 "manufacturer": "Lumel",
 "manufacturer_slug": "lumel",
 "model": "NR30 DIN-rail power network meter",
 "model_slug": "nr30",
 "short_model": "NR30",
 "aliases": [
  "NR30"
 ],
 "equipment_type": "Power meter (DIN-rail network meter)",
 "applies_to": "Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.",
 "summary": "The NR30 is a DIN-rail 3-phase power network meter with RS-485 Modbus RTU and, in Ethernet versions, Modbus TCP. Its fixed measurement list is offered as floats in several areas; this map uses the 8000 area (two registers per value, high word first), plus comms settings, the status word and 32-bit energy counters.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "0-based",
  "note": "Addresses are used as printed: the example frames read 7000 as 0x1B58 and 6000 as 0x1770. Float registers show the table's 6xxx/8xxx pair in 'documented'; this map uses the 8xxx address."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "NR30 Rail mounted power network meter - User's manual",
  "doc_number": "NR30-09E_R1",
  "revision_date": null,
  "url": "https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/NR30/NR30_service_manual.pdf",
  "pages": "Example frames around PDF p. 31; register area table PDF p. 34; configuration and status/energy tables PDF pp. 41-52; Table 21 floats PDF pp. 55-60"
 },
 "notes": [
  "Byte order: the area table gives 8000-8970 as bytes 3-2-1-0 and 6000-6970 as 1-0-3-2; example 2 returns 41 20 00 00 (10.0) for a 3-2-1-0 area and example 3 returns 00 00 41 20 for the 6000 area, so the 8000 area is high word first (ABCD).",
  "The 7000/7200/7400 areas are a user-programmable group (set in 4200-4259) and are not listed.",
  "Energy counters 4426-4435 follow the manual's formula (high x 65536 + low) / 100.",
  "Left out: 4101 transmission mode (its row could not be read cleanly), time/date and status floats 8110-8128, the min/max area from 8136, and the alarm, MQTT and display setup registers.",
  "Frequency (8072) is printed with unit 'f'; it is listed in Hz."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 4100,
   "documented": "4100",
   "name": "Modbus address",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4102,
   "documented": "4102",
   "name": "Baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "4800",
    "1": "9600",
    "2": "19200",
    "3": "38400",
    "4": "57600",
    "5": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4104,
   "documented": "4104",
   "name": "Apply transmission settings",
   "description": "Write 1 to make new address/mode/baud take effect.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4403,
   "documented": "4403",
   "name": "Program version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4415,
   "documented": "4415",
   "name": "Status register 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "RTC battery used up",
    "2": "Ethernet and internal memory present",
    "5": "Supervisory relay register error",
    "6": "MQTT register error",
    "7": "Phase sequence error",
    "8": "Energy value error",
    "9": "Programmable readout group register error",
    "10": "Display page register error",
    "11": "Configuration register error",
    "14": "No input calibration",
    "15": "FRAM memory corruption"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4426,
   "documented": "4426-4427",
   "name": "Active import energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4428,
   "documented": "4428-4429",
   "name": "Active export energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4430,
   "documented": "4430-4431",
   "name": "Reactive inductive energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4432,
   "documented": "4432-4433",
   "name": "Reactive capacitive energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4434,
   "documented": "4434-4435",
   "name": "Apparent energy (counter)",
   "description": "High register x 65536 + low register, in 0.01 units.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8000,
   "documented": "6000/8000",
   "name": "Voltage of L1 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8002,
   "documented": "6002/8002",
   "name": "Current of L1 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8004,
   "documented": "6004/8004",
   "name": "Active power of L1 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8006,
   "documented": "6006/8006",
   "name": "Reactive power of L1 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8008,
   "documented": "6008/8008",
   "name": "Apparent power of L1 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8010,
   "documented": "6010/8010",
   "name": "L1 power factor (P1/S1)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8012,
   "documented": "6012/8012",
   "name": "L1 tg phi (Q1/P1)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8014,
   "documented": "6014/8014",
   "name": "THD U1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8016,
   "documented": "6016/8016",
   "name": "THD I1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8018,
   "documented": "6018/8018",
   "name": "Voltage of L2 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8020,
   "documented": "6020/8020",
   "name": "Current of L2 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8022,
   "documented": "6022/8022",
   "name": "Active power of L2 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8024,
   "documented": "6024/8024",
   "name": "Reactive power of L2 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8026,
   "documented": "6026/8026",
   "name": "Apparent power of L2 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8028,
   "documented": "6028/8028",
   "name": "L2 power factor (P2/S2)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8030,
   "documented": "6030/8030",
   "name": "L2 tg phi (Q2/P2)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8032,
   "documented": "6032/8032",
   "name": "THD U2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8034,
   "documented": "6034/8034",
   "name": "THD I2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8036,
   "documented": "6036/8036",
   "name": "Voltage of L3 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8038,
   "documented": "6038/8038",
   "name": "Current of L3 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8040,
   "documented": "6040/8040",
   "name": "Active power of L3 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8042,
   "documented": "6042/8042",
   "name": "Reactive power of L3 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8044,
   "documented": "6044/8044",
   "name": "Apparent power of L3 phase",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8046,
   "documented": "6046/8046",
   "name": "L3 power factor (P3/S3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8048,
   "documented": "6048/8048",
   "name": "L3 tg phi (Q3/P3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8050,
   "documented": "6050/8050",
   "name": "THD U3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8052,
   "documented": "6052/8052",
   "name": "THD I3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8054,
   "documented": "6054/8054",
   "name": "Average 3-phase voltage",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8056,
   "documented": "6056/8056",
   "name": "Average 3-phase current",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8058,
   "documented": "6058/8058",
   "name": "3-phase active power (P1+P2+P3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8060,
   "documented": "6060/8060",
   "name": "3-phase reactive power (Q1+Q2+Q3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8062,
   "documented": "6062/8062",
   "name": "3-phase apparent power (S1+S2+S3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8064,
   "documented": "6064/8064",
   "name": "3-phase power factor (P/S)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8066,
   "documented": "6066/8066",
   "name": "Mean 3-phase tg phi (Q/P)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8068,
   "documented": "6068/8068",
   "name": "Mean 3-phase THD U",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8070,
   "documented": "6070/8070",
   "name": "Mean 3-phase THD I",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8072,
   "documented": "6072/8072",
   "name": "Frequency",
   "description": "Unit printed as 'f' in the table.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8074,
   "documented": "6074/8074",
   "name": "Phase-to-phase voltage L1-2",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8076,
   "documented": "6076/8076",
   "name": "Phase-to-phase voltage L2-3",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8078,
   "documented": "6078/8078",
   "name": "Phase-to-phase voltage L3-1",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8080,
   "documented": "6080/8080",
   "name": "Average phase-to-phase voltage",
   "description": "Printed as 'Average phase-to-phase voltage L1-2'.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8082,
   "documented": "6082/8082",
   "name": "Averaged active power (P demand)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8084,
   "documented": "6084/8084",
   "name": "Averaged apparent power (S demand)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8086,
   "documented": "6086/8086",
   "name": "Averaged current (I demand)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8088,
   "documented": "6088/8088",
   "name": "Current in neutral wire (calculated from vectors)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8090,
   "documented": "6090/8090",
   "name": "Active import energy overflows",
   "description": "Counts roll-overs of the next register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8092,
   "documented": "6092/8092",
   "name": "Active import energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8094,
   "documented": "6094/8094",
   "name": "Active export energy overflows",
   "description": "Counts roll-overs of the next register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8096,
   "documented": "6096/8096",
   "name": "Active export energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8098,
   "documented": "6098/8098",
   "name": "Reactive inductive energy overflows",
   "description": "Counts roll-overs of the next register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 Mvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8100,
   "documented": "6100/8100",
   "name": "Reactive inductive energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8102,
   "documented": "6102/8102",
   "name": "Reactive capacitive energy overflows",
   "description": "Counts roll-overs of the next register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 Mvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8104,
   "documented": "6104/8104",
   "name": "Reactive capacitive energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8106,
   "documented": "6106/8106",
   "name": "Apparent energy overflows",
   "description": "Counts roll-overs of the next register.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "100 MVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8108,
   "documented": "6108/8108",
   "name": "Apparent energy",
   "description": "Counter up to 99999.99; add the overflow register for the full total.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read holding registers from 8000: per-phase values, then 3-phase totals at 8054-8066, frequency at 8072 and energies from 8090. Floats are high word first in the 8000 area.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8000,
    "why": "L1 voltage"
   },
   {
    "table": "holding_register",
    "address": 8002,
    "why": "L1 current"
   },
   {
    "table": "holding_register",
    "address": 8058,
    "why": "3-phase active power"
   },
   {
    "table": "holding_register",
    "address": 8064,
    "why": "3-phase power factor"
   },
   {
    "table": "holding_register",
    "address": 8072,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 4426,
    "why": "Active import energy counter"
   },
   {
    "table": "holding_register",
    "address": 4415,
    "why": "Status 1"
   }
  ],
  "enable": "Modbus RTU is always on; set address and baud from the menu or registers 4100-4102, then write 1 to 4104.",
  "watchdog": null,
  "quirks": [
   "The 6000 area is low word first and the 8000 area high word first.",
   "Powers are in W, var and VA."
  ],
  "setup": [
   "Factory settings: address 1, 9600 baud, RTU 8N2.",
   "Modbus TCP: unit address in 4146 (default 1), port in 4147 (default 502), idle close time 4145 (60 s), up to 4 connections (4144)."
  ],
  "gotchas": [
   "7000-7118 returns whatever was programmed in 4200-4259, not a fixed list."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/lumel/nr30",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}