 "manufacturer": "Lovato Electric",
 "manufacturer_slug": "lovato-electric",
 "model": "ADXL soft starters (Modbus RTU / ASCII / TCP)",
 "model_slug": "adxl-soft-starter",
 "short_model": "ADXL",
 "aliases": [
  "ADXL",
  "ADXL0030600",
  "ADXL0045600",
  "ADXL0060600",
  "ADXL0075600",
  "ADXL0085600",
  "ADXL0115600",
  "ADXL0135600",
  "ADXL0162600",
  "ADXL0195600",
  "ADXL0250600",
  "ADXL0320600",
  "EXC1042"
 ],
 "equipment_type": "Soft starter",
 "applies_to": "ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.",
 "summary": "The Lovato ADXL is a soft starter for three-phase motors. With the optional EXC1042 RS-485 board it answers Modbus RTU or ASCII (the addendum also lists Modbus TCP as a protocol choice). This map covers voltage, currents, powers, power factor, frequency, torque, thermal status, thyristor temperature, I/O bits, the start/stop commands, the command register and the parameter-access selectors.",
 "transport": [
  "RTU",
  "ASCII",
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The tables print hex addresses one higher than the address sent on the wire; the document says to subtract one, and its example reads thyristor temperature (table 0FB2h) by sending 0F B1. Write example: parameter menu 5000h is sent as 4F FF. Addresses here are already reduced by one."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "ADXL soft starter Modbus communication protocol (addendum)",
  "doc_number": "I454IGB03_22",
  "revision_date": "2022-03-28",
  "url": "https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/05.%20SOFT%20STARTER/I454IGB03_22.pdf",
  "pages": "pp. 2-4 (settings, functions, examples), p. 8 (Table 2 measures), p. 9 (Table 3 commands, events, parameter setting)"
 },
 "notes": [
  "Measurements are read with function 03 or 04 (same data); they are listed as input registers. Commands and parameters are written with function 06 only (no function 16 is listed).",
  "Word order: the read example returns 00 00 01 10 for a thyristor temperature of 27.2 °C (272 x 0.1), so the high word comes first (ABCD).",
  "Scales are the divisors printed in the unit column: V/100, A/10000, kW/100000 for phase powers but kW/10000 for total power, PF/10000, Hz/1000, %/10, °C/10.",
  "Left out: the status register F84h (printed as 2 words but 'Unsigned integer', so its width is unclear) and the total active energy at 1B20h (4 words labelled 'Unsigned long'). Function 07 (read exception status) returns a status byte with start/stop input, block, alarm, motor running and bypass bits.",
  "Left out: the 28-register event description text at 5032h (read via the pointer at 5030h).",
  "Parameter access: write the menu (5000h), sub-menu (5001h) and parameter number (5002h), then read or write the value at table address 5004h (wire 5003h); write 5 to 2F03h to save and reboot. 5004h is not listed as a register because the document prints no data format for it. The document recommends a reboot (5 to 2F03h) after commands C11-C14.",
  "Only one communication port can be configured (menu P08)."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 5,
   "documented": "06h",
   "name": "L3-L1 voltage",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "08h",
   "name": "L1 current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "0Ah",
   "name": "L2 current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "0Ch",
   "name": "L3 current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 19,
   "documented": "14h",
   "name": "L1 active power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "16h",
   "name": "L2 active power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 23,
   "documented": "18h",
   "name": "L3 active power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1e-05,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 37,
   "documented": "26h",
   "name": "L1 power factor",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 39,
   "documented": "28h",
   "name": "L2 power factor",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 41,
   "documented": "2Ah",
   "name": "L3 power factor",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 49,
   "documented": "32h",
   "name": "Frequency",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 57,
   "documented": "3Ah",
   "name": "Total active power",
   "description": "Printed as kW/10000 (phase powers are kW/100000).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 63,
   "documented": "40h",
   "name": "Total power factor",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 117,
   "documented": "76h",
   "name": "Max current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.0001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 119,
   "documented": "78h",
   "name": "Torque",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 121,
   "documented": "7Ah",
   "name": "Maximum instantaneous current",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3967,
   "documented": "F80h",
   "name": "Motor hour meter",
   "description": "Printed as h/3600, i.e. the count is in seconds.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3969,
   "documented": "F82h",
   "name": "Start counter",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4015,
   "documented": "FB0h",
   "name": "Motor thermal status",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4017,
   "documented": "FB2h",
   "name": "Thyristor temperature",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8447,
   "documented": "2100h",
   "name": "Inputs 1-3",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input 1",
    "1": "Input 2",
    "2": "Input 3"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8512,
   "documented": "2141h",
   "name": "Outputs 1-3",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Output 1",
    "1": "Output 2",
    "2": "Output 3"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8575,
   "documented": "2180h",
   "name": "Remote variables 1-4",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Remote 1",
    "1": "Remote 2",
    "2": "Remote 3",
    "3": "Remote 4"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8639,
   "documented": "21C0h",
   "name": "Limit thresholds 1-4",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Limit 1",
    "1": "Limit 2",
    "2": "Limit 3",
    "3": "Limit 4"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4097,
   "documented": "1002h",
   "name": "Motor start command",
   "description": "Write 1 to start the motor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4098,
   "documented": "1003h",
   "name": "Motor stop command",
   "description": "Write 1 to stop the motor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12034,
   "documented": "2F03h",
   "name": "Save to flash / reboot",
   "description": "Write 5 to save parameters to flash (also given as the reboot command).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12271,
   "documented": "2FF0h",
   "name": "Command register",
   "description": "Write a command code (function 06).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "C01 Reset maintenance interval",
    "1": "C02 Thermal status reset",
    "2": "C03 Reset start counter",
    "3": "C04 Reset motor hour meter",
    "4": "C05 Reset energy counters",
    "5": "C06 Reset LIM variables with memory",
    "10": "C11 Repeat AUTOSET wizard",
    "11": "C12 Restore factory defaults",
    "12": "C13 Save copy of setup",
    "13": "C14 Restore copy of setup",
    "14": "C15 Test with low power motor",
    "15": "C16 Reset event list"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20479,
   "documented": "5000h",
   "name": "Parameter menu number",
   "description": "Step 1 of parameter access.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20480,
   "documented": "5001h",
   "name": "Parameter sub-menu number",
   "description": "Step 2, if the menu has sub-menus.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20481,
   "documented": "5002h",
   "name": "Parameter number",
   "description": "Step 3: parameter within the menu.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20527,
   "documented": "5030h",
   "name": "Event pointer / counter",
   "description": "High byte = events stored, low byte = last index. Write to select an event.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Fit the EXC1042 RS-485 board, set P08 serial parameters, then read currents (08h-0Dh), total power (3Ah), thermal status (FB0h) and thyristor temperature (FB2h) as big-endian 32-bit values. Start and stop with a 1 written to 1002h and 1003h.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 7,
    "why": "L1 current"
   },
   {
    "table": "input_register",
    "address": 57,
    "why": "Total active power"
   },
   {
    "table": "input_register",
    "address": 4015,
    "why": "Motor thermal status"
   },
   {
    "table": "input_register",
    "address": 4017,
    "why": "Thyristor temperature"
   },
   {
    "table": "input_register",
    "address": 3967,
    "why": "Motor hours (seconds)"
   },
   {
    "table": "holding_register",
    "address": 4097,
    "why": "Start command"
   },
   {
    "table": "holding_register",
    "address": 4098,
    "why": "Stop command"
   }
  ],
  "enable": "Install the EXC1042 RS-485 communication board, then in menu 01-SETUP > P08 COMMUNICATION set node address (08.01), baud rate (08.02), data format (08.03), stop bits (08.04) and protocol (08.05).",
  "watchdog": null,
  "quirks": [
   "Table addresses are one above the wire address.",
   "32-bit values are high word first.",
   "Phase active powers are kW/100000 but total active power is kW/10000."
  ],
  "setup": [
   "Defaults: node 1, 9600 baud, 8 data bits, no parity, 1 stop bit, Modbus RTU.",
   "Data format choices: 8 bit none/odd/even and 7 bit odd/even."
  ],
  "gotchas": [
   "Without the EXC1042 board the soft starter has no Modbus port.",
   "Only function 06 is listed for writes; function 16 is not among the supported functions."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/lovato-electric/adxl-soft-starter",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}