 "manufacturer": "LG",
 "manufacturer_slug": "lg",
 "model": "PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)",
 "model_slug": "pahcmr000-ahu-comm-kit",
 "short_model": "PAHCMR000",
 "aliases": [
  "PAHCMR000",
  "LG AHU Communication Kit R32",
  "LG AHU comm kit Modbus"
 ],
 "equipment_type": "Air handler DX kit (VRF / split AC gateway built in)",
 "applies_to": "LG PAHCMR000 AHU Communication Kit (R32 and R410A Multi V / single split outdoor units with a PRLK EEV kit), installation manual IM_AHU_Comm_Kit_PAHCMR000_R32_06_26.",
 "summary": "The PAHCMR000 kit lets a third-party air handler use an LG Multi V or single-split outdoor unit, and its RS485 CH1 port talks Modbus RTU directly to a DDC controller. Coils switch the unit and lock wired-controller functions, holding registers set mode, fan speed, target temperature and its limits, and discrete inputs and input registers report compressor, defrost and oil-return status, error code, return-air and coil temperatures.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Points are printed as 00001/10001/30001/40001-style registers together with the function codes for each block (01/05 coils 00001-00008, 02 inputs 10001-10008, 04 input registers 30001-30008, 03/06 holding registers 40001-40010). The wire address is the printed number minus the block base: 40003 is holding register 2."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Communications Kit Installation Manual for LG R32 Air Handler Unit (AHU) - PAHCMR000",
  "doc_number": "IM_AHU_Comm_Kit_PAHCMR000_R32_06_26",
  "revision_date": "2025",
  "url": "https://media.us.lg.com/m/d2725fbeddc5be9/original/IM_AHU_Comm_Kit_PAHCMR000-pdf.pdf",
  "pages": "printed p. 31 (PDF p. 31) Modbus function codes and memory map; p. 10 DIP switch SW1; p. 22 Modbus control overview"
 },
 "notes": [
  "Reserved points (coils 00002 and 00008, inputs 10004-10008, input registers 30003, 30007-30008, holding 40006-40010) are left out.",
  "Access follows the function-code columns of the memory map: coil 00007 (Error) is read with 01 only; the other coils accept 01 and 05. Holding registers accept 03 and 06.",
  "Temperatures are sent multiplied by 10 and cover negative ranges, so they are listed as signed 16-bit.",
  "The manual does not print the data-bit setting; only 9600 bps, no parity and 1 stop bit are stated."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "00001",
   "name": "Operating On/Off",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "00003",
   "name": "All button lock",
   "description": "Locks the LG wired controller keys.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "00004",
   "name": "Mode lock",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "00005",
   "name": "Fan speed lock",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "00006",
   "name": "Target temperature lock",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlock",
    "1": "Lock"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "00007",
   "name": "Error",
   "description": "Read only (function 01).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "10001",
   "name": "Compressor status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "10002",
   "name": "Defrost status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Defrost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "10003",
   "name": "Oil return",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Oil return"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "Error code",
   "description": "LG error code 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "30002",
   "name": "Return air temperature",
   "description": "Range -50 to 100 °C, sent x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "30004",
   "name": "Pipe in temperature",
   "description": "Range -50 to 100 °C, sent x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "30005",
   "name": "Pipe out temperature",
   "description": "Range -50 to 100 °C, sent x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "30006",
   "name": "Capacity",
   "description": "AHU capacity setting, 0-255.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kBtu",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cooling",
    "2": "Fan",
    "4": "Heating"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Low",
    "2": "Middle",
    "3": "High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Target temperature",
   "description": "Range -10 to 100 °C, sent x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Target temperature upper range",
   "description": "15.6-30 °C, sent x10, in 1.0 °C steps.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Target temperature lower range",
   "description": "15.6-30 °C, sent x10, in 1.0 °C steps.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set DIP SW1-2 to ON (communication), wire the DDC to RS485 CH1, then write coil 00001 for on/off and holding registers 40001-40003 for mode, fan and target temperature; read 30002 for return-air temperature and 30001 / coil 00007 for errors.",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 0,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Operation mode"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Target temperature"
   },
   {
    "table": "input_register",
    "address": 1,
    "why": "Return air temperature"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "Error code"
   },
   {
    "table": "discrete_input",
    "address": 0,
    "why": "Compressor status"
   },
   {
    "table": "discrete_input",
    "address": 1,
    "why": "Defrost status"
   }
  ],
  "enable": "DIP switch SW1-2 ON selects control by DDC Modbus (or LG remote / central controllers); OFF selects contact-signal control, where an LG central controller can only monitor.",
  "watchdog": null,
  "quirks": [
   "Operation mode uses 0 = cooling, 2 = fan, 4 = heating (no auto value).",
   "Only function 06 is listed for writing holding registers and 05 for coils."
  ],
  "setup": [
   "RS485 CH1 to the DDC: 2-core 1.0-1.5 mm2 shielded cable, up to 500 m.",
   "9600 bps, no parity, 1 stop bit.",
   "The Modbus slave (sub) address follows the main module address setting described in the manual."
  ],
  "gotchas": [
   "Discharge-air temperature control, forced thermal on/off and capacity control are not available over Modbus with this kit."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/lg/pahcmr000-ahu-comm-kit",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}