 "manufacturer": "LG",
 "manufacturer_slug": "lg",
 "model": "PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)",
 "model_slug": "pahcms000-ahu-comm-kit",
 "short_model": "PAHCMS000",
 "aliases": [
  "PAHCMS000",
  "LG AHU Communication Kit discharge air",
  "LG AHU comm kit PAHCMS000 Modbus"
 ],
 "equipment_type": "Air handler DX kit (VRF / split AC gateway built in)",
 "applies_to": "LG PAHCMS000 AHU Communication Kit for discharge (supply) air control with up to four LG outdoor units, installation manual IM_AHU_Comm_Kit_PAHCMS000_11_23.",
 "summary": "The PAHCMS000 kit connects a third-party air handler to LG Multi V or single-split outdoor units and controls discharge air temperature; a DDC can drive it over Modbus RTU on RS485 CH4. A coil switches the unit, holding registers set mode, capacity request and the cooling and heating discharge targets, and discrete inputs and input registers report unit and per-outdoor-unit (up to 4) run, compressor, defrost and error status, the error code and return/supply air temperatures.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Points are printed as 00001/10001/30001/40001-style registers, with a function-code table per block (01/05 coils 00001-00008, 02 inputs 10001-10030, 04 input registers 30001-30016, 03/06 holding registers 40001-40010). The wire address is the printed number minus the block base: 30011 is input register 10."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Installation Manual for LG Air Handler Unit (AHU) Communications Kit - PAHCMS000",
  "doc_number": "IM_AHU_Comm_Kit_PAHCMS000_11_23",
  "revision_date": "2023-11",
  "url": "https://media.us.lg.com/m/11adf83da67f6527/original/IM_AHU_Comm_Kit_PAHCMS000-pdf.pdf",
  "pages": "pp. 55-56 function codes and memory map; DIP switch SW1 table in the installation section"
 },
 "notes": [
  "Access follows the function-code dots in the memory map: coil 00001 takes 01 and 05, discrete inputs 02 only, input registers 04 only, holding registers 03 and 06.",
  "Reserved points are left out.",
  "The manual does not print the RS485 serial settings for the DDC port; set them to match the kit (the R32 sister kit PAHCMR000 states 9600 bps, no parity, 1 stop bit, but that is a different manual).",
  "Temperatures are sent multiplied by 10; the return/supply air range includes negative values, so they are listed as signed 16-bit.",
  "For the capacity ratio behind register 40002 see the UI7 (0-10 V) capacity table in the manual.",
  "An older revision of this manual (IM_AHU_Comm_Kit_PAHCMS000_5_18) is also hosted by LG."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "00001",
   "name": "Operating On/Off",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "10001",
   "name": "Error status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "10002",
   "name": "Operation status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "10003",
   "name": "Defrost status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Defrost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 10,
   "documented": "10011",
   "name": "ODU#1 operation status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 11,
   "documented": "10012",
   "name": "ODU#1 compressor status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 12,
   "documented": "10013",
   "name": "ODU#1 defrost status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Defrost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 13,
   "documented": "10014",
   "name": "ODU#1 error status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 14,
   "documented": "10015",
   "name": "ODU#2 operation status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 15,
   "documented": "10016",
   "name": "ODU#2 compressor status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 16,
   "documented": "10017",
   "name": "ODU#2 defrost status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Defrost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 17,
   "documented": "10018",
   "name": "ODU#2 error status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 18,
   "documented": "10019",
   "name": "ODU#3 operation status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 19,
   "documented": "10020",
   "name": "ODU#3 compressor status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 20,
   "documented": "10021",
   "name": "ODU#3 defrost status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Defrost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 21,
   "documented": "10022",
   "name": "ODU#3 error status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 22,
   "documented": "10023",
   "name": "ODU#4 operation status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 23,
   "documented": "10024",
   "name": "ODU#4 compressor status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 24,
   "documented": "10025",
   "name": "ODU#4 defrost status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Defrost"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 25,
   "documented": "10026",
   "name": "ODU#4 error status",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal",
    "1": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "Error code",
   "description": "Format 1xxxx: second digit = module number, last three digits = error code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "30011",
   "name": "Return air temperature",
   "description": "Range -50 to 100 °C, sent x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "30013",
   "name": "Supply air temperature",
   "description": "Range -50 to 100 °C, sent x10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cooling",
    "2": "Fan",
    "4": "Heating"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Capacity",
   "description": "Capacity request as a UI7 0-10 V equivalent: 0 or 2.0-10 V, x10, 0.5 V steps.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Cooling target temperature",
   "description": "15.6-30 °C, sent x10, 1.0 °C steps.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Heating target temperature",
   "description": "15.6-30 °C, sent x10, 1.0 °C steps.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "With DIP SW1-1 ON (communication), write coil 00001 for on/off and holding registers 40001, 40003 and 40004 for mode and discharge targets; read 30011/30013 for air temperatures and 10001-10026 for unit and outdoor-unit status.",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 0,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Operation mode"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Cooling discharge target"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Heating discharge target"
   },
   {
    "table": "input_register",
    "address": 12,
    "why": "Supply air temperature"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "Error code"
   },
   {
    "table": "discrete_input",
    "address": 0,
    "why": "Error status"
   },
   {
    "table": "discrete_input",
    "address": 2,
    "why": "Defrost status"
   }
  ],
  "enable": "DIP SW1-1 ON = controlled by DDC through Modbus or an LG central controller (OFF = contact signal, where Modbus control functions are unavailable). SW1-4 ON selects LG central communication over Modbus.",
  "watchdog": null,
  "quirks": [
   "Operation mode uses 0 = cooling, 2 = fan, 4 = heating.",
   "The error code is a decimal number whose second digit is the module number."
  ],
  "setup": [
   "DDC central communication on RS485 CH4, 2-core 18-16 AWG, up to 1640 ft.",
   "The main module address (1-247, needed with an LG central controller) is set with the Set/ESC buttons and the 7-segment display; the manual does not say whether it is also the Modbus slave ID for a DDC."
  ],
  "gotchas": [
   "Control functions are not available when contact-signal control is selected (SW1-1 OFF)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/lg/pahcms000-ahu-comm-kit",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}