",
  "Left out: command speed #24 and actual speed #25. Table 6 prints 0.1 Hz (0-2400), while the data-type table and notes 3a/3b say hundredths of a Hz (0x0201 = 5.13 Hz); the guide contradicts itself. #24 can still be read as a 6-register block starting at address 24.",
  "Operational status (low byte #26): 0 fault lockout, 1 fault, 2 start pending, 3 stop, 4 DC brake, 5 run at 0 Hz, 6 run, 7 accel, 8 decel, 9 current limit, 10 decel override, 11 lower transistors switching on, 12 sleep.",
  "Speed source (high byte #28): 0 keypad, 1 0-10 VDC, 2 4-20 mA, 3-6 preset 1-4, 7 MOP, 8 reserved, 9 keypad speed (PID enabled), 10 PID keypad setpoint, 11 0-10 VDC PID setpoint, 12 4-20 mA PID setpoint.",
  "No kWh registers are listed for the MC Series. Only the control registers and serial-setup parameters are included here.",
  "Present fault (high byte #29): 0 none, 1 output transistor, 3 high DC bus, 4 high drive temperature, 5 thermal overload, 7 low DC bus, 9 DC brake error, 10 follower loss, 11 dynamic brake overload, 12 power sag, 13 control, 14 language, 15 external, 16 internal 16, 17 power transient, 18-23 internal errors (2, 6 and 8 reserved).",
  "P30 CONTROL: MC1000 0 local (default), 1 remote, 2 both; MC3000 0 local (default), 1 remote, 2 serial, 3 keypad, 4 TB strip, 5 keypad 2."
 ],
 "integration": {
  "summary": "Set P57 and P58 on the keypad. Read #26-#29 (or the 6-register block at #24) for load, status, mode, source and fault. To control: write the password (default 19) to #48, send 0200h to #1 for manual mode, start/stop via #1 and write the speed to #40.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 48,
    "why": "Unlock control"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Start / stop / direction"
   },
   {
    "table": "holding_register",
    "address": 40,
    "why": "Keypad speed command"
   },
   {
    "table": "holding_register",
    "address": 27,
    "why": "Control mode (low byte) and direction"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Load and status"
   },
   {
    "table": "holding_register",
    "address": 29,
    "why": "Present fault"
   }
  ],
  "enable": "P57 SERIAL LINK = 01 (with 10 s watchdog) or 02 (without); P58 = address; P30 CONTROL usually LOCAL on MC1000 and SERIAL on MC3000 for serial use.",
  "watchdog": "Fixed 10 s once #48 or #49 has unlocked the drive and P57 = with timer; in LOCAL/KEYPAD 2 control the drive stops on time-out (no fault is logged).",
  "quirks": [
   "Read one register at a time except the #24 six-word block.",
   "FC16 accepts a single register only; FC03 and FC04 are identical.",
   "No broadcast support."
  ],
  "setup": [
   "Fixed 9600 baud, 8 data bits, no parity, 2 stop bits."
  ],
  "gotchas": [
   "Changing CONTROL from LOCAL to REMOTE stops the drive immediately.",
   "End a session by writing 2 to #1 (lock security)."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "#1 (4X 40002)",
   "name": "Drive control",
   "description": "One bit per write: 0004h stop, 0008h start, 0200h manual mode, 0002h lock.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "Update buffers",
    "1": "Lock security",
    "2": "Stop drive",
    "3": "Start drive",
    "6": "Set reverse",
    "7": "Set forward",
    "8": "Auto mode",
    "9": "Manual mode"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "#19 (4X 40020)",
   "name": "Drive family",
   "description": "Reads 65 (41h) for MC Series.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "#21 (4X 40022)",
   "name": "Drive size code",
   "description": "HP / voltage code (table 9 of the guide).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "#26 (4X 40027)",
   "name": "Load (high byte) / operational status (low byte)",
   "description": "High byte = % of full load. Low byte = status code, see notes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "#27 (4X 40028)",
   "name": "Actual direction (high) / control mode (low)",
   "description": "High: 0 fwd, 1 rev. Low: 0 local, 1 remote, 2 serial.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "#28 (4X 40029)",
   "name": "Speed source (high) / speed reference (low)",
   "description": "High: speed source code (notes). Low: 0 auto, 1 manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "#29 (4X 40030)",
   "name": "Present fault (high) / commanded direction (low)",
   "description": "High byte = fault code. Low: 0 fwd, 1 rev.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "#30 (4X 40031)",
   "name": "Motor voltage",
   "description": "Effective output voltage to the motor, 0-999 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "#36 (4X 40037)",
   "name": "Total run time, hours",
   "description": "MC3000 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "#37 (4X 40038)",
   "name": "Total run time, minutes",
   "description": "MC3000 only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "#38 (4X 40039)",
   "name": "PID setpoint",
   "description": "MC1000 with PID and MC3000. Internal units 0-32736 over the feedback range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "#39 (4X 40040)",
   "name": "PID feedback",
   "description": "MC1000 with PID and MC3000. Internal units 0-32736 over the feedback range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "#40 (4X 40041)",
   "name": "Keypad speed command",
   "description": "0-65000; drive must be in manual mode (0200h to #1).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "#41 (4X 40042)",
   "name": "Local PID command",
   "description": "MC1000 with PID and MC3000. Internal units 0-32736 over the feedback range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "#48 (4X 40049)",
   "name": "Unlock commands",
   "description": "0 unlocks control; the password (default 19) also unlocks parameters.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "#49 (4X 40050)",
   "name": "Unlock parameters",
   "description": "Password unlocks parameter writes only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "#50 (4X 40051)",
   "name": "Register version",
   "description": "Parameter configuration 188, 189 or 190 for software 213-083 rev 13.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "#81 (4X 40082)",
   "name": "P30 control",
   "description": "MC1000: 0 local, 1 remote, 2 both. MC3000 adds 2 serial, 3-5 (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "#108 (4X 40109)",
   "name": "P57 serial link",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "With timer",
    "2": "Without timer"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "#109 (4X 40110)",
   "name": "P58 serial address",
   "description": "1-247 (default 30). Set before using the serial link; avoid address 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/lenze/mc-series",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}