 "manufacturer": "LMI",
 "manufacturer_slug": "lmi",
 "model": "Excel XR series electronic metering pump (Modbus RTU)",
 "model_slug": "excel-xr",
 "short_model": "Excel XR",
 "aliases": [
  "Excel XR",
  "LMI Excel XR",
  "Milton Roy Excel XR",
  "Excel XR Modbus"
 ],
 "equipment_type": "Pump (chemical metering pump)",
 "applies_to": "LMI Excel XR electronic metering pumps fitted with the Modbus RTU interface (manual 55312 rev 04).",
 "summary": "The Excel XR is a stepper-driven chemical metering pump from LMI (Milton Roy). Its Modbus RTU version exposes coils for on/off, prime and mode selection, holding registers for flow setpoints and I/O configuration, input registers for live flow, analog I/O and totalizers, and discrete inputs for status and alarms. This map covers the control, live-value and alarm points plus the main mode settings.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Every table says PLC addressing (base 1) is used and lists each point as decimal and hex (holding register 1 = 0x0001). Request address n-1 on the wire: manual flow rate (1) is wire address 0."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Excel XR Series Electronic Metering Pump Modbus RTU Manual",
  "doc_number": "55312 Rev 04",
  "revision_date": "2020-03",
  "url": "https://www.pumpworld.com/assets/lmi-excel-xr-chemical-pump-modbus-manual.pdf",
  "pages": "Settings p. 7; functions p. 8; coils p. 9; holding registers pp. 10-15; input registers pp. 16-17; discrete inputs pp. 17-19",
  "unofficial": true
 },
 "notes": [
  "LMI does not host this manual publicly as far as we could find; the linked copy is the unaltered LMI manual hosted by a distributor (Pumpworld).",
  "Multi-register values: the manual states the first register holds the high-order value, so 32- and 64-bit counters are high word first (ABCD).",
  "Pulse mode volume (13-14) and batch mode volume (17-18) are left out: the manual gives a decimal range for a two-register integer but no scale.",
  "Timed event, RTC, password and stay-prime registers are left out; stay-prime remaining time and weekly event time have no stated units or length conflicts.",
  "Flow values are in GPH or L/h and volumes in gallons or litres depending on the units setting (coil 13 / discrete input 14)."
 ],
 "integration": {
  "summary": "Set slave address, bit rate, parity and stop bits on the pump's Communication Settings screen. Read input register 3 for live flow and discrete inputs 1 and 101 for running and global alarm; set the flow with holding register 1 and start/stop with coil 1.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 2,
    "why": "Current flow rate"
   },
   {
    "table": "input_register",
    "address": 3,
    "why": "Flow percentage"
   },
   {
    "table": "discrete_input",
    "address": 0,
    "why": "Running status"
   },
   {
    "table": "discrete_input",
    "address": 100,
    "why": "Global alarm"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Manual mode flow setpoint"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "On/off toggle"
   },
   {
    "table": "coil",
    "address": 5,
    "why": "Select manual mode"
   }
  ],
  "enable": "Modbus settings are on the pump display under Settings > Communication Settings: slave address 1-125, bit rate 9600/19200/38400/115200 or Auto, parity none/even/odd, 1 or 2 stop bits, internal line termination on/off.",
  "watchdog": null,
  "quirks": [
   "Coil 1 toggles on/off rather than setting a state; read discrete input 1 to know the result.",
   "Flow values are four-digit integers with two implied decimals (1234 = 12.34)."
  ],
  "setup": [
   "With Auto bit rate the pump hunts for the speed, so the first messages may fail; set the rate explicitly when known.",
   "Enable internal termination on the last device on the bus. Connection is an M12 5-pin B-coded connector (pin 2 D0, pin 4 D1, pin 3 DGND)."
  ],
  "gotchas": [
   "Function code 07 (read exception status) and 17 (report server ID) are also supported."
  ]
 },
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "1 (0x0001)",
   "name": "On/Off",
   "description": "Write ON to toggle the pump on/off state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "2 (0x0002)",
   "name": "Prime",
   "description": "ON starts the prime sequence, OFF ends it.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "3 (0x0003)",
   "name": "100 % run",
   "description": "ON runs the pump at 100 %.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "4 (0x0004)",
   "name": "Force internal/external mode",
   "description": "ON forces internal control mode, OFF external.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "5 (0x0005)",
   "name": "Force home screen",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "6 (0x0006)",
   "name": "Manual operation mode",
   "description": "ON selects manual mode.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "7 (0x0007)",
   "name": "Analog operation mode",
   "description": "ON selects analog (mA) mode.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "8 (0x0008)",
   "name": "Pulse operation mode",
   "description": "ON selects pulse mode.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "9 (0x0009)",
   "name": "Batch operation mode",
   "description": "ON selects batch mode.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "10 (0x000A)",
   "name": "Cycle timer operation mode",
   "description": "ON selects cycle timer mode.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "11 (0x000B)",
   "name": "Timed event operation mode",
   "description": "ON selects timed event mode.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "12 (0x000C)",
   "name": "Slow mode",
   "description": "ON enables slow mode.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "13 (0x000D)",
   "name": "Metric/English units",
   "description": "ON = metric, OFF = English units.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "14 (0x000E)",
   "name": "Reset user totalizer",
   "description": "ON resets the user totalizer.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 15,
   "documented": "16 (0x0010)",
   "name": "Start batch",
   "description": "ON starts a batch.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "1 (0x0001)",
   "name": "Running status",
   "description": "1 = running.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "2 (0x0002)",
   "name": "Internal/external operating mode",
   "description": "0 = internal, 1 = external.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "3 (0x0003)",
   "name": "Tank low",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 3,
   "documented": "4 (0x0004)",
   "name": "Tank empty",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "5 (0x0005)",
   "name": "Manual mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "6 (0x0006)",
   "name": "Analog mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "7 (0x0007)",
   "name": "Pulse mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "8 (0x0008)",
   "name": "Batch mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 8,
   "documented": "9 (0x0009)",
   "name": "Cycle timer mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 9,
   "documented": "10 (0x000A)",
   "name": "Timed event mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 10,
   "documented": "11 (0x000B)",
   "name": "100 % mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 11,
   "documented": "12 (0x000C)",
   "name": "Prime mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 12,
   "documented": "13 (0x000D)",
   "name": "Slow mode",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 13,
   "documented": "14 (0x000E)",
   "name": "Metric/English units",
   "description": "0 = English, 1 = metric.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 14,
   "documented": "15 (0x000F)",
   "name": "Pump calibrated",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 15,
   "documented": "16 (0x0010)",
   "name": "Keypad locked",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 16,
   "documented": "17 (0x0011)",
   "name": "Digital output 1",
   "description": "1 = switched.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 17,
   "documented": "18 (0x0012)",
   "name": "Digital output 2",
   "description": "1 = switched.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 18,
   "documented": "19 (0x0013)",
   "name": "Digital input 1",
   "description": "1 = switched.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 19,
   "documented": "20 (0x0014)",
   "name": "Digital input 2",
   "description": "1 = switched.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 20,
   "documented": "21 (0x0015)",
   "name": "Digital input 3",
   "description": "1 = switched.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 21,
   "documented": "22 (0x0016)",
   "name": "Digital input 4",
   "description": "1 = switched.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 23,
   "documented": "24 (0x0018)",
   "name": "Batch mode dosing",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 100,
   "documented": "101 (0x0065)",
   "name": "Global alarm",
   "description": "ON if any alarm is active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 101,
   "documented": "102 (0x0066)",
   "name": "User alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 102,
   "documented": "103 (0x0067)",
   "name": "Tank empty alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 103,
   "documented": "104 (0x0068)",
   "name": "Tank low alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 104,
   "documented": "105 (0x0069)",
   "name": "Internal system error alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 105,
   "documented": "106 (0x006A)",
   "name": "Motor stall alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 106,
   "documented": "107 (0x006B)",
   "name": "Analog loss of signal alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 107,
   "documented": "108 (0x006C)",
   "name": "Analog overrange alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 108,
   "documented": "109 (0x006D)",
   "name": "Motor homing error alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 109,
   "documented": "110 (0x006E)",
   "name": "Pulse signal not present alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 110,
   "documented": "111 (0x006F)",
   "name": "Pulse signal overrange alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "1 (0x0001)",
   "name": "Model ID",
   "description": "Output code for pump size.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "2": "5.6 GPH (21.2 l/h) 175 psi",
    "3": "14.0 GPH (53.0 l/h) 75 psi",
    "4": "18.0 GPH (68.1 l/h) 50 psi"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "3 (0x0003)",
   "name": "Current flow rate",
   "description": "Flow in GPH or L/h (per the units setting), two decimals. 0000-9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "4 (0x0004)",
   "name": "Flow percentage",
   "description": "0.00-100.00 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "5 (0x0005)",
   "name": "Analog input 1",
   "description": "0.0-20.0 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "6 (0x0006)",
   "name": "Analog input 2",
   "description": "0.0-20.0 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "7 (0x0007)",
   "name": "Analog output",
   "description": "0.0-20.0 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "8 (0x0008)",
   "name": "Totalizer user strokes",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "10 (0x000A)",
   "name": "Totalizer user volume",
   "description": "Gallons or litres per the units setting.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 13,
   "documented": "14 (0x000E)",
   "name": "Totalizer user hours",
   "description": "Motor run hours.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "16 (0x0010)",
   "name": "Totalizer user power cycles",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "17 (0x0011)",
   "name": "Totalizer unit strokes",
   "description": "Lifetime count.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "19 (0x0013)",
   "name": "Totalizer unit volume",
   "description": "Lifetime; gallons or litres per the units setting.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "23 (0x0017)",
   "name": "Totalizer unit hours",
   "description": "Lifetime motor run hours.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "25 (0x0019)",
   "name": "Totalizer unit power cycles",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "26 (0x001A)",
   "name": "Calibrated volume",
   "description": "Volume of one stroke from calibration.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "mL",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "27 (0x001B)",
   "name": "Batch mode remaining volume",
   "description": "Gallons or litres per the units setting.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "29 (0x001D)",
   "name": "Batch mode remaining dosing time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "31 (0x001F)",
   "name": "Cycle mode startup delay left",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "33 (0x0021)",
   "name": "Cycle mode run time left",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 39,
   "documented": "40 (0x0028)",
   "name": "Main firmware version",
   "description": "Read as hex digits X.X.X.X.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1 (0x0001)",
   "name": "Flow rate for manual mode",
   "description": "Flow in GPH or L/h (per the units setting), two decimals. 0000-9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2 (0x0002)",
   "name": "Flow rate for prime mode",
   "description": "Flow in GPH or L/h (per the units setting), two decimals.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3 (0x0003)",
   "name": "Prime mode duration",
   "description": "1-3600 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "4 (0x0004)",
   "name": "Power loss mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Resume operation",
    "1": "Stay idle",
    "2": "Run at configured speed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5 (0x0005)",
   "name": "Power loss resume speed",
   "description": "Flow in GPH or L/h (per the units setting), two decimals.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "6 (0x0006)",
   "name": "Slow mode setpoint",
   "description": "10-90 % in steps of 10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "12 (0x000C)",
   "name": "Pulse mode count",
   "description": "Pulses received per delivery, 1-10000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "19 (0x0013)",
   "name": "Batch mode time",
   "description": "Dosing time for batch mode, 1-86400 s.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "24 (0x0018)",
   "name": "Analog mode P1 flow",
   "description": "Flow in GPH or L/h (per the units setting), two decimals.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "25 (0x0019)",
   "name": "Analog mode P1 current",
   "description": "0.0-20.0 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "mA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "26 (0x001A)",
   "name": "Analog mode P2 flow",
   "description": "Flow in GPH or L/h (per the units setting), two decimals.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "27 (0x001B)",
   "name": "Analog mode P2 current",
   "description": "0.0-20.0 mA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "mA",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "28 (0x001C)",
   "name": "Cycle mode cycle time",
   "description": "1-1439 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28,
   "documented": "29 (0x001D)",
   "name": "Cycle mode duration",
   "description": "Inactive period, 1-1439 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "30 (0x001E)",
   "name": "Cycle mode delay",
   "description": "First inactive period before cycling, 0-1439 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "31 (0x001F)",
   "name": "Cycle mode flow",
   "description": "Flow in GPH or L/h (per the units setting), two decimals.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "57 (0x0039)",
   "name": "Digital input 1 config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Remote on/off",
    "2": "Float switch empty",
    "3": "Float switch low",
    "4": "Remote internal/external mode",
    "5": "Pacing pulse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "58 (0x003A)",
   "name": "Digital input 1 contact state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally open",
    "1": "Normally closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "59 (0x003B)",
   "name": "Digital input 2 config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Remote on/off",
    "2": "Float switch empty",
    "3": "Float switch low",
    "4": "Remote internal/external mode",
    "5": "Pacing pulse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "60 (0x003C)",
   "name": "Digital input 2 contact state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally open",
    "1": "Normally closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "61 (0x003D)",
   "name": "Digital input 3 config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Remote on/off",
    "2": "Float switch empty",
    "3": "Float switch low",
    "4": "Remote internal/external mode",
    "5": "Pacing pulse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "62 (0x003E)",
   "name": "Digital input 3 contact state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally open",
    "1": "Normally closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "63 (0x003F)",
   "name": "Digital input 4 config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Remote on/off",
    "2": "Float switch empty",
    "3": "Float switch low",
    "4": "Remote internal/external mode",
    "5": "Pacing pulse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "64 (0x0040)",
   "name": "Digital input 4 contact state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally open",
    "1": "Normally closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "65 (0x0041)",
   "name": "Analog input 1 config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Pacing",
    "2": "Level"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "66 (0x0042)",
   "name": "Analog input 2 config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Pacing",
    "2": "Level"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "67 (0x0043)",
   "name": "Digital output 1 config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Stroke pulse",
    "2": "Pump running",
    "3": "Pump standby",
    "4": "Alarm out",
    "5": "Internal/external mode",
    "6": "User alarm out",
    "7": "Pump stopped",
    "8": "Timed event"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 67,
   "documented": "68 (0x0044)",
   "name": "Digital output 1 contact state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally open",
    "1": "Normally closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 68,
   "documented": "69 (0x0045)",
   "name": "Digital output 2 config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Stroke pulse",
    "2": "Pump running",
    "3": "Pump standby",
    "4": "Alarm out",
    "5": "Internal/external mode",
    "6": "User alarm out",
    "7": "Pump stopped",
    "8": "Timed event"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 69,
   "documented": "70 (0x0046)",
   "name": "Digital output 2 contact state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Normally open",
    "1": "Normally closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "71 (0x0047)",
   "name": "Analog output config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Flow",
    "2": "Mirror input"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 71,
   "documented": "72 (0x0048)",
   "name": "Remote internal mode",
   "description": "Mode used under internal control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Manual",
    "1": "Cycle timer",
    "2": "Weekly timer"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "73 (0x0049)",
   "name": "Remote external mode",
   "description": "Mode used under external control.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "mA",
    "1": "Pulse",
    "2": "Batch"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "74 (0x004A)",
   "name": "Keypad lock style",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "No lock",
    "2": "All lock",
    "3": "All lock, power unlock",
    "4": "All lock, password"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "76 (0x004C)",
   "name": "User alarm mask",
   "description": "Set a bit to route that alarm to the user alarm.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "2": "Tank empty",
    "3": "Tank low",
    "4": "Internal system error",
    "5": "Motor stall",
    "6": "Analog loss of signal",
    "7": "Analog overrange",
    "8": "Motor homing error",
    "9": "Pulse signal not present",
    "10": "Pulse signal overrange"
   },
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/lmi/excel-xr",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}