 "manufacturer": "Lenze",
 "manufacturer_slug": "lenze",
 "model": "SMVector drive with ESVZAR0 RS-485 Modbus module",
 "model_slug": "smvector-esvzar0",
 "short_model": "SMVector (ESVZAR0)",
 "aliases": [
  "SMVector",
  "SMV",
  "ESVZAR0",
  "Lenze AC Tech SMV",
  "CMVMB401C"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Lenze AC Tech SMVector drives up to 10 HP with the ESVZAR0 RS-485 Modbus module, module software 1.01 / 1.10 / 1.30 (guide CMVMB401C).",
 "summary": "The SMVector is a Lenze AC Tech inverter (models up to 10 HP in this guide). The ESVZAR0 option module adds Modbus RTU on RS-485. Registers 1-99 are network control and status (control word, status word, frequencies, load, fault, run-hour counters, network speed/PID/torque commands); every drive parameter Pxxx is also readable as register xxx.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "parameter-derived",
  "note": "Lenze numbers registers by drive register #, and Modbus 4X/3X register = drive register + 1. The drive register # is the wire address: the guide's example reads #60 with start address 0x003C. Drive parameter Pxxx is register #xxx (P103 = #103)."
 },
 "default_word_order": "CDAB",
 "firmware": "ESVZAR0 module software 1.01, 1.10 or 1.30 (check P494 before writing)",
 "source": {
  "title": "SMVector ESVZAR0 RS-485 Modbus Communication Module - Communications Interface Reference Guide",
  "doc_number": "CMVMB401C",
  "revision_date": null,
  "url": "https://www.precision-elec.com/wp-content/uploads/2014/08/lenze-ac-tech-rs485-modbus-communications-reference.pdf",
  "unofficial": true,
  "pages": "pp. 10-11 (P400-P499), pp. 12-17 (protocol, unlock, watchdog), pp. 19-28 (registers, bit tables, parameters)"
 },
 "notes": [
  "Host: copy hosted by Precision Electric (a Lenze AC Tech distributor); a search did not find this guide as a direct download on lenze.com.",
  "Scaling: values are sent in internal units, value x 10^DP; e.g. 34.3 Hz is sent as 343. Frequencies, torque, PID and analog output are one-decimal values (scale 0.1). PID values (37-39, 41, 45) are signed.",
  "Word order: registers #60/#61 and #64/#65 are low word first; the guide's example shows run-time hours 0x12345678 read as 5678h then 1234h (CDAB).",
  "Left out: motor voltage #30 and total kWh #32/#33 (scaling defers to the drive manual), and the 32-bit registers #511/#540/#541 (high word first per the guide, but its #540 example frame uses the address of #511). Parameters #100-399 and #500-599 follow the SMV operating instructions (SV01) and are not listed.",
  "Present fault codes (high byte of #29): 0 no fault, 1 TMP output, 2 output transistor, 3 ground, 4 high drive temperature, 5 flying start, 6 high DC bus, 7 low DC bus, 8 thermal overload, 9 OEM, 10 illegal setup, 11 dynamic brake over-temperature, 12 single phase, 13 external, 14 control, 15 start error, 16 incompatibility, 17 internal 1 (EPM), 18 internal 2, 19 internal 3, 20/21 internal 5, 22 internal 6, 23 internal 7, 24 internal 8, 25 internal 9, 26 personality, 27 AD offset, 28 remote keypad lost, 29 assertion level, 30 internal 4, 31 internal 0, 32 follower lost, 33 ISO comm, 34 SPI time-out, 35 invalid message received, 36 network time-out.",
  "Run status codes (low byte of #26): 0 fault lockout, 1 fault, 2 start pending, 3 IDE not done, 4 inhibit, 5 stop, 6 lower transistors on, 7 run IDE, 8 run, 9 accel, 10 decel, 11 decel override, 12 DC brake, 13 flying restart, 14 slow current limit, 15 fast current limit, 16 sleep.",
  "Usually only one register per read; exceptions are #24 (6 registers #24-29) and the 2-register counters. FC16 writes only one register.",
  "Left out: network PID setpoint command #45. Table 5 marks it read-only, but section 8.3 says to write it; the access is unclear."
 ],
 "integration": {
  "summary": "Set P400 = 2, address/baud/format in P410-P412, then read #23-#29 for status, frequencies, load and fault. To run from the network: assert a terminal set to NET ENABLE, write 0 to #48 to unlock #1 (or the P194 password to also unlock #44), then write control bits to #1 and the speed to #44.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1,
    "why": "Control word: start/stop/direction"
   },
   {
    "table": "holding_register",
    "address": 48,
    "why": "Unlock controls"
   },
   {
    "table": "holding_register",
    "address": 44,
    "why": "Network speed command"
   },
   {
    "table": "holding_register",
    "address": 23,
    "why": "Status word"
   },
   {
    "table": "holding_register",
    "address": 25,
    "why": "Actual frequency"
   },
   {
    "table": "holding_register",
    "address": 29,
    "why": "Present fault"
   }
  ],
  "enable": "P400 = 2 (Modbus RTU); P410 address, P411 baud, P412 format. For control set one of P121-P123 to 09 (NET ENABLE) and close that TB-13 input, and P100 to 00, 01, 03 or 04. Use P101 = 06 or bits 12-15 of #1 to make the network the speed reference.",
  "watchdog": "Once controls are unlocked via #48, P425 (0-300 s, default 10.0 s) sets the message time-out and P426 the action (default trip fault). Any read keeps it alive.",
  "quirks": [
   "Function codes 03 and 04 are identical; FC16 only writes one register.",
   "Only one action bit per write to #1, except stop/quick stop/inhibit; otherwise exception 04.",
   "Writing #1 with bit 1 (lock security) ends network control and stops the drive if P100 = 3.",
   "Broadcast is not supported."
  ],
  "setup": [
   "RS-485 on the ESVZAR0 terminal block; terminate the end of the network.",
   "Default 9600 baud, 8 data bits, no parity, 2 stop bits, address 1."
  ],
  "gotchas": [
   "If P494 does not show 1.01, 1.10 or 1.30, Lenze warns not to write any register with this map.",
   "Writes are ignored unless the NET ENABLE terminal is configured and closed."
  ]
 },
 "registers": [
  {
   "table": "holding_register",
   "address": 1,
   "documented": "#1 (4X 40002)",
   "name": "Drive control",
   "description": "Set one bit per write (0x0008 start, 0x0004 stop). Unlock via #48 first.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "Quick stop",
    "1": "Lock security (ends network control)",
    "2": "Stop (per P111)",
    "3": "Start",
    "4": "Inhibit",
    "5": "Network reference off",
    "6": "Set reverse",
    "7": "Set forward",
    "8": "Stop forcing manual reference",
    "9": "Force manual reference (P101)",
    "10": "DC braking on",
    "11": "DC braking off",
    "12": "Network reference select (bits 12-15 enumeration)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "#19 (4X 40020)",
   "name": "Drive family",
   "description": "Reads 72 for SMVector.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "#21 (4X 40022)",
   "name": "Drive size index",
   "description": "Voltage / power rating code (table 7 of the guide).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "#23 (4X 40024)",
   "name": "Drive status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Running (0 = stopped)",
    "1": "Quick stop active",
    "2": "Commanded direction reverse",
    "3": "Actual direction reverse",
    "4": "Network reference sets active source",
    "5": "Network enable active",
    "6": "Closed loop (PID on)",
    "7": "AUTO source",
    "8": "Set point source code bit 0",
    "9": "Set point source code bit 1",
    "10": "Set point source code bit 2",
    "11": "Set point source code bit 3",
    "12": "Control source code bit 0",
    "13": "Control source code bit 1",
    "14": "Network control enabled",
    "15": "DC braking active"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "#24 (4X 40025)",
   "name": "Command frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "#25 (4X 40026)",
   "name": "Actual frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "#26 (4X 40027)",
   "name": "Load (high byte) / run status (low byte)",
   "description": "High byte = load % of rated current; low byte = operational status code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "#27 (4X 40028)",
   "name": "Actual direction (high byte) / control mode (low byte)",
   "description": "High: 0 fwd, 1 rev. Low: 0 local, 1 terminal, 2 remote keypad, 3 net only, 4 net control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "#28 (4X 40029)",
   "name": "Speed source (high byte) / auto-manual (low byte)",
   "description": "High: 0 keypad ... 11 network, 12 jog. Low: 0 manual, 1 auto.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "#29 (4X 40030)",
   "name": "Present fault (high byte) / commanded direction (low byte)",
   "description": "High byte = fault code (see notes). Low: 0 fwd, 1 rev.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "#37 (4X 40038)",
   "name": "Actual PID setpoint",
   "description": "Signed, one decimal.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "#38 (4X 40039)",
   "name": "PID setpoint command",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "#39 (4X 40040)",
   "name": "PID feedback",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "#40 (4X 40041)",
   "name": "Keypad speed command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "#41 (4X 40042)",
   "name": "Keypad PID setpoint command",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "#42 (4X 40043)",
   "name": "Keypad torque command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "#44 (4X 40045)",
   "name": "Network speed command",
   "description": "P102 to P103. Used when the network is the speed reference.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "#46 (4X 40047)",
   "name": "Network torque command",
   "description": "0.0-400.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "#48 (4X 40049)",
   "name": "Unlock controls",
   "description": "0 unlocks register #1; the password (P194, default 225) unlocks all.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "#49 (4X 40050)",
   "name": "Unlock parameters",
   "description": "Password (P194) unlocks all writable registers except #1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "#50 (4X 40051)",
   "name": "Parameter version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "#60 (4X 40061)",
   "name": "Total run time hours",
   "description": "Low word at #60, high word at #61.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "#64 (4X 40065)",
   "name": "Total power-on hours",
   "description": "Low word at #64, high word at #65.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "scale_factor_ref": null,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "#70 (4X 40071)",
   "name": "Network controlled digital output + relay",
   "description": "Needs P140/P142 = 25 (network controlled).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "9": "TB-14 output energized",
    "10": "Relay energized"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "#71 (4X 40072)",
   "name": "Network controlled analog output",
   "description": "Needs P150 = 09 (network controlled).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "#400 (4X 40401)",
   "name": "P400 network protocol",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not active",
    "1": "Remote keypad",
    "2": "Modbus RTU"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "#402 (4X 40403)",
   "name": "P402 module status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not initialized",
    "1": "Init: module to EPM",
    "2": "Init: EPM to module",
    "3": "Online",
    "4": "Failed initialization",
    "5": "Time-out error",
    "6": "Initialization failed",
    "7": "Initialization error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 410,
   "documented": "#410 (4X 40411)",
   "name": "P410 network address",
   "description": "1-247, default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 411,
   "documented": "#411 (4X 40412)",
   "name": "P411 baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "2400",
    "1": "4800",
    "2": "9600 (default)",
    "3": "19200",
    "4": "38400",
    "5": "57600",
    "6": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "#412 (4X 40413)",
   "name": "P412 data format",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "8N2 (default)",
    "1": "8N1",
    "2": "8E1",
    "3": "8O1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 425,
   "documented": "#425 (4X 40426)",
   "name": "P425 network message time-out",
   "description": "0.0-300.0 s, default 10.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 426,
   "documented": "#426 (4X 40427)",
   "name": "P426 time-out action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Not active",
    "1": "Stop (P111)",
    "2": "Quick stop",
    "3": "Inhibit",
    "4": "Trip fault (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 530,
   "documented": "#530 (4X 40531)",
   "name": "P530 terminal and protection status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "Protection status",
    "3": "Fast current limit",
    "4": "Input TB-1",
    "6": "Input TB-13A",
    "7": "Input TB-13B",
    "8": "Input TB-13C",
    "9": "Output TB-14",
    "10": "Relay output",
    "11": "Charge relay",
    "12": "Assertion level switch"
   },
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/lenze/smvector-esvzar0",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}