 "manufacturer": "Lumel",
 "manufacturer_slug": "lumel",
 "model": "ND31LITE network parameter meter",
 "model_slug": "nd31lite",
 "short_model": "ND31LITE",
 "aliases": [
  "ND31LITE"
 ],
 "equipment_type": "Power meter (panel network parameter meter)",
 "applies_to": "Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.",
 "summary": "The ND31LITE is a 96x96 panel meter for 3- and 1-phase networks with RS-485 Modbus RTU. Its fixed measurement list is offered as floats in several areas; this map uses the 8000 area (two registers per value, high word first), plus comms settings, status words and the 32-bit energy counters from the 4000/4400 areas.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Addresses are used as printed: the example frames read 7000 as 0x1B58, 6000 as 0x1770 and 4000 as 0x0FA0. Float registers show the table's 6xxx/8xxx pair in 'documented'; this map uses the 8xxx address."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "ND31LITE Network parameter meter - User manual",
  "doc_number": "ND31LITE-09",
  "revision_date": null,
  "url": "https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/ND31Lite/ND31LITE_user_manual.pdf",
  "pages": "Example frames pp. 39-40; Table 12 register areas p. 42; Table 13 configuration and Table 16 status/energy pp. 42-53; Table 18 floats pp. 56-62 (PDF pages)"
 },
 "notes": [
  "Byte order: the area table gives 8000-8970 as bytes 3-2-1-0 and 6000-6970 as 1-0-3-2. The example frames show that 3-2-1-0 means 41 20 00 00 for 10.0 (high word first) and 1-0-3-2 means 00 00 41 20, so the 8000 area is ABCD.",
  "The 7000/7200/7400 areas are a user-programmable group (set in 4200-4259) and are not listed.",
  "Energy counters 4426-4435 follow the manual's formula (high x 65536 + low) / 100.",
  "Left out: 8084 (printed as 'Reactive power averaged (S Demand)' with unit VA, which does not agree), time/date and status floats 8110-8128, the min/max area from 8136, and the alarm/display setup registers.",
  "Frequency (8072) is printed with unit 'f'; it is listed in Hz."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 4100,
   "documented": "4100",
   "name": "Modbus address",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4101,
   "documented": "4101",
   "name": "Transmission mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "8N2",
    "1": "8E1",
    "2": "8O1",
    "3": "8N1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4102,
   "documented": "4102",
   "name": "Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "4800",
    "1": "9600",
    "2": "19200",
    "3": "38400",
    "4": "57600",
    "5": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4104,
   "documented": "4104",
   "name": "Apply transmission settings",
   "description": "Write 1 to make new address/mode/baud take effect.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4403,
   "documented": "4403",
   "name": "Program version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4415,
   "documented": "4415",
   "name": "Status 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "RTC battery used up",
    "5": "Supervisory relay register error",
    "7": "Phase sequence error",
    "8": "Energy value error",
    "9": "Programmable readout group register error",
    "10": "Display screen register error",
    "11": "Configuration register error",
    "13": "Output not calibrated",
    "14": "Input not calibrated",
    "15": "FRAM memory damage"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4416,
   "documented": "4416",
   "name": "Status 2 (alarms)",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Alarm 1 active",
    "4": "Alarm 1 signalled",
    "8": "Alarm 2 active",
    "12": "Alarm 2 signalled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4426,
   "documented": "4426-4427",
   "name": "Active import energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4428,
   "documented": "4428-4429",
   "name": "Active export energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4430,
   "documented": "4430-4431",
   "name": "Reactive inductive energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4432,
   "documented": "4432-4433",
   "name": "Reactive capacitive energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4434,
   "documented": "4434-4435",
   "name": "Apparent energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8000,
   "documented": "6000/8000",
   "name": "L1 phase voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8002,
   "documented": "6002/8002",
   "name": "L1 phase current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8004,
   "documented": "6004/8004",
   "name": "L1 phase active power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8006,
   "documented": "6006/8006",
   "name": "L1 phase reactive power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8008,
   "documented": "6008/8008",
   "name": "L1 phase apparent power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8010,
   "documented": "6010/8010",
   "name": "L1 power factor (P1/S1)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8012,
   "documented": "6012/8012",
   "name": "L1 tg phi (Q1/P1)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8014,
   "documented": "6014/8014",
   "name": "THD U1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8016,
   "documented": "6016/8016",
   "name": "THD I1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8018,
   "documented": "6018/8018",
   "name": "L2 phase voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8020,
   "documented": "6020/8020",
   "name": "L2 phase current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8022,
   "documented": "6022/8022",
   "name": "L2 phase active power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8024,
   "documented": "6024/8024",
   "name": "L2 phase reactive power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8026,
   "documented": "6026/8026",
   "name": "L2 phase apparent power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8028,
   "documented": "6028/8028",
   "name": "L2 power factor (P2/S2)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8030,
   "documented": "6030/8030",
   "name": "L2 tg phi (Q2/P2)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8032,
   "documented": "6032/8032",
   "name": "THD U2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8034,
   "documented": "6034/8034",
   "name": "THD I2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8036,
   "documented": "6036/8036",
   "name": "L3 phase voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8038,
   "documented": "6038/8038",
   "name": "L3 phase current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8040,
   "documented": "6040/8040",
   "name": "L3 phase active power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8042,
   "documented": "6042/8042",
   "name": "L3 phase reactive power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8044,
   "documented": "6044/8044",
   "name": "L3 phase apparent power",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8046,
   "documented": "6046/8046",
   "name": "L3 power factor (P3/S3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8048,
   "documented": "6048/8048",
   "name": "L3 tg phi (Q3/P3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8050,
   "documented": "6050/8050",
   "name": "THD U3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8052,
   "documented": "6052/8052",
   "name": "THD I3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8054,
   "documented": "6054/8054",
   "name": "Mean 3-phase voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8056,
   "documented": "6056/8056",
   "name": "Mean 3-phase current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8058,
   "documented": "6058/8058",
   "name": "3-phase active power (P1+P2+P3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8060,
   "documented": "6060/8060",
   "name": "3-phase reactive power (Q1+Q2+Q3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8062,
   "documented": "6062/8062",
   "name": "3-phase apparent power (S1+S2+S3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8064,
   "documented": "6064/8064",
   "name": "3-phase power factor (P/S)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8066,
   "documented": "6066/8066",
   "name": "Mean 3-phase tg phi (Q/P)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8068,
   "documented": "6068/8068",
   "name": "Mean 3-phase THD U",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8070,
   "documented": "6070/8070",
   "name": "THD I mean 3-phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8072,
   "documented": "6072/8072",
   "name": "Frequency",
   "description": "Unit printed as 'f' in the table.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8074,
   "documented": "6074/8074",
   "name": "Phase-to-phase voltage L 1-2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8076,
   "documented": "6076/8076",
   "name": "Phase-to-phase voltage L 2-3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8078,
   "documented": "6078/8078",
   "name": "Phase-to-phase voltage L 3-1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8080,
   "documented": "6080/8080",
   "name": "Mean phase-to-phase voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8082,
   "documented": "6082/8082",
   "name": "Active power averaged (P Demand)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8086,
   "documented": "6086/8086",
   "name": "Current averaged (I Demand)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8088,
   "documented": "6088/8088",
   "name": "Neutral wire current (calculated from vectors)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8090,
   "documented": "6090/8090",
   "name": "Active import energy overflows",
   "description": "Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8092,
   "documented": "6092/8092",
   "name": "Active import energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8094,
   "documented": "6094/8094",
   "name": "Active export energy overflows",
   "description": "Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8096,
   "documented": "6096/8096",
   "name": "Active export energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8098,
   "documented": "6098/8098",
   "name": "Reactive inductive energy overflows",
   "description": "Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 Mvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8100,
   "documented": "6100/8100",
   "name": "Reactive inductive energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8102,
   "documented": "6102/8102",
   "name": "Reactive capacitive energy overflows",
   "description": "Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 Mvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8104,
   "documented": "6104/8104",
   "name": "Reactive capacitive energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8106,
   "documented": "6106/8106",
   "name": "Apparent energy overflows",
   "description": "Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 MVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8108,
   "documented": "6108/8108",
   "name": "Apparent energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers from 8000 (function 03 or 04): 3 x 9 per-phase values, then 3-phase totals at 8054-8066, frequency at 8072 and energies from 8090. Floats are high word first in the 8000 area.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8000,
    "why": "L1 voltage"
   },
   {
    "table": "holding_register",
    "address": 8002,
    "why": "L1 current"
   },
   {
    "table": "holding_register",
    "address": 8058,
    "why": "3-phase active power"
   },
   {
    "table": "holding_register",
    "address": 8064,
    "why": "3-phase power factor"
   },
   {
    "table": "holding_register",
    "address": 8072,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 4426,
    "why": "Active import energy counter"
   },
   {
    "table": "holding_register",
    "address": 4415,
    "why": "Status 1"
   }
  ],
  "enable": "Modbus RTU is always on; set address, mode and baud from the menu or registers 4100-4102, then write 1 to 4104.",
  "watchdog": null,
  "quirks": [
   "The 6000 area is low word first and the 8000 area high word first.",
   "Powers are in W, var and VA."
  ],
  "setup": [
   "Factory settings: address 1, 9600 baud, RTU 8N2."
  ],
  "gotchas": [
   "7000-7118 is not a fixed map on this meter: it returns whatever was programmed in 4200-4259."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/lumel/nd31lite",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}