 "manufacturer": "Lenze",
 "manufacturer_slug": "lenze",
 "model": "SCF Series drive with Modbus module (basic network control)",
 "model_slug": "scf-series",
 "short_model": "SCF",
 "aliases": [
  "SCF",
  "Lenze AC Tech SCF",
  "AN0028"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).",
 "summary": "The SCF is a Lenze AC Tech drive. With its Modbus option it can be started, stopped, reversed and speed-controlled over Modbus RTU at 9600 baud. This map holds the basic control registers from Lenze's quick-start note plus the rule that maps every SCF parameter to a Modbus register.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The note gives 4xxxx Modbus register numbers, which are AC Tech register + 1 (control register 1 = 40002). Wire address = Modbus register - 40001, so the control register is address 1. SCF parameter Pn is Modbus register n + 51 (P19 -> 40070)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Application Note: Basic Network Control of the SCF Drive using ModBus Communications",
  "doc_number": "AN0028/A1",
  "revision_date": "2008-01",
  "url": "https://www.precision-elec.com/wp-content/uploads/2014/08/basic-network-control-of-scf-drive-using-modbus-communications.pdf",
  "unofficial": true,
  "pages": "pp. 1-2"
 },
 "notes": [
  "Host: copy hosted by Precision Electric (a Lenze AC Tech distributor); no current copy was found on lenze.com.",
  "This is a quick-start map only. The full register list is in the SCF ModBus Reference Guide RG-SFMOD, which was not available; other parameters follow 'Modbus register = parameter + 51' with scaling from the SCF manual.",
  "Only 9600 baud is supported. Data format is chosen with P15: 02/03 = 8N2, 04/05 = 8E1, 06/07 = 8O1 (even numbers enable the 10 s watchdog).",
  "Only one command bit per write to the control register."
 ],
 "integration": {
  "summary": "Set P14 = 01 and P43 = address, write 0 (or the password) to 40049 once after power-up, then write 0008h to 40002 to start and the speed in 0.1 Hz to 40041 (with P05 = 01). Read 40027 for the run status.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 48,
    "why": "Unlock"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Start / stop / direction"
   },
   {
    "table": "holding_register",
    "address": 40,
    "why": "Speed command"
   },
   {
    "table": "holding_register",
    "address": 26,
    "why": "Run status"
   }
  ],
  "enable": "P14 = 01 enables serial communication; P43 sets the address (1-247); P15 sets data format and watchdog.",
  "watchdog": "Fixed 10 s: if enabled via P15 and the master stops communicating while the drive is under network control, the drive stops.",
  "quirks": [
   "Use FC06, or FC16 with a length of 1, for every write.",
   "The local STOP circuit stays active: input 1 (TB1 to TB2) must be asserted to start."
  ],
  "setup": [
   "Master at 9600 baud with the data format matching P15."
  ],
  "gotchas": [
   "Lenze advises not to leave the slave at address 1 to avoid duplicates."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Drive control (AC Tech register 1)",
   "description": "One command per write: 0004h stop, 0008h start, 0040h reverse, 0080h forward, 0200h manual.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "2": "Stop (per P04)",
    "3": "Start",
    "6": "Set reverse (needs P17 = 2)",
    "7": "Set forward",
    "9": "Manual mode (use keypad speed register)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "40025",
   "name": "Status block start (AC Tech register 24)",
   "description": "First of a 6-register status block; read 6 registers from here.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "40027",
   "name": "Run status (AC Tech register 26, low byte)",
   "description": "Low byte = operational status code; see values.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault lockout",
    "1": "Fault",
    "2": "Start pending",
    "3": "Stop",
    "4": "DC brake",
    "5": "Run at 0 Hz",
    "6": "Run",
    "7": "Accel",
    "8": "Decel",
    "9": "Current limit",
    "10": "Decel override",
    "11": "Lower transistors switching on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40041",
   "name": "Keypad speed command (AC Tech register 40)",
   "description": "Network speed when P05 = 01 (keypad); 412 = 41.2 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "40049",
   "name": "Unlock (AC Tech register 48)",
   "description": "0 unlocks control only; password (default 225) also unlocks parameters.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "40070",
   "name": "P19 acceleration time",
   "description": "Example of the parameter rule: register = parameter + 51.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/lenze/scf-series",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}