 "manufacturer": "Lenze",
 "manufacturer_slug": "lenze",
 "model": "MCH Series HVAC drive (Modbus RTU)",
 "model_slug": "mch-series",
 "short_model": "MCH",
 "aliases": [
  "MCH",
  "Lenze AC Tech MCH",
  "RG-MHMOD"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Lenze AC Tech MCH Series drives, software 213-070 rev 00 (parameter configuration 148); reference guide RG-MHMOD.",
 "summary": "The MCH is a Lenze AC Tech drive family that acts as a Modbus RTU slave at a fixed 9600 baud. Registers #1-#50 hold the control word, speed commands, status bytes, fault code, kWh and run-time counters and PID values; programming parameter n sits at register n + 51.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "parameter-derived",
  "note": "Lenze numbers by AC Tech register #, which is exactly the address sent on the wire (Modbus 4X/3X register numbers are one larger). The guide's frames confirm it: #24 is read with start address 0x0018. Programming parameter n = AC Tech register n + 51."
 },
 "default_word_order": null,
 "firmware": "MCH software 213-070 revision 00 (register #50 = 148)",
 "source": {
  "title": "MCH Series Drives Modbus Communications Reference Guide",
  "doc_number": "RG-MHMOD",
  "revision_date": null,
  "url": "https://www.precision-elec.com/wp-content/uploads/2014/08/lenze-ac-tech-mch-series-modbus-communications-reference.pdf",
  "unofficial": true,
  "pages": "pp. 3-19 (protocol, setup, control registers and bit/status tables), pp. 20+ (parameter list)"
 },
 "notes": [
  "Host: copy hosted by Precision Electric (a Lenze AC Tech distributor); no copy was found on lenze.com.",
  "Left out: command speed #24 and actual speed #25. Table 6 prints 0.1 Hz (0-2400), while the data-type table and notes 3a/3b say hundredths of a Hz (0x0201 = 5.13 Hz); the guide contradicts itself. #24 can still be read as a 6-register block starting at address 24.",
  "kWh: #32 is the low word and #33 the high word; total = high x 65536 + low. The guide reads one register at a time (only #24 and #100/#101 allow multi-word reads), so they are listed as two separate words.",
  "Operational status (low byte #26): 0 fault lockout, 1 fault, 2 start pending, 3 stop, 4 DC brake, 5 run at 0 Hz, 6 run, 7 accel, 8 decel, 9 current limit, 10 decel override.",
  "Speed source (high byte #28): 0 keypad, 1 0-10 VDC, 2 4-20 mA, 3-6 preset 1-4, 7 MOP, 8 keypad speed, 9 keypad/serial PID setpoint, 10 0-10 VDC PID setpoint, 11 4-20 mA PID setpoint, 12 serial speed, 13 serial PID setpoint, 14 sleep.",
  "Present fault (high byte #29): 0 none, 1 output transistor, 3 high DC bus, 4 high drive temperature, 5 thermal overload, 7 low DC bus, 9 DC brake error, 10 serial/follower loss, 11 dynamic brake overload, 12 power sag, 13 control, 14 language, 15 external, 16 internal 16, 17 power transient, 18-23 internal errors.",
  "Only the control registers and the three serial-setup parameters are listed; the full parameter list (#51 onward, one or two implied decimals) applies to software 213-070 rev 00 only."
 ],
 "integration": {
  "summary": "Set P57 (serial link) and P58 (address) on the keypad. Read #26-#29 for load, status, mode, source and fault. To control: write 0 to #48 to unlock #1, or the password (default 19) to also unlock #40/#42; start/stop via #1 and write speed to #40, or set serial select (0200h on #1) and write #42.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 48,
    "why": "Unlock control"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Start / stop / serial select"
   },
   {
    "table": "holding_register",
    "address": 40,
    "why": "Keypad speed command"
   },
   {
    "table": "holding_register",
    "address": 27,
    "why": "Control mode (low byte) and direction"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Load and status"
   },
   {
    "table": "holding_register",
    "address": 29,
    "why": "Present fault"
   }
  ],
  "enable": "P57 SERIAL LINK = 01 (with 10 s watchdog) or 02 (without); P58 = address; P30 CONTROL sets how much the serial link may command (serial speed/auto modes). TB1 must be closed to unlock serial control.",
  "watchdog": "Fixed 10 s once #48 or #49 has unlocked the drive and P57 = with timer. Action depends on P30: normal modes drop out of serial control, serial speed modes follow P56 SERIAL LOSS, serial auto modes trip FLWR/SER fault.",
  "quirks": [
   "Read one register at a time except the #24 six-word block (and 4-word #100/#101).",
   "FC16 accepts a single register only; FC03 and FC04 are identical.",
   "No broadcast support."
  ],
  "setup": [
   "Fixed 9600 baud, 8 data bits, no parity, 2 stop bits."
  ],
  "gotchas": [
   "If register #50 is not 148, do not write registers with this map.",
   "End a session by writing 2 to #1 (lock security)."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "#1 (4X 40002)",
   "name": "Drive control",
   "description": "One bit per write: 0004h stop, 0008h start, 0200h serial select, 0002h lock.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "Update buffers",
    "1": "Lock security",
    "2": "Stop drive",
    "3": "Start drive",
    "8": "Clear serial select flag",
    "9": "Set serial select flag"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "#19 (4X 40020)",
   "name": "Drive family",
   "description": "Reads 68 (44h) for MCH.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "#21 (4X 40022)",
   "name": "Drive size code",
   "description": "HP / voltage code (table 9 of the guide).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "#26 (4X 40027)",
   "name": "Load (high byte) / operational status (low byte)",
   "description": "High byte = % of full load. Low byte = status code, see notes.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "#27 (4X 40028)",
   "name": "Actual direction (high) / control mode (low)",
   "description": "High: 0 fwd, 1 rev. Low: 0 off, 1 hand, 2 auto, 3 serial.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "#28 (4X 40029)",
   "name": "Speed source (high) / auto-hand (low)",
   "description": "High: speed source code (notes). Low: 0 hand, 1 auto.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "#29 (4X 40030)",
   "name": "Present fault (high) / commanded direction (low)",
   "description": "High byte = fault code (notes). Low: 0 fwd, 1 rev.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "#30 (4X 40031)",
   "name": "Motor voltage",
   "description": "Effective output voltage to the motor, 0-999 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "#32 (4X 40033)",
   "name": "Kilowatt hours, low word",
   "description": "Read separately; total kWh = #33 x 65536 + #32.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "#33 (4X 40034)",
   "name": "Kilowatt hours, high word",
   "description": "Read separately; total kWh = #33 x 65536 + #32.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "#36 (4X 40037)",
   "name": "Total run time, hours",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "#37 (4X 40038)",
   "name": "Total run time, minutes",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "#38 (4X 40039)",
   "name": "PID setpoint",
   "description": "Internal units 0-32736 over the feedback device range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "#39 (4X 40040)",
   "name": "PID feedback",
   "description": "Internal units 0-32736 over the feedback device range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "#40 (4X 40041)",
   "name": "Keypad speed command",
   "description": "0-65000; writable after unlocking control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "#41 (4X 40042)",
   "name": "Local PID command",
   "description": "Internal units 0-32736.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "#42 (4X 40043)",
   "name": "Serial speed command",
   "description": "Followed when the serial select flag is set.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "#43 (4X 40044)",
   "name": "Serial PID command",
   "description": "Internal units 0-32736.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "#48 (4X 40049)",
   "name": "Unlock commands",
   "description": "0 unlocks control; the password (default 19) also unlocks parameters.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "#49 (4X 40050)",
   "name": "Unlock parameters",
   "description": "Password unlocks parameter writes only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "#50 (4X 40051)",
   "name": "Register version",
   "description": "Parameter configuration number; 148 for software 213-070 rev 00.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "#81 (4X 40082)",
   "name": "P30 control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normal (default)",
    "1": "Norm no hand",
    "2": "Serial speed",
    "3": "S spd / no hand",
    "4": "Serial auto",
    "5": "S auto / no hand"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "#108 (4X 40109)",
   "name": "P57 serial link",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable (default)",
    "1": "With timer",
    "2": "Without timer"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "#109 (4X 40110)",
   "name": "P58 serial address",
   "description": "1-247 (default 30). Must be set before using the serial link.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/lenze/mch-series",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}